HVAC LEGEND: ABBREVIATIONS: GENERAL NOTES: GENERAL HVAC NOTES: <br /> F -t THERMOSTAT LINE AC AIR CONDITIONING IMC INTERNATIONAL MECHANICAL CODE 1. COMPLETE INSTALLATION OF THE MECHANICAL SYSTEM SHALL BE PER THE LATEST ADOPTED VERSION OF INTERNATIONAL 1. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK(HVAC)ARE DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND <br /> RISE ACF AIR CURTAIN FAN IPC INTERNATIONAL PLUMBING CODE BUILDING CODE(IBC),INTERNATIONAL MECHANICAL CODE(IMC),WASHINGTON STATE ENERGY CODE(WSEC),INTERNATIONAL GENERAL ARRANGEMENT ONLY. - Q <br /> F__ RISE DIRECTION OF RISE FOR DUCT ADA AMERICAN DISABILITIES ACT ID INDIRECT DRAIN PLUMBING CODE(UPC),INTERNATIONAL FUEL GAS CODE(IFGC),INTERNATIONAL FIRE CODE(IFC),NFPA AND HEALTH CODES AND E <br /> AN ADJUSTABLE IE INVERT ELEVATION REGULATIONS AS ADOPTED BY THE LOCAL JURISDICTIONS. U EO <br /> 2 INSTALL ALL DUCT MOUNTED SENSING AND CONTROL DEVICES IN LOCATIONS WITH STRAIGHT SECTION OF DUCT UP AND 0 <br /> 24x12 DUCT(FIRST FIGURE DENOTES VIEW SHOWN) AFF ABOVE FINISHED FLOOR IN INCH DOWNSTREAM AS RECOMMENDED BY THE MANUFACTURER FOR GOOD ACCURACY AND ACCESSIBILITY. •_ <br /> AL ACOUSTIC LINED INSUL INSULATE;INSULATION <br /> ALIGN ALIGNMENT 2. CONTRACTOR SHALL COORDINATE DIFFUSER,GRILLE AND REGISTER LOCATIONS AND DUCT ROUTING CLEARANCES WITH THE f13 v <br /> 10x8 SINGLE LINE DUCTWORK INDICATES DUCT STRUCTURAL,REFLECTED CEILING AND LIGHTING PLANS. a--� <br /> 24x12 WITH VIEW DIMENSION LESS THAN 12 INCHES AP ACCESS PANEL KW KILOWATT 3. COORDINATE AND PROVIDE ALL DUCT TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT. N O <br /> APPROX APPROXIMATELY KWH KILOWATTHOUR FIELD VERIFY AND COORDINATE ALL DUCT DIMENSIONS BEFORE FABRICATION. J <br /> ARCH ARCHITECTURAL 3. MAKE ACCEPTABLE ACCESS PROVISIONS FOR REMOVAL OF FILTER AND MAINTENANCE AND SERVICE FOR ALL MECHANICAL <br /> ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS L LENGTH EQUIPMENT AND UNITS.REFER TO MANUFACTURER'S INSTALLATION GUIDE. 4J <br /> 4. ALL EQUIPMENT,DUCTWORK,ETC.,SHALL BE SUPPORTED REQUIRED TO PROVIDE A VIBRATION FREE INSTALLATION,AND <br /> DUCT TAKEOFF AVG AVERAGE LAT LEAVING AIR TEMPERATURE SEISMICALLY BRACED AS REQUIRED.PROVIDE VIBRATION ISOLATION <br /> ATION FOR ALL MECHANICAL EQUIPMENT TO PREVENT TRANSMISSION <br /> LB POUNDS 4. ALL CONTROL WIRE AND CONDUIT SHALL COMPLY WITH THE NATIONAL ELECTRIC CODE. OF VIBRATION TO BUILDING STRUCTURE. N <br /> --I--�� BAS BUILDING AUTOMATION SYSTEM LF LINEAL FOOT r , <br /> SUPPLY DUCT TURNING TOWARD,UP BFF BELOW FINISH FLOOR LVG LEAVING `/ Q <br /> 1-�- BHP BRAKE HORSEPOWER 5. THE