Mr. Eric Evans <br />Shelter Holdings <br />Plan Check Number: B1912-032, First Structural Review <br />January 3, 2020 <br />Structural <br />General: <br />1. The concrete schedule in Note "03000: Concrete' of the Structural Notes on Sheet SLOB <br />specifies exterior concrete strengths less than 4,500 psi. The project appears to include <br />concrete elements that are exposed to freeze -thaw cycles and water and qualify as Class F2 <br />concrete per ACI 318-14 Table 19.3.1.1. In addition, the project appears to include concrete <br />elements exposed to deicing chemicals, which qualifies as Class F3 concrete. Per ACI 318-14 <br />Table 19.3.2.1, the minimum concrete strengths for Class F2 and F3 concrete are 4,500 psi and <br />5,000 psi, respectively. The minimum concrete strengths for exposed concrete on Sheet SLOB <br />should be revised as required. See IBC Section 1901.2. <br />2. The First Story concrete columns on Sheet S2.12B do not appear to be specified. See Sheet <br />S2.11B specifying columns for the south end of the structure. The columns should be specified. <br />The dark areas within the concrete shear walls, which are specified as Column Type C3 on <br />Sheet S2.11B, should be similarly specified. See IBC Section 1603.1. <br />3. The First Story concrete shear walls on Sheets 2.11B and S2.12B do not appear to be specified. <br />Section 16/S6.05 is specified at multiple locations but is not identified as a typical condition. <br />The required construction of all walls should be clearly specified. See IBC Section 1603.1. <br />4. The Wood Framing Plans on Sheets S4.11B through S4.52B include a Wood Beam Schedule. <br />The "Type" column of the schedule appears incomplete. It appears the schedule is intended to <br />specify beam sizes identified in the plans, such as "FR-X" and "HR-X". The schedule should be <br />revised as needed. See IBC Section 1603.1. <br />5. Continuing with the previous comment, some framing in the Wood Framing Plans on Sheets <br />S4.11B through S4.52B appear to include additional information that may be redundant or <br />conflicting with the Wood Beam Schedule. See the "FB-5x15" framing at Grid A/12.2-12.8 <br />occurring on all floor levels; the framing also occurs at other locations. The framing should be <br />reviewed and revised as needed. See IBC Section 1603.1. <br />Foundation System: <br />6. The building foundation is supported by cast -in -place concrete piles per the Pile Plans on Sheets <br />S2.01B and S2.02B. The locations of some piles do not appear to be specified. See IBC Section <br />1603.1. The following conditions should be addressed: <br />a. Single piles located off -grid. See the pile located near Grid K/4 for an example. <br />b. Pile pairs located off -grid. See the piles located near Grid E/10. Note that the spacing <br />between the piles is not specified in Detail 6/S6.03. Both the spacing and grid offset(s) <br />should be specified. <br />c. The piles supporting the mat foundation at Grid E-G/7.5-8. Note that while Sections <br />17/S6.06 and 20/S6.06 specify a 2'-V pile inset dimension, the overall dimensions for the <br />foundation do not appear to be specified. The dimensions should be identified as typical. <br />3200 <br />dar <br />0 Everett WAStreet98201 O 425.257.88577 fax O everett asgov/permitgov <br />s <br />Page 2 of 7 <br />