STRUCTURAL NOTES NOTES <br /> STRUCTURAL WOOD <br /> 1. STRUCTURAL WOOD COMPONENTS(BEAMS,HEADER,JOISTS,RAFTERS.ETC.)SHALL HAVE THE FOLLOWING <br /> MINIMUM ALLOWABLE FIBER STRESSES CONFORMING TO 2015 NDS(SIZE FACTOR INCLUDED IN STRESS VALUE): <br /> A.NO.1 DOUG FIR LARCH: <br /> SHEAR Fv= 180 PSI <br /> BENDING 2x4 Fb= 1,500 PSI <br /> BENDING 2x8 Fb= 1,300 PSI <br /> BENDING 2x8 Fb= 1,200 PSI <br /> BENDING 2x10 Fb= 1,100 PSI <br /> BENDING 2x12 Fb= 1,000 PSI <br /> 2. STRUCTURAL WOOD COMPONENTS FOR STUDS,POSTS AND MISCELLANEOUS FRAMING MEMBERS SHALL BE <br /> SOUTHERN PINE NO.2,DOUG FIR LARCH NO.2 OR BETTER. <br /> 3. ALL WOOD IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PRESSURE TREATED IN ACCORDANCE WITH <br /> AWPA UI. <br /> 4. SUBSTITUTIONS ARE ACCEPTABLE WITH THE APPROVAL OF THE PROJECT ENGINEER.UNLESS SHOWN <br /> OTHERWISE,INSTALL SIZE AND NUMBER OF FASTENERS SHOWN IN THE LATEST SIMPSON CATALOG. <br /> 5. NAILS-COMMON TYPE NAILS PER ASTM F1667. IF REQUIRED,PRE-DRILL HOLES TO 3/4 OF THE DIAMETER OF <br /> THE NAIL SHANK TO PREVENT SPLITTING. <br /> 8D 0.131'DIA BY 2-1/2'LONG WITH FYB=100 KSI <br /> 10D 0.148'DIA BY 3' LONG WITH FYB=90 KSI <br /> 12D 0.148'DIA BY 3-1/4'LONG WITH FYB=90 KSI <br /> 16D 0.182'DIA BY 3-1/2'LONG WITH FYB=90 KSI <br /> 6. FASTEN MULTI-PLY MEMBERS SUCH AS(2)2X4,(2)2X8,(3)2X8,ETC.WITH 10G NAILS AT 12-INCHES ON CENTER, <br /> STAGGERED IN TWO ROWS AND ON BOTH SIDES OF THE MEMBER. <br /> 7. SHEATHINGS:PLYWOOD OR OSB AND SHALL BE APA RATED STRUCTURAL SHEATHING EXPOSURE 1 WITH A <br /> MINIMUM SPAN RATING OF 32/16.ALL SHEATHING SHALL BEAR THE TRADEMARK STAMP"APA,THE ENGINEERED <br /> WOOD ASSOCIATION,"AND SHALL CONFORM TO STANDARD PS-1 OR PS-2.THE MINIMUM SPECIFIC GRAVITY,G, No. REVISED FOR: DATE(v-,w): <br /> SHALL BE 0.49 AND THE MOISTURE CONTENT SHALL NOT BE GREATER THAN 16%AT THE TIME OF INSTALLATION. <br /> ALL EXTERIOR SHEATHINGS SHALL BE"EXTERIOR"GRADE. 1.. <br /> A.WALL SHEATHING: MATCH EXISTING SHEATHING THICKNESS OR MINIMUM 15/32 INCH THICK OR AS SHOWN 2. <br /> ON THE PLANS <br /> 8. BOLTS:ALL BOLT HOLES IN WOOD SHALL BE DRILLED 1/32"DIAMETER LARGER THAN NOMINAL BOLT DIAMETERS. <br /> 4, <br /> BOLTS IN WOOD SHALL NOT BE LESS THAN 7 DIAMETERS FROM THE END AND 4 DIAMETERS FROM THE EDGE OF 5. <br /> THE MEMBER.THREAD PROJECTION SHALL BE 1/16 INCH MINIMUM.ALL NUTS SHALL BE TIGHTENED WHEN e. <br /> INSTALLED AND RE-TIGHTENED AT THE COMPLETION OF WORK OR BEFORE CLOSING IN. 7. <br /> 9. MACHINE BOLT ANCHOR BOLTS SHALL BE ASTM A307,GRADE A,GALVANIZED.THEY SHALL BE PROVIDED WITH <br /> FULL BODY DIAMETER AS FOLLOWS: RI M KU S <br /> BODY OR SHANK <br /> NOMINAL DIAMETER <br /> SIZE MAX MIN <br /> 16932 WOODINVILLE REDMOND RD