LOCATIONS OF ALL ITEMS SHOWN ON THE DRAWINGS OR CALLED FOR IN THE DOCUMENTS THAT ARE NOT DEFINITELY FIXED 5. CERTAIN ITEMS SUCH AS RISES AND DROPS IN DUCTWORK,ACCESS DOORS,VOLUME DAMPERS,ETC.ARE INDICATED ON THE ^ V <br /> BLDG BUILDING MA MIXED AIR BY DIMENSIONS ARE APPROXIMATE ONLY.THE EXACT LOCATIONS NECESSARY TO SECURE THE BEST CONDITIONS AND RESULTS CONTRACT DOCUMENT DRAWINGS FOR CLARITY FOR A SPECIFIC LOCATION REQUIREMENT AND SHALL NOT BE INTERPRETED AS <br /> ] SUPPLY DUCT TURNING AWAY THE EXTENT OF THE REQUIREMENTS FOR THESE ITEMS. W <br /> BOD BOTTOM OF DUCT MAX MAXIMUM MUST BE DETERMINED BY THE PROJECT SITE CONDITIONS AND SHALL HAVE THE APPROVAL OF THE PROJECT MANAGER BEFORE 92BOP BOTTOM OF PIPE MBH;MBUH THOUSAND BRITISH THERMAL UNITS PER HOUR BEING INSTALLED.DO NOT SCALE DRAWINGS. <br /> BTU BRITISH THERMAL UNIT MCA MINIMUM CIRCUIT AMPACITY . <br /> RETURN DUCT TURNING TOWARD,UP 6. UNLESS OTHERWISE SHOWN,LOCATE ALL ROOM THERMOSTATS 4'-0"(CENTERLINE)ABOVE FINISHED FLOOR.NOTIFY THE PROJECT U._ <br /> IIII--------����� BTUH BRITISH THERMAL UNITS PER HOUR MCC MOTOR CONTROL CENTER MANAGER OF ANY ROOMS WHERE THE ABOVE LOCATION CANNOT BE MAINTAINED OR WHERE THERE IS A QUESTION ON LOCATION. <br /> BV BALANCING VALVE MD MOTORIZED DAMPER 6. ALL ROOF PENETRATIONS SHALL S MINIMUM OF 5 FEET AWAY FROM THE AREA/OCCUPATION SEPARATION WALLS.ALL PIPE, � <br /> EXHAUST DUCT TURNING AWAY MECH MECHANICAL DUCT AND CONDUIT PENETRATIONS THROUGH RATED ASSEMBLIES SHALL BE FIRE AND SMOKE STOPPED PER CODE. �J <br /> CD CEILING DIFFUSER MFR MANUFACTURER 7. ALL DUCTWORK SHALL CLEAR DOORS AND WINDOWS. CD'% <br /> CFM CUBIC FEET PER MINUTE MIN MINIMUM;MINUTE 7. ALL EQUIPMENT,DAMPERS,PIPING,AND ACCESSORIES IN CONCEALED SPACES REQUIRING ACCESS SHALL HAVE ACCESS DOORS. <br /> EXHAUST DUCT TURNING TOWARD,UP CG CEILING GRILLE MISC MISCELLANEOUS ALL ACCESS DOORS IN FIRE RATED STRUCTURE SHALL BE FIRE RATED.COORDINATE LOCATIONS WITH 8. UNLESS OTHERWISE NOTED,ALL DUCTWORK IS OVERHEAD,TIGHT TO THE UNDERSIDE OF THE STRUCTURE(WITHIN TRUSSES),WITH <br /> CI CAST IRON MTD MOUNTED ARCHITECT/OWNER/CONTRACTOR TO PROVIDE ACCESS DOORS. SPACE FOR INSULATION IF REQUIRED. u <br /> -<� RETURN DUCT TURNING AWAY CENTERLINE MTG MOUNTING <br /> CLG CEILING 8. ALL EQUIPMENT SHALL BE FREE FROM DEFECTS IN MATERIAL,WORKMANSHIP,AND SHALL BE OF THE KIND AND QUALITY 9. MAXIMUM LENGTH OF FLEXIBLE DUCTS SHALL BE AS CODE PERMITS. <br /> �J CO CLEANOUT N.C. NORMALLY CLOSED DESCRIBED HEREIN. m <br /> ROUND DUCT TURNING TOWARD,UP CONN CONNECT;CONNECTED;CONNECTION N.O. NORMALLY OPEN <br /> CONST CONSTRUCTION NO NOISE CRITERIA 10. ALL