FARRINGTON <br /> AIR QUALITY SERVICES <br /> Air Handling Unit <br /> PROJECT: Ballot Facility TI DATE: 6/17/2024 <br /> LOCATION: Everett,WA CONTACT: JT Parker <br /> PROJECT#: 23-1064 <br /> SYSTEM/UNIT: AHU-01/B-01 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 825 CFM <br /> Model Number VDDF Actual Max Airflow 820 CFM <br /> Serial Number R23K01738 Max Diff.SP 0.29 in.wc <br /> Box Inlet Size 10/08 Min Design CFM 275 CFM <br /> K Factor 2.0/2.0 Actual Min Airflow 285 CFM <br /> Min Diff.SP 0.04 in.wc <br /> Design Reheat Airflow 550 CFM <br /> Actual Reheat Airflow 525 CFM <br /> Reheat Diff.SP 0.31 in.wc <br /> AHU-01/B-01 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type D Factor CFM CFM <br /> Outlet-01 CD 10 Flowhood 1.00 275 275 275 100 <br /> Outlet-02 CD 12 Flowhood 1.00 ' 275 275 275 100 <br /> Outlet-03 CD 12 Flowhood 1.00 275 275 275 100 <br /> Totals: - - - - 825 825 825 100 <br /> SYSTEM/UNIT: AHU-01/B-02 Tested By: Eric Liles <br /> Date: 6/17/2024 <br /> Unit Data Term Box Test Data <br /> Manufacturer Trane Design Max Airflow 825 CFM <br /> Model Number VDDF Actual Max Airflow 825 CFM <br /> Serial Number R23K01739 Max Diff.SP 0.29 in.wc <br /> Box Inlet Size 10/08 Min Design CFM 275 CFM <br /> K Factor 2.20/2.10 Actual Min Airflow 275 CFM <br /> Min Diff.SP 0.04 in.wc <br /> Design Reheat Airflow 550 CFM <br /> Actual Reheat Airflow 550 CFM <br /> Reheat Diff.SP 0.33 in.wc <br /> AHU-01/B-02 Supply Outlet Summary <br /> System/Unit Outlet Size LxW/ Instrument AK Design Prelim Final CFM %Final <br /> Type _ D _Factor CFM CFM <br /> Outlet-01 CD 10 Flowhood 1.00 275 275 275 100 <br /> Outlet-02 CD 12 Flowhood 1.00 275 275 275 100 <br /> Outlet-03 CD 14 Flowhood 1.00 275 275 275 100 <br /> Totals: - - - - 825 825 825 100 <br /> Farrington Air Quality Services <br />