w w�^ <br /> TESTING Al Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> UNIT DATA <br /> UNIT ID ERV-7(SUPPLY) ERV-7(EXHAUST) <br /> EQUIP. LOCATION CEILING CEILING <br /> AREA SERVED LVL 2 CENTRAL UNITS LVL 2 CENTRAL UNITS <br /> MANUFACTURER LOSSNAY LOSSNAY <br /> MODEL NUMBER TLGHF060ORVX02A TLGHF060ORVX02A <br /> SERIAL NUMBER 22100029546177 22100029546177 <br /> FAN DATA <br /> DESIGN CFM 590 520 <br /> ACTUAL CFM 566 528 <br /> T.S.P."W.C. 0.66 0.66 <br /> TESTED SPEED HIGH HIGH <br /> STATIC SETTING N./APPL. N./APPL. <br /> MOTOR DATA <br /> MANUFACTURER MITSUBISHI MITSUBISHI <br /> HORSEPOWER 0.42 0.41 <br /> NAMEPLATE VOLTS 208-230 208-230 <br /> TESTED VOLTS 208 208 <br /> NAMEPLATE AMPS 1.37 1.34 <br /> TESTED AMPS 1.3 1.3 <br /> MOTOR RPM VARIABLE VARIABLE <br /> SPEED 4-SPEED 4-SPEED <br /> PHASE/ HZ 1/60 1/60 <br /> OVERLOAD SIZE THERMAL THERMAL <br /> AREA SERVED NO. CODE SIZE AK • OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> UNIT 08 1 CD-2 6X6 F. H. 30 26 87% 30 1000/0 <br /> UNIT 10 2 CD-2 6X6 F. H. 30 22 73% 30 1000/0 <br /> UNIT 11 3 CD-2 6X6 F. H. 30 30 1000/0 30 1000/0 <br /> UNIT 07 4 CD-2 6X6 F. H. 30 27 900/0 30 1000/0 <br /> UNIT 09 5 CD-2 6X6 F. H. 30 25 83% 30 1000/0 <br /> LVL 2 STAFF 6 CD-1 10X10 F. H. - 200 - 154 77% - 180 900/0 <br /> LVL 2 CORRIDOR 7 SG-1 6X6 0.85 47 40 81 69 172% 52 44 1100/0 <br /> LVL 2 LOUNGE 8 SG-1 12X6 F. H. - 200 - 251 126% - 192 96% <br /> SUPPLY 590 604 102% 566 96% <br /> Jill <br /> FORM:DIRECT DRIVE TEST DATA <br /> 10/24/2023 <br /> Page 35 of 56 <br />