NORMAL CRITICAL CRITICAL
<br />r�1tL
<br />FBXHDP1
<br />4
<br />AJ
<br />AT'
<br />-A
<br />SOOA
<br />LIFE
<br />37,515
<br />30,454
<br />2000AF 800AF 400AF 400AF ° 400AF ° 400AF ° 225AF 400AF 225AF 225AF
<br />1600AT ( 600AT ( 175AT ( 175AT ( SPARE ( SPARE ( SPARE I SPACE SPACE SPACE
<br />N�FBCHDPI
<br />1600A 480Y/277V, 30, 4W
<br />65,000AIC
<br />ATS-Cl
<br />160OA/4P
<br />CRITICAL
<br />LS OR NORMAL EQ
<br />CONTINUED ON DRAWING E6.1
<br />225AF
<br />SPACE
<br />225AF
<br />SPACE
<br />400AF
<br />SPACE
<br />° 225AF
<br />( SPARE
<br />° 400AF
<br />( SPARE
<br />° 400AF
<br />( SPARE
<br />400AF
<br />( 400AT
<br />800AF
<br />( 600AT'
<br />i600AF
<br />1200AT
<br />�'-
<br />FBNHDPI
<br />1600A 480Y/277V, 30, 4W
<br />100,000AIC
<br />PARTIAL HOSPITAL POWER RISER DIAGRAM - LEVEL B SOUTH WING
<br />EQUIPMENT
<br />ATS-El
<br />3000A/4P
<br />EQUIPMENT
<br />LS OR EQ
<br />L
<br />CONTINUED ON DRAWING E6.2
<br />K ENGINEERS INC.
<br />208 Third Street
<br />Lyndon, WA. 98264
<br />Bus. (360) 354-4757
<br />FAX (360) 354-6794
<br />FEEDER SCHEDULE
<br />FEEDER NO.
<br />CONDUCTORS (COPPER AND COMPACT ALUMINUM)
<br />AMPACITY
<br />AXX = Cu
<br />AXX = AI
<br />CONDUIT WIRE
<br />CA4
<br />1-1/4" 4 - #4, 1#8 G.
<br />85
<br />CA3
<br />1" 3 - #4, 1#8 G.
<br />85
<br />C64
<br />1-1/4" 4 - #2, 1 #6 G.
<br />115
<br />CB3
<br />1-1/4" 3 - #2, 1 #6 G.
<br />115
<br />CC5
<br />2" 3 - #1, 2#1/0 N, 1#6 G.
<br />120
<br />CC4
<br />1-1/2" 4 - #1, 1 #6 G.
<br />130
<br />CC3
<br />1 1-1/2" 3 - #1, 1 #6 C.
<br />130
<br />AF5
<br />2" 5 - #3/0, 1 #4 G.
<br />140
<br />AF4
<br />2" 4 - #3/0, 1 #4 G.
<br />155
<br />AF3
<br />1-1/2" 3 - #3/0, 1 #4 G.
<br />155
<br />AG5
<br />2-1/2" 5 - #4/0, 1 #4 G.
<br />164
<br />AG4
<br />2" 4 - #4/0, 1 #4 G.
<br />180
<br />AG3
<br />2" 3 - #4/0, 1 #4 G.
<br />180
<br />AH5
<br />2-1/2" 5-250kcm11, 1 #4 G.
<br />184
<br />AH4
<br />2-1/2" 4-250kcmil, 1 #4 G.
<br />205
<br />AH3
<br />2" 3-250kcmil, 1 #4 G.
<br />205
<br />AJ5
<br />3" 5-300kcmil, 1 #4 G.
<br />204
<br />AJ4
<br />2-1/2" 4-300kcmil, 1 #2 G.
<br />230
<br />AJ3
<br />2" 3-300kcmil, 1 #2 G.
<br />230
<br />AK5
<br />3" 5-350kcmil, 1 #2 G.
<br />224
<br />AK4
<br />2-1/2" 4-350kcmil, 1 #2 G.
<br />250
<br />AK3
<br />2-1/2" 3-350kcmil, 1 #2 G.
<br />250
<br />AL5
<br />3" 5-400kcmil, 1 #2 G.
<br />244
<br />AL4
<br />3" 4-400kcmil, 1 #2 G.
<br />270
<br />AL3
<br />2-1/2" 3-400kcmil, 1 #2 G.
<br />270
<br />AM5
<br />3 1/2" 5-500kcmil, 1 #2 G.
<br />280
<br />AM4
<br />3" 4-500kcmil, 1 #2 G.
<br />310
<br />AM3
<br />3" 3-500kcmil, 1 #2 G.
<br />310
<br />AN5
<br />3-1/2" 5-600kcmil, 1 #2 G.
<br />308
<br />AN4
<br />3-1/2" 4-600kcmil, 1 #1 G.
<br />340
<br />AN3
<br />3" 3-600kcmil, 1 #1 G.
<br />340
<br />A2G3
<br />(2) 2-1/2" 3-#4/0, 1 #iG EA.
<br />360
<br />AP4
<br />4" 4-750kcmil, 1 #1 G. EA.
<br />385
<br />AP3
<br />3-1/2" 3-750kcmil, 1 #1 G. EA.
<br />385
<br />A2J5
<br />(2) 3" 5-300kcmil, 1 #1 G. EA.