DUCTWORK SHALL BE COORDINATED WITH ALL TRADES INVOLVED,OFFSETS IN DUCTS,INCLUDING DIVIDED DUCTS AND <br /> J ROUND DUCT TURNING AWAY CONT CONTINUOUS;CONTINUATION NIC NOT IN CONTRACT 9. ALL EQUIPMENT SHALL BE APPROVED FOR INSTALLATION IN THE STATE OF WASHINGTON AND SHALL HAVE ALL CERTIFICATIONS TRANSITIONS AROUND OBSTRUCTIONS. <br /> COOED COORDINATE NTS NOT TO SCALE AND RATINGS REQUIRED TO MEET ALL ENERGY,POLLUTION,ENVIRONMENTAL,SEISMIC,ETC.CODES AND REGULATIONS. <br /> F___0 OVAL DUCT TURNING TOWARD,UP CORR CORRIDOR 3132 N.E.133 ST <br /> 11. PROVIDE ACCESS DOORS IN DUCTWORK TO PROVIDE ACCESS FOR ALL VOLUME DAMPERS AND OTHER ITEMS LOCATED IN THE <br /> Cu CONDENSING UNIT OAT OUTSIDE AIR TEMP 10. VERIFY ALL THE MECHANICAL EQUIPMENT'S ELECTRICAL LOADS VOLTAGE/PHASE,ETC.WITH ELECTRICAL CONTRACTOR PRIOR TO Seattle,Washington 981254423 <br /> J OVAL DUCT TURNING AWAY <br /> CU FT CUBIC FEET OD OUTSIDE DIAMETER ORDERING. DUCTWORK WHICH REQUIRE SERVICE AND/OR INSPECTION. PO Box 27073 <br /> CU IN CUBIC INCHES OH OVERHEAD <br /> Battle,Washington 98165-1473 <br /> OA OUTSIDE AIR 12. ALL AIR DISTRIBUTION SUPPLY OUTLETS SHALL HAVE VOLUME CONTROL DEVICES. (206)367-2500 <br /> DB DRY BULB TEMPERATURE 11. WHERE MULTIPLE RISERS OR HORIZONTAL LOOPS ARE USED,BALANCING VALVES IN THE RETURN LINES ARE REQUIRED.A CHECK Fax(206)368-6856 <br /> I w CONICAL WYE VALVE SHALL BE PROVIDED IN EACH RETURN TO PREVENT TEMPORARY REVERSAL OF FLOW. <br /> DEG DEGREE P PUMP PSRMEML809C6 <br /> DET DETAIL PD PRESSURE DROP 13. ALL 90 DEGREE TRUNK DUCT ELBOWS SHALL BE SMOOTH-ROUND OR SQUARE WITH TURNING VANES. <br /> I Z a CONICAL TEE CIA DIAMETER P PHASE 12. COORDINATE CONSTRUCTION OF ALL MECHANICAL WORK WITH ARCHITECTURAL,STRUCTURAL,ELECTRICAL WORK,ETC.,SHOWN ON <br /> DIFF DIFFERENTIAL R PROPERTY LINE CONTRACT DOCUMENT DRAWINGS.LOCATIONS AND SIZES OF ALL FLOOR,WALL,AND ROOF OPENINGS SHALL BE COORDINATED 14. ALL FAN SYSTEMS WITH OVER 2000 CFM SHALL HAVE DUCT SMOKE DETECTORS IN THE RETURN AIR STREAM TO DISABLE FAN <br /> �I VOLUME DAMPER(VD) DIM DIMENSION POC POINT OF CONNECTION WITH ALL OTHER TRADES INVOLVED. UPON SMOKE DETECTION DETECTION.DUCT SMOKE DETECTORS ARE NOT REQUIRED IN THE RETURN AIR STREAM WHERE ALL <br /> CISCH DISCHARGE PRELIM PRELIMINARY PORTIONS OF THE BUILDING SERVED BY THE AIR DISTRIBUTION SYSTEM ARE PROTECTED BY AREA SMOKE DETECTORS CONNECTED <br /> ON DOWN PRES PRESSURE TO A FIRE ALARM SYSTEM IN ACCORDANCE WITH THE INTERNATIONAL FIRE CODE.THE AREA SMOKE DETECTION SYSTEM SHALL <br /> ♦ FIRE SMOKE DAMPER(FSD) 13. ALL TESTS SHALL BE COMPLETED BEFORE ANY MECHANICAL EQUIPMENT OR PIPING