SPECIFICATIONS:
<br />1. THE GENERAL, SUPPLEMENTARY AND OTHER CONDITIONS OF THE CONTRACT,
<br />21. DEFINITIONS
<br />27. WIRING
<br />MODIFICATIONS TO THE GENERAL CONDITIONS, THE DRAWINGS, AND THE APPLICABLE
<br />PROVISIONS OF THE OTHER DIVISIONS AR HEREBY MADE APART OF THIS DIVISION AND
<br />A.
<br />THE TERM "CONTRACTOR" USED THROUGHOUT THESE SPECIFICATIONS AND ON
<br />A.
<br />ALL WIRING SHALL BE ENCLOSED WITHIN THE RACEWAY SYSTEM.
<br />ALL ITS SECTIONS.
<br />THE ELECTRICAL DRAWINGS SHALL BE UNDERSTOOD TO MEAN THE ELECTRICAL
<br />CONTRACTOR. ALL OTHER WORK SHALL BE CALLED OUT BY NAME.
<br />B.
<br />PROTECT"OPEN" CABLE WIRING FROM ROUGH AND/OR SHARP EDGES ON
<br />2. THE REQUIREMENTS OF THIS SECTION APPLY TO ALL ELECTRICAL WORK.
<br />SUPPORTS, STRUCTURAL MEMBERS, ETC. AS REQUIRED DURING INSTALLATION.
<br />B.
<br />"FURNISH" MEANS TO SUPPLY AND DELIVER TO THE PROJECT, READY FOR
<br />3. COORDINATE ELECTRICAL WORK WITH RELATED WORK SHOWN AND SPECIFIED
<br />INSTALLATION AND IN OPERABLE CONDITION.
<br />C.
<br />WIRE AND CABLE SIZES INDICATED AND/OR SPECIFIED ARE MINIMUMS ONLY AND
<br />ELSEWHERE.
<br />SHALL BE INCREASED AS REQUIRED DUE TO NEC, SYSTEM, LOAD,
<br />C.
<br />"INSTALL" MEANS TO INCORPORATE IN THE WORK FINAL POSITION, COMPLETE,
<br />VOLTAGE DROP, ETC. REQUIREMENTS.
<br />4. WORK INCLUDED: THE CONTRACTOR SHALL PERFORM ALL THE WORK REQUIRED
<br />ANCHORED, CONNECTED, AND IN OPERABLE CONDITION.
<br />(INCLUDING THE FURNISHING OF ALL SUPERVISION, LABOR, SERVICES, TOOLS,
<br />D.
<br />BRANCH CIRCUIT& EQUIPMENT GROUND CABLES WITHIN A CONDUIT SYSTEM
<br />MATERIALS AND EQUIPMENT AND THE PERFORMANCE OF ALL OPERATIONS AND
<br />D.
<br />"PROVIDE" MEANS FURNISH AND INSTALL.
<br />SHALL BE 11C COPPER STRANDED, #12 AWG (UNLESS NOTED OTHERWISE), WITH
<br />INCIDENTALS NECESSARY) FOR A COMPLETE, SAFE AND RELIABLE ELECTRICAL
<br />600V TYPE XHHW OR THHN/THWN INSULATION.
<br />INSTALLATION, ADJUSTED, TESTED AND READY FOR OPERATION. THE ELECTRICAL WORK
<br />E
<br />F.O. I.C. - FURNISHED BY OTHERS, INSTALLED BY CONTRACTOR.
<br />(NEW AND MODIFICATION OF EXISTING) IS GENERALLY DESCRIBED AS FOLLOWS:
<br />E.
<br />CABLE SHALL BE UNROLLED FROM REELS, OR REMOVED FROM CARTONS, AND
<br />22. SUBMITTALS
<br />INSTALLED IN A MANNER WHICH WILL PREVENT KINKING, CRUSHING OR EXCESSIVE
<br />A. DEMOLITION.
<br />TENSION ON CONDUCTORS AND INSULATION. CABLE PULLING LUBRICANTS OF A
<br />B. GROUNDING.
<br />A.
