Laserfiche WebLink
SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 7 <br /> DATE: 12/4/2023-54 RACKS\4 CALCULATIONS\HYDRAULIC CALCIS\OUTDOOR RACK.SDF <br /> JOB TITLE: Boeing 40-54 Outdoor Racks - Dry System SV-54-14 <br /> WATER SUPPLY ANALYSIS <br /> Static: 67.00 psi Resid: 57.00 psi Flow: 3090.0 gpm <br /> 180.0 <br /> LEGEND <br /> Pressure available <br /> 1 <br /> C at source <br /> 150.0 66.43 psi @ 656.0 gpm <br /> 5 2 Pressure required <br /> at source <br /> 0.10 psi @ 656.0 gpm <br /> G 3 Pressure available <br /> A from pump <br /> U 120.0 ' 80.64 psi @ 656.1 gpm <br /> 4 Pressure required <br /> from pump <br /> E <br /> 42.10 psi @ 656.1 gpm <br /> Total Pressure avail- <br /> s <br /> P 90.0 13 able at pump dschg. <br /> R 147.07 psi @ 656.1 gpm <br /> E 3 6 Total Pressure re- <br /> S quired at pump dschg. <br /> 42.20 psi @ 656.1 gpm <br /> S �F <br /> 1 <br /> U 60 <br /> •0 A. Source Supply Curve <br /> R <br /> B. Net Pump Supply Curve <br /> E <br /> C. Pump Discharge Curve <br /> 6 D. System Demand Curve <br /> ( <br /> p 3 0 .0 F. Available at Pump Suction <br /> s <br /> i <br /> 0.0 , <br /> „ ,,,,,,,,,,,,,., ., ,,.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,..,, ,. ,.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, ,. ,.,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,,, <br /> 2 � <br /> -14.7 <br /> 80C12001600 2000 2400 2800 3200 3600 4000 <br /> FLOW (GPM) <br /> Note: (1) Dashed Lines indicate extrapolated values from Test Results <br />