INSULATION IS APPLIED. <br /> DR DRAIN PRV PRESSURE REDUCING VALVE COMPLY WITH SECTION 606.4 OF THE IMC.DUCT/SMOKE DETECTORS SHALL BE LISTED BY AN APPROVED AGENCY AND FOR <br /> FIRE DAMPER(FD) DSD DUCT SMOKE DETECTOR PSI POUNDS PER SQUARE INCH INSTALLATION IN AIR DUCTS PER IMC SECTION 606. Z <br /> OWG DRAWING PSIG POUNDS PER SQUARE INCH GAGE 14, WHERE TWO OR MORE ITEMS OF THE SAME TYPE OF EQUIPMENT ARE REQUIRED,THE PRODUCT OF ONE MANUFACTURER SHALL W <br /> MOTORIZED DAMPER(FD) BE USED. 15. ALL MECHANICAL HEATING AND VENTILATION EQUIPMENT SHALL CONFORM TO SMACNA,LOCAL AND STATE REGULATIONS FOR 0 <br /> EA EACH RA RETURN AIR SEISMIC RESTRAINT(INCLUDING PIPING AND DUCTWORK). Q W Z <br /> EAT ENTERING AIR TEMPERATURE RECIRC RECIRCULATING 15. REFER TO TYPICAL DETAILS FOR DUCTWORK,PIPING,AND EQUIPMENT INSTALLATION. <br /> --------------- <br /> DOUBLE LINE,LINED DUCT/ACOUSTIC DUCT EF EXHAUST FAN RECT RECTANGULAR z U Q <br /> EFF EFFICIENCY REF REFERENCE <br /> 16. ALL RECTANGULAR DUCTWORK SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS. <br /> J <br /> EG EXHAUST GRILLE REG REGULATOR 16. RECORD DRAWINGS SHALL BE PROVIDED TO THE OWNER WITHIN 90 DAYS OF THE DATE OF RECEIPT OF THE CERTIFICATE OF W Q W <br /> RECTANGLE TO RECTANGLE FITTING(RIGHT) ELECT ELECTRICAL READ REQUIRED OCCUPANCY AS REQUIRED BY SECTION C103.6 OF 2018 WSEC.THE DRAWINGS SHALL INDICATE THE LOCATION AND PERFORMANCE f^ J � Q <br /> DATA OF EQUIPMENT,GENERAL CONFIGURATION OF DUCTWORK AND PIPING DISTRIBUTION SYSTEMS,INCLUDING FLOW RATES AS A 17. SUPPLY AND RETURN DUCTWORK FOR HVAC TO HAVE 1"SOUND LINING FOR THE FIRST 10 FEET FROM UNIT DISCHARGE OUTLET. V m <br /> ELEV ELEVATION RG RETURN GRILLE ALL DUCT LINING TO MEET AND EXCEED MOLD,HUMIDITY.EROSION RESISTANT.ETC.TO MEET IMC CHAPTER 6. W a <br /> ELERG EMERGENCY RL RE-LOCATE MINIMUM,THAT HAVE BEEN DENATED FROM THESE DOCUMENTS.A COMPLETE RECORD OF CHANGES SHALL BE KEPT TO DATE ON <br /> �n ROUND TO ROUND HIGH/MEDIUM VELOCITY FITTING A DAILY BASIS AND MADE ACCESSIBLE TO OWNER AND ENGINEER. Ill Z <br /> 0� ENT ENTERING RNLI ROUNDJ N�/ m = <br /> Q U <br /> ESP EXTERNAL STATIC PRESSURE RPM REVOLUTIONS PER MINUTE 18. ALL DUCTWORK TO BE CLASS-I AIR DUCTS.CLASS-II DUCTS SHALL NOT BE USED. �_�x( ly N <br /> ROUND TO ROUND FITTING EXH EEXHAUST XISTING <br /> RV RELIEF VALVE 18. LOCATIONS AND SIZES OF ALL FLOOR,WALL,AND ROOF OPENINGS SHALL BE COORDINATED WITH ALL OTHER TRADES INVOLVED. 