Laserfiche WebLink
Victaullc9 FireLock Model FL-(UK/G <br /> Standard Coverage, Quick Response ✓ctauIic° <br /> Concealed Pendent Sprinklers, K5.6 (8.1) 41.03 <br /> 1.0 PRODUCT DESCRIPTION <br /> QUICK RESPONSE CONCEALED PENDENT SPRINKLERS <br /> SIN V5606 V3802 V3808 <br /> ORIENTATION Concealed Pendent Concealed Pendent Concealed Pendent <br /> K-FACTOR1 5.6 lmp./8.1 S.I. 5.6 lmp./8.1 S.I. 5.6 lmp./8.1 S.I. <br /> CONNECTION 1/2"NPT/15mm BSPT '"NPT/15mm BSPT 1/2"NPT/15mm BSPT <br /> MAX.WORKING PRESSURE 175 psi(1200 kPa) 175 psi(1200 kPa) 300psi(2068 kPa) <br /> ESCUTCHEON Concealed Concealed Concealed <br /> GLOBE RE-DESIGNATED GL5606 <br /> GLOBE EQUIVALENT GL5604 GL5605 <br /> AVAILABLE WRENCHES <br /> SPRINKLER 1"ADJ Concealed V38 Concealed V38 Concealed <br /> PENDENT ■ ■ ■ <br /> CLEAN ROOM GASKET <br /> SPRINKLER 1"ADJ Concealed V38 Concealed V38 Concealed <br /> PENDENT ■ ■ <br /> Factory Hydrostatic Test: 100% @ 500 psi/3447 kPa/34 bar <br /> Min. Operating Pressure: UL/FM: 7psi/48 kPa/.5 bar <br /> Temperature Rating: See tables in section 2.0 <br /> - For K-Factor when pressure is measured in bar,multiply S.I.units by 10.0. <br /> ALWAYS REFER TO ANY NOTIFICATIONS AT THE END OF THIS DOCUMENT REGARDING PRODUCT INSTALLATION,MAINTENANCE OR SUPPORT.-1 <br /> victaulic.com <br /> 41.03 16369 Rev B Updated 04/2021 ©2021 Victaulic Company.All rights reserved. <br /> 1 .ctaul.c° <br />