Laserfiche WebLink
AC <br /> w�^ <br /> TESTING ANO Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> ERV-5 <br /> • LVL 1 CR'S/ LVL 2 OFFICES <br /> AREA SERVED NO. CODE SIZE AK DESIGN INITIAL %OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> JC/LAUN E1 EG-2 6" F. H. 60 59 980/0 66 1100/0 <br /> IMH SP E2 RG-2 4" F. H. 15 52 347% 19 127% <br /> IMH SP E3 RG-2 4" F. H. 15 12 80% 15 1000/0 <br /> RESOURCE E4 RG-1 6" F. H. 70 175 250% 76 1090/0 <br /> LVL 2 CORRIDOR E5 I RG-1 6X6 F. H. 40 46 115% 40 1000/0 <br /> THERAPY E6 RG-1 4" F. H. 15 54 360% 14 93% <br /> READING NOOK E7 RG-1 6X6 F. H. 90 97 1080/0 84 93% <br /> ST/JC E8 EG-1 4" F. H. 30 23 77% 30 1000/0 <br /> CLASSROOM 1 E9 RG-1 12X6 F. H. 150 96 64% 158 105% <br /> CLASSROOM 1 RR E10 EG-1 6" F. H. 70 53 76% 68 97% <br /> EXHAUST 555 667 120% 570 103% <br /> EXHAUST REGISTER#E2 HAS ITS BALANCING DAMPER IN A FULL CLOSED POSITION. NO OBJECTIONABLE NOISE OR DRAFT NOTED. <br /> FORM ID:LOW VELOCITY TEST SHEET <br /> 10/24/2023 <br /> Page 32 of 56 <br />