06 O o <br /> EXIST,(E) <br /> EXP EXPANSION SOILED SCHEDULE <br /> LOW VELOCITY(PRESSURE)ROUND DUCT TAKE-OFF, SF SQUARE FEET LLI w <br /> TO SUPPLY DIFFUSER F FAHRENHEIT SG SUPPLY GRILLE 2018 WASHINGTON STATE w _� � � <br /> FCO FLOOR SO SCREENED OPENING .J •J SITE INFO T Z O W <br /> FLOOR CLEANOUT SOV SHUT OFF VALVE 2 <br /> RECTANGLE/ROUND RADIUSED ELBOW DUCT FC FIRE DAMPER SP STATIC PRESSURE ENERGY CODE (WSEC NOTES 0 } � Y > <br /> FIO FURNISHED AND INSTALLED BY OWNER SPEC SPECIFICATION J w <br /> FLA FULL LOAD AMP SPECD SPECIFIED ADDRESS: 1401 HEWITT AVE <br /> RECTANGULAR 90'ELBOW W/TURNING VANES TYPICAL FLEX FLEXIBLE SS STAINLESS STEEL 1. HVAC EQUIPMENT SHALL HAVE MINIMUM PERFORMANCE AT SPECIFIED RATING CONDITIONS NOT LESS THAN THE VALUES INDICATED CO <br /> 41 FILE FLOOR STRUCT STRUCTURAL IN 0403.3.2. EVERETT, WA 98201 w - <br /> FOB FLAT BOTTOM SWR SUPPLY WALL GRILLE N <br /> FOIC FURNISHSH ED BY OWNER INSTALLED BY CONTRACTOR SWR SUPPLY WALL REGISTER OWNER: HOBAN REALTY INTERESTS LLC <br /> O 0- _O <br /> ECCENTRIC CONICAL DUCT REDUCTION FITTING FpT FLAT ON TOP 2. HVAC SYSTEMS SHALL BE EQUIPPED'MIH AUTOMATIC CONTROLS CAPABLE OF ACCOMPLISHING SETBACK OR SHUTDOWN DURING <br /> UNOCCUPIED PERIODS AS REQUIRED BY SECTION C403.4.2 OF THE WSEC AND AS DESCRIBED IN THE TEMPERATURE CONTROL PARCEL/TAX 00439166900902 U <br /> FPM FEET PER MINUTE TBD TO BE DETERMINED SEQUENCES,IF PROVIDED. <br /> CONCENTRIC CONICAL DUCT REDUCTION FITTING FPS FEET PER SECOND TEMP TEMPERATURE LEGAL: EVERETT PLAT OF BLK 669 D-02 - W 48 FT OF LOTS 9 <br /> FSO FIRE SMOKE DAMPER TSTAT THERMOSTAT <br /> FT FOOT;FEET THRU THROUGH 3. PROVIDE BALANCING DEVICES IN ALL BRANCH DUCTS AND PIPE RUNS TO TERMINAL DEVICES AS REQUIRED BY SECTION C408.221 10 11 12 & 13 <br /> 30X20 FU FIXTURE UNITS TOD TOP OF DUCT AND 0408.2.2.2 OF THE WSEC AND CHAPTER 6 OF THE IMC AND AS INDICATED ON THE CONTRACT DOCUMENTS. ^ <br /> TOP TOP OF PIPE LTL <br /> 18"4 RECTANGLE TO ROUND FITTING GAL GALLON TO <br /> TRAP PRIMER 4. ALL DUCTWORK SHALL COMPLY WITH SMACNA STANDARDS FOR CONSTRUCTION OF GALVANIZED DUCTWORK.ALL DUCTWORK SHALL 2 <br /> GALV GALVANIZED TS TEMPERATURE SENSOR BE SEALED AS REQUIRED BY SECTION C403.10.2 OF THE WSEC.DUCT TAPE NOT ALLOWED. <br /> GEN GENERAL TV TURNING VANE <br /> SOUND ATTENUATOR CND GROUND TYR TYPICAL 5. ALL DUCTWORK SHALL BE INSULATED AS REQUIRED BY SECTION C403.10.1 OF THE WSEC. e .( <br /> GPH GALLONS PER HOUR <br /> GPM GALLONS PER MINUTE V VENT _ COPYRIGHT rr� TURNING VANES VD VOLUME DAMPER 6. ALL PIPING INSULATION SHALL CONFORM TO SECTION 0403.10.3 OF THE WSEC. .