<br />408
<br />A21<5
<br />(2) 3" 5-350kcmil, 1 #1/0 G. EA.
<br />448
<br />A21<4
<br />(2) 3" 4-350kcmil, 1 #1/0 G. EA.
<br />500
<br />A21<3
<br />(2) 2-1/2" 3-350kcmil, 1 #1/0 G. EA.
<br />500
<br />A2M4
<br />(2) 3" 4-500kcmil, 1 #3/0 G. EA.
<br />620
<br />A2M3
<br />(2) 3" 3-500kcmil, 1 #3/0 G. EA.
<br />620
<br />A2114
<br />(2) 3-1/2" 4-600kcmil, 1 #3/0 G. EA.
<br />680
<br />A2113
<br />(2) 3" 3-600kcmil, 1 #3/0 G. EA.
<br />680
<br />A3L4
<br />(3) 3" 4-400kcmil, 1 #3/0 G. EA.
<br />810
<br />A313
<br />(3) 2-1/2" 3-400kcmil, 1 #3/0 G. EA.
<br />810
<br />A3114
<br />(3) 3-1/2" 4-600kcmil, 1 #4/0 G. EA.
<br />1020
<br />A3N3
<br />(3) 3" 3-600kcmil, 1 #4/0 G. EA.
<br />1020
<br />A4M4
<br />(4) 3" 4-500kcmil, 1 #350 G. EA.
<br />1240
<br />A4M3
<br />(4) 3" 3-500kcmil, 1 #350 G. EA,
<br />1240
<br />C4114
<br />(4) 4" 4-600kcmil, 1-250kcmil G. EA.
<br />1680
<br />A5114
<br />(5) 3-1/2" 4-600kcmil, 1 #400 G. EA.
<br />1700
<br />A5113
<br />(5) 3" 3-600kcmil, 1 #400 G. EA,
<br />1700
<br />A6114
<br />(6) 3-1/2" 4-600kcmil, 1 #600 G. EA.
<br />2040
<br />A6113
<br />(6) 3" 3-600kcmil, 1 #600 G. EA.
<br />2040
<br />TRANSFORMER SECONDARY FEEDER SCHEDULE
<br />480 TO 208Y/12OV, THREE PHASE TRANSFORMERS (K-Rated)
<br />SECONDARY
<br />NO.
<br />kVA
<br />CONDUCTORS (COPPER AND COMPACT ALUMINUM)
<br />GROUNDING
<br />ELECTRODE
<br />CONDUCTOR
<br />CONDUIT WIRE
<br />CXX=Cu, AXX=A1
<br />RATING
<br />FLA
<br />CONDUCTOR
<br />AMPACITY
<br />CTK3
<br />3
<br />8
<br />1 2 3- #12, 1 #8 N. 1 #8 G.
<br />8
<br />20
<br />CTK6
<br />6
<br />17
<br />3/4" 3 - #10, 1 #6 N, 1 #8 G.
<br />8
<br />30
<br />CTK9
<br />9
<br />25
<br />1" 3 - #8, 1 #4 N, 1 #8 G.
<br />8
<br />44
<br />CTK15
<br />15
<br />42
<br />1 1/4' 3 - #6, 1 #1 N, 1 #8 G.
<br />8
<br />60
<br />CTK30
<br />30
<br />83
<br />1 1/2" 3 - #2, 1 #4/0 N, 1 #6 G.
<br />6
<br />104
<br />ATK45
<br />45
<br />125
<br />2 1/2" 5 - #4/0, 1 #2 G.
<br />2
<br />164
<br />ATK75
<br />75
<br />208
<br />3" 5 - 350kcmil, 1 #1/0 G.
<br />1/0
<br />224
<br />ATK112
<br />112.5
<br />312
<br />5" 5 - 750kcmil, 1 #3/0 G. EA,
<br />3/0
<br />348
<br />ATK150
<br />150
<br />416
<br />(2) 3-1/2" 5 - 500kcmil, 1 #4/0 G. EA,
<br />4/0
<br />560
<br />ATK225
<br />225
<br />625
<br />(2) 5' 5 - 750kcmil, 1 #4/0 G. EA,
<br />4/0
<br />696
<br />ATK300
<br />300
<br />833
<br />(4) 3-1/2" 5 - 500kcmil, 1 #250kcmil G. EA.
<br />250
<br />1120
<br />ATK500
<br />500
<br />1388
<br />6 4' 5 - 600kcmil, 1 #500kerril G. EA.
<br />250
<br />1848
<br />2727 Oakes Ave.
<br />Suite 100
<br />Everett, WA 98201
<br />REVISIONS
<br />R.
<br />1Q op WAS A
<br />v
<br />44794
<br />IONAL E�yG
<br />V/
<br />O
<br />O
<br />W
<br />ass
<br />O
<br />U
<br />m
<br />OD
<br />o
<br />aD
<br />N
<br />�
<br />a'
<br />o�
<br />O
<br />3O
<br />Los�
<br />0
<br />3
<br />O
<br />m
<br />L
<br />0-
<br />U
<br />N
<br />r
<br />W
<br />J0e D
<br />2341
<br />D� 9
<br />KL
<br />CMECxED By
<br />BD
<br />BID SET
<br />1-23-24
<br />ELECTRICAL -
<br />POWER SYSTEM
<br />RISER DIAGRAM
<br />E 6.3
<br />
|