Laserfiche WebLink
w w�^ <br /> TESTING Al Ca A~Ry <br /> SERVICES <br /> • EVERGREEN MANOR <br /> • • EVERETT,WA <br /> • • 2220161 <br /> • <br /> BRUCE HURLBUT <br /> UNIT DATA <br /> UNIT ID ERV-U2(SUPPLY) ERV-U2(EXHAUST) <br /> EQUIP. LOCATION CEILING CEILING <br /> AREA SERVED S WING LVL 1 UNITS S WING LVL 1 UNITS <br /> MANUFACTURER BROAN BROAN <br /> MODEL NUMBER ERVS100 ERVS100 <br /> SERIAL NUMBER TF64221117691 TF64221117691 <br /> FAN DATA <br /> DESIGN CFM 30 30 <br /> ACTUAL CFM 82 73 <br /> T.S.P."W.C. 0.40 0.40 <br /> TESTED SPEED LOW LOW <br /> STATIC SETTING N./APPL. N./APPL. <br /> MOTOR DATA <br /> MANUFACTURER BROAN BROAN <br /> HORSEPOWER 103(W) 103(W) <br /> NAMEPLATE VOLTS 120 120 <br /> TESTED VOLTS 121 121 <br /> NAMEPLATE AMPS 0.9 0.9 <br /> TESTED AMPS 0.5 0.5 <br /> MOTOR RPM VARIABLE VARIABLE <br /> SPEED 2-SPEED 2-SPEED <br /> PHASE/ HZ 1/60 1/60 <br /> OVERLOAD SIZE THERMAL THERMAL <br /> AREA SERVED NO. CODE SIZE AK • OF OF <br /> FPM CFM FPM CFM DESIGN FPM CFM DESIGN <br /> UNIT A 1 SG-1 6X6 0.85 35 30 140 119 397% 96 82 272% <br /> SUPPLY 30 119 397% 82 272% <br /> UNIT A E1 EG-1 6X6 F. H. - 30 103 343% 73 243% <br /> EXHAUST 30 103 343% 73 243% <br /> III III JIJIIJ�Jill <br /> UNIT HAS TWO SPEED SETTINGS(65CFM OR 105 CFM). <br /> UNIT IS SET TO LOW SPEED.NO OBJECTIONABLE NOISE OR DRAFTS OBSERVED. <br /> FORM:DIRECT DRIVE TEST DATA <br /> 10/24/2023 <br /> Page 41 of 56 <br />