`2 <br /> H HEIGHT,HIGH VEL VELOCITY F■ THIS uvoUTIDESIGN 15 AD LISHED <br /> HP HORSEPOWER VERT VERTICAL woaK,ANO PUGET111vo <br /> HR HOUR VOL VOLUME 7. FAN OF GREATER THAN 5 HE SHALL HAVE A FAN EFFICIENCY GRADE(EEG)OF 67 OR HIGHER AS REQUIRED BY SECTION C403.8.3 1� <br /> .Vy^nf <br /> FLEXIBLE DUCT HTG HEATING OF THE WSEC. a D , co�iM Echo=-R­1 <br /> oFI usnAcooe ioRE <br /> WB WET BULB TEMPERATURE PREVENTANY UNAUTHORIZED COPYING. <br /> T S THERMOSTAT OR TEMPERATURE SENSOR HVAC HEATING,VENTILATING,AND AIR CONDITIONING -'LS-' PUBLICKDON OR USE OF THIS DESIGN, <br /> - <br /> 0 HZ <br /> IT WET WALL EXHAUST FAN 8. MOTOR EFFICIENCY SHALL NOT BE LESS THAN THE MINIMUM CALLOUTS PER SECTIONS C405.8 OF THE WSEC FOR FULL LOAD I„r� II AND TO OMIN DAMAGES THEREOF. <br /> WG WATER GAGE EFFICIENCIES.MOTORS BETWEEN 1/12 HP AND 1 HP NOT COVERED BY TABLES C405.8(3)AND C405.8(4)SHALL BE ELECTRICALLY <br /> ❑T THERMOSTAT OR TEMPERATURE SENSOR(CEILING) IBC INTERNATIONAL BUILDING CODE W/ NTH COMMUTATED MOTORS. <br /> EGO INTERNATIONAL FUEL GAS CODE W/0 WITHOUT <br /> SD DUCT SMOKE DETECTOR W4 WEIGHT 9. HVAC SYSTEMS SHALL BE BALANCED AS REQUIRED BY SECTION C408.22 OF THE WSEC. <br /> L� _ 1 <br /> ©O ^ SUPPLY AIR DIFFUSER RPM G LEGEND• 10. HVAC SYSTEMS DO NOT REQUIRE COMMISSIONING PER THE WSEC SECTION C408.2 EXCEPTION 1. <br /> v ROUND SUPPLY AIR DIFFUSER 4 <br /> 11. FRESH AIR INTAKE AND RELIEF/EXHAUST SHALL BE EQUIPPED NTH LOW LEAK CLASS 1A MOTORIZED DAMPERS AS REQUIRED BY <br /> RETURN AIR GRILLE N.C. 0&N.C. BALL VALVE QA AUTOMATIC AIR VENTLOAT VALVE C- PIPE DOWN SECTION C403.7.8 OF THE WSEC. - .1 <br /> ® ;• MANUAL AIR VENT O PIPE UP <br /> •; ;•: ; <br /> EXHAUST AIR GRILLE BALL FLOAT VALVE 4 12. FAN AND PUMP MOTORS 7.5 HE AND GREATER SHALL BE EQUIPPED WITH A VFD AS REQUIRED BY SECTION C403.2.3 OF THE Q <br /> N.C. �(I(r�N.O. DIFFERENTIAL PRESSURE GAUGE ASSEMBLY -8- TEE DOWN WSEC. _ v <br /> SIDEWALL SUPPLY AIR GRILLE "" BUTTERFLY VALVE ® O TEE UP <br /> S I REGISTER N.C. N.O. DIFFERENTIAL PRESSURE SENSOR ASSEMBLY 13. IF NOT SPECIFICALLY STATED ABOVE,CONTRACTOR SHALL COMPLY WITH THE WSEC ITEMS THAT DO APPLY TO THIS PROJECT. <br /> III UNION r-'-I <br /> SIDEWALL RETURN/EXHAUST AIR GATE VALVE GAUGE W/COCK <br /> GRILLE OR REGISTER N.C. N.O. tI CLEAN OUT t <br /> No. Revision/Issue Date <br /> 1I GLOBE VALVE P/T PORT p REDUCER ' <br /> N.C. N.Q. m _._ U <br /> Y PIPE WELL THERMOMETER WYE STRAINER IT, ° C.STONE <br /> N CHECK VALVE L-' ,e -� 12/27/2023 <br /> FLOW METER Q FLOW SENSOR i (,� <br /> PLUG VALVE . <br /> I iii <br /> PRESSURE REGULATING VALVE 1 BTU METER W/WELL SENSOR 4 MOTORIZED VALVE ACTUATOR PROJECT LOCATION G.EYRE <br /> SOLENOID VALVE ACTUATOR SITE VICINITY 12/27/2023 <br /> + T PRESSURE RELIEF VALVE m <br /> P5822 <br /> NTS �J e <br /> G.E. MO.O <br /> AS NOTED <br />