z <br /> 4 of 31 <br /> GENERAL NOTES <br /> HELICAL PILES <br /> 1. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED IN ACCORDANCE WITH THE 2018 <br /> INTERNATIONAL BUILDING CODE (IBC). <br /> 2. HELICAL PILES SHALL BE DESIGNED AND MANUFACTURED BY IDEAL MANUFACTURING, INC.,AND <br /> SHALL BE IN ACCORDANCE WITH ESR-3750. <br /> 3. ALL MATERIAL PROPERTIES OF HELICAL PILE COMPONENTS SHALL BE IN ACCORDANCE WITH <br /> ESR-3750. <br /> 4. CORROSION PROTECTION OF ALL PILE COMPONENTS SHALL COMPLY WITH THE ICC-ES <br /> ACCEPTANCE CRITERIA FOR CORROSION PROTECTION OF STEEL FOUNDATION SYSTEMS USING <br /> POLYMER(EAA)COATINGS (AC228). <br /> 5. ALL HELICAL FOUNDATION COMPONENTS SHALL BE GALVANICALLY ISOLATED FROM CONCRETE <br /> REINFORCING STEEL, BUILDING STRUCTURAL STEEL, OR ANY OTHER METAL BUILDING <br /> COMPONENTS PER AC358 SECTION 3.9. <br /> 6. THE SHAFT SHALL BE DESIGNED AND FABRICATED TO SUPPORT THE SPECIFIED DESIGN LOADS. <br /> 7. ONLY MANUFACTURER-APPROVED CONNECTORS,ADAPTORS,AND ACCESSORIES MAY BE USED. <br /> 8. HELICAL PILES SHALL BE INSTALLED VERTICALLY INTO THE GROUND WITH AN ALLOWABLE ANGLE <br /> OF INCLINATION OF+/- 1 DEGREE FROM VERTICAL PER SECTION 4.2.1 OF ESR-3750. <br /> 9. MONITOR AND RECORD DEPTH OF PILE PENETRATION. PROVIDE TORQUE MONITORING DEVICE <br /> AS PART OF THE INSTALLING UNIT. MONITOR AND RECORD TORQUE APPLIED DURING THE <br /> INSTALLATION OF EACH PILE AT SPECIFIC DEPTHS. <br /> 10. HELICAL PILES SHALL BE INSTALLED TO THE MINIMUM TORQUE VALUE REQUIRED TO PROVIDE <br /> THE MINIMUM REQUIRED LOAD CAPACITIES INDICATED ON PLAN INCLUDING A FACTOR OF <br /> SAFETY NO LESS THAN TWO (2). THE MAXIMUM INSTALLATION TORQUE SHALL NOT EXCEED THE <br /> ALLOWABLE TORSIONAL CAPACITY OF ANY INDIVIDUAL COMPONENT OF THE PILE ASSEMBLY. <br /> 11. ALL BRACKETS AND HELICAL PILE ASSEMBLY COMPONENTS SHALL HAVE ADEQUATE CAPACITY <br /> TO ACHIEVE THE MINIMUM REQUIRED BEARING CAPACITY INCLUDING A FACTOR OF SAFETY NO <br /> LESS THAN TWO (2). <br /> 12. REPAIR BRACKETS MUST BE CONCENTRICALLY LOADED AND THE BRACKET PLATE MUST BE <br /> FULLY ENGAGED WITH BOTTOM OF CONCRETE FOUNDATION. <br /> 13. ALL HELICAL PILE ASSEMBLY COMPONENTS MUST HAVE ADEQUATE STRENGTH TO DEVELOP THE <br /> TORQUE REQUIRED FOR INSTALLATION AND ALL INDUCED STRESSES. <br /> 14. THE PILE QUANTITY, LAYOUT, AND SPACING INDICATED ON PLAN SHALL NOT BE CHANGED <br /> WITHOUT WRITTEN APPROVAL FROM THE ENGINEER-OF-RECORD PRIOR TO INSTALLATION. <br /> 15. CONTINUOUS SPECIAL INSPECTION IN ACCORDANCE WITH 2018 AND 2012 IBC SECTION 1705.9 <br /> MUST BE PROVIDED FOR THE INSTALLATION OF THE HELICAL PILES AND FOUNDATION <br /> BRACKETS. ITEMS TO BE RECORDED AND CONFIRMED BY THE SPECIAL INSPECTOR MUST <br /> INCLUDE THE FOLLOWING: <br /> A. PRODUCT MANUFACTURER <br /> B. MANUFACTURER'S CERTIFICATION OF THE INSTALLERS <br /> C. PRODUCT TYPE AND CONFIGURATIONS FOR HELICAL PILE LEAD SHAFT SECTIONS, <br /> EXTENSIONS, BRACKETS, BOLTS, THREADED RODS, NUTS, WASHERS,AND TORQUES AS <br /> SPECIFIED IN THIS REPORT AND THE CONSTRUCTION DOCUMENTS <br /> D. INSTALLATION PROCEDURES FOR THE HELICAL PILE SHAFT, INSTALLATION EQUIPMENT <br /> USED,AND THE IDEAL FOUNDATION SYSTEMS INSTALLATION INSTRUCTIONS <br /> E. ANTICIPATED AND ACTUAL PILING DEPTH <br /> F. REQUIRED TARGET INSTALLATION TORQUE OF PILES AND MINIMUM DEPTH OF INSTALLATION <br /> G. INCLINATION AND POSITION OF PILES, TOP OF PILE EXTENSION IN FULL CONTACT WITH <br /> BRACKET, TIGHTNESS OF ALL BOLTS AND EVIDENCE THAT THE PILE FOUNDATION SYSTEMS <br /> ARE INSTALLED BY AN APPROVED IDEAL FOUNDATION SYSTEMS INSTALLER. <br /> 16. PILES IMPROPERLY INSTALLED BECAUSE OF MISLOCATION, MISALIGNMENT, OR FAILURE TO <br /> MEET OTHER SPECIFIED DESIGN/INSTALLATION CRITERIA ARE NOT ACCEPTABLE.ABANDON <br /> REJECTED PILES AND INSTALL ADDITIONAL PILES AS REQUIRED. <br /> HELICAL PILE PROOF TESTING <br /> THE CAPACITY OF THE INSTALLED PILES SHALL BE VERIFIED BY FIELD TESTING OF A MINIMUM THREE <br /> (3) PERCENT OF PILES UP TO FIVE (5) PILES MAXIMUM (ONE (1) MINIMUM) IN ACCORDANCE WITH THE <br /> PROCEDURE OUTLINED IN ASTM D1143 AND/OR THE 2018 SEATTLE BUILDING CODE (SBC). THE <br /> MAXIMUM TEST LOAD SHALL BE TWO-HUNDRED (200)PERCENT OF THE SPECIFIED DESIGN LOAD. <br />