NE,#A103 <br /> 1/2 0.5150 0.4820 WOODINVILLE,WA 98072 <br /> 5/8 0.6420 0.6050 DHODSON©RIMKUS.COM <br /> 580-3228 0) <br /> 3/4 0.7880 0.7290 <br /> 7/8 0.8950 0.8520 s-" � <br /> 1 1.0220 0.9760 ; d .d^� <br /> A. ADOPTED FROM ASME B18.2.1 <br /> I <br /> B. FOR DIAMETERS NOT INDICATED,REFER TO ASME B18.2.1&B18.2.6 <br /> C. THE AND SHANK OF A BOLT IS THE SMOOTH PORTION BETWEEN THE HEAD AND THE THREADS 4.* <br /> D.ALL SIZES IN TABLE IN INCHES t�•� <br /> 10. WASHERS:ALL BOLT HEADS,LAG SCREWS AND NUTS BEARING ON WOOD SHALL HAVE STANDARD CUT N0. ISSUED FOR: DATE(Y-M-D)'. <br /> WASHERS. 1. ISSUE FOR PERMIT 2024,1-5 <br /> 11. REPLACE ALL FULL DEPTH BLOCKING OR BRIDGING WHEN REMOVED. 2. <br /> 12. MOISTURE CONTENT OF WOOD AT TIME OF PLACING SHALL NOT EXCEED 19%. 3. <br /> 13. OVER DRIVING OF NAILS THROUGH SHEARWALL,ROOF,OR FLOOR SHEATHING IS NOT ALLOWED.NAILS SHALL a <br /> BE DRIVEN SO THAT THE HEADS ARE FLUSH WITH THE SURFACE OF SHEATHING. <br /> 14. MACHINE APPLIED NAILING:SUBJECT TO SATISFACTORY JOB SITE DEMONSTRATION FOR THIS PROJECT AND <br /> CONTINUED SATISFACTORY PERFORMANCE MAINTAINING EDGE DISTANCES AND WITHOUT OVERDRIVING <br /> 6. <br /> NAILS. 7 <br /> 15. ANCHOR BOLTS,FASTENERS,NAILS,WOOD SCREWS,LAG SCREWS,BOLTS AND ALL OTHER CONNECTORS PROJECT: <br /> SHALL BE GALVANIZED IN ACCORDANCE WITH ASTM A-153,ASTM A-653 HOT DIPPED ZINC COATED GALVANIZED STRUCTURAL REPAIR FOR <br /> OR SHALL BE STAINLESS STEEL.FASTENERS OTHER THAN NAILS,WOOD SCREWS AND LAG SCREWS SHALL BE <br /> PERMITTED TO BE OF MECHANICALLY-DEPOSITED ZINC-COATED STEEL WITH COATING WEIGHTS IN WOODBROOK APARTMENTS <br /> ACCORDANCE WITH ASTM B695,CLASS 55 MINIMUM. 525 112TH ST SOUTHEAST <br /> 16, CONTRACTOR SHALL BE REQUIRED TO FURNISH AND INSTALL SOLID BLOCKING HAVING A MINIMAL NOMINAL EVERETT,WA 98208 <br /> THICKNESS OF TWO INCH AND A MINIMUM DEPTH TO MATCH ADJOINING MATERIALS.SAID BLOCKING SHALL BE <br /> INSTALLED AT ALL JOIST SUPPORT LOCATIONS. <br /> 17. ALL MANUFACTURERS PRODUCTS IDENTIFIED ON THE DRAWINGS AND/OR SPECIFIED WITHIN THE CLIENT: <br /> CALCULATIONS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS CUSHMAN AND WAKEFIELD <br /> AND REQUIREMENTS. 11235 SE 6TH ST SUITE 200 <br /> BELLEVUE,WA 98004 <br /> SHEET TITLE: <br /> STRUCTURAL NOTES <br /> FOR CLIENTS SOLE USE PER GOVERNING CONTRACT <br /> AND LIMITED TO APPLICABLE PROJECT.NO <br /> MODIFICATIONS OR REPRODUCTIONS WITHOUT <br /> WRITTEN APPROVAL OF RIMKUS.CONTRACTOR SOLELY <br /> RESPONSIBLE FOR VERIFYING ALL DIMENSIONS. <br /> PROJECT NO: 100239362 <br /> DATE(Yaa-D): 2024-01-5 <br /> SCALE AS NOTED <br /> DESIGNED BY: RIMKUS <br /> DRAWN BY: DJH <br /> CHECKED BY: RJD <br /> DRAWING NO Soot <br /> SHEET NO: <br />