<br />PROVIDE SUBMITTALS TO THE ENGINEER, TOGETHER, AT ONE TIME, SEPARATED AND
<br />TYPE HAVING NO DAMAGING EFFECT ON THE INSULATION, SHALL BE USED TO
<br />C. WIRING DEVICES AND SPECIAL PURPOSE RECEPTACLES.
<br />INDEXED FOR EACH SPECIFICATION SECTION. INDIVIDUAL OR INCOMPLETE
<br />MINIMIZE PULLING STRESSES ON THE CABLE.
<br />D. LIGHTING FIXTURES.
<br />SUBMITTALS ARE NOTACCEPTABLE.
<br />E. LIGHTING CONTROLS,
<br />F.
<br />CABLE SHALL BE INSTALLED OR DRAWN INTO THE CONDUIT SYSTEM ONLY AFTER
<br />F. BRANCH CIRCUIT WIRING SYSTEM FOR LIGHTING, OUTLETS, EQUIPMENT, ETC.
<br />B.
<br />THE ENGINEER WILL REVIEW EACH SUBMITTAL, INDICATE ACTION TO BE TAKEN,
<br />ALL WORK OF ANY NATURE THATCOULD CAUSE INJURY TO THE CABLE IS
<br />G. DISCONNECTING MEANS, SWITCHES, RECEPTACLES, MOTOR STARTERS, CONTROL
<br />AND RETURN. THE CONTRACTOR SHALL ALLOW FOR 1 1/2 WEEKS FOR ENGINEER
<br />COMPLETED. THE CONDUIT SYSTEM SHALL BE COMPLETE, SNAKED AND CLEANED
<br />DEVICES, ETC. (INSTALLATION ONLY IF FURNISHED WITH EQUIPMENT), AND FINAL
<br />REVIEW MINIMUM. COMPLIANCE WITH SPECIFIED CHARACTERISTICS IS THE
<br />BEFORE PULLING ANY CABLE.
<br />POWER AND LINE VOLTAGE (120 VOLT OR GREATER) CONTROL CONNECTIONS TO
<br />CONTRACTOR'S RESPONSIBILITY. APPROVAL OF SUBMITTALS DOES NOT RELEASE
<br />EQUIPMENT AND DEVICES PROVIDED BY THE OWNER, GENERAL CONTRACTOR OR
<br />THE CONTRACTOR FROM A PROPER INSTALLATION, COMPLIANCE WITH THE
<br />28. GROUNDING:
<br />OTHER SUB -CONTRACTORS, INCLUDING THE FOLLOWING.
<br />DRAWINGS, SPECIFICATIONS, CODES, STANDARDS, SITE CONSTRAINTS, ETC. OR
<br />1. FLUOROSCOPY IMAGING EQUIPMENT
<br />COORDINATION OF THE WORK.
<br />A.
<br />ALL ELECTRICAL EQUIPMENT, BOXES, DEVICES, SHALL BE PROVIDED WITH A
<br />H. LINE VOLTAGE (120 VOLT OR HIGHER) CONTROL STATIONS, DEVICES, CONDUIT,
<br />GROUND FAULT RETURN PATH BY MEANS OF THE INTEGRITY OF THE METALLIC
<br />I. BOXES, WIRING, ETC. (INSTALLATION ONLY IF FURNISHED WITH IMAGING EQUIPMENT)
<br />C.
<br />PROVIDE SUBMITTALS FOR THE FOLLOWING:
<br />CONDUITSYSTEM (WHERE APPLICABLE) & AN INSULATED GROUNDING
<br />J. SUPPORTS.
<br />CONDUCTOR INSTALLED WITH THE CIRCUIT CONDUCTORS. CONDUIT SHALL BE
<br />K. TRENCHING AND BACKFILLING FOR UNDERGROUND ELECTRICAL WORK.
<br />1. CIRCUTBREAKER.
<br />CLOSELY & TIGHTLY FITTED IN COUPLINGS, CONNECTORS, ETC. AND BE PROPERLY
<br />L TEMPORARY CONSTRUCTION POWER AND LIGHTING.
<br />2, LIGHTING FIXTURES & LIGHTING CONTROLS
<br />BONDED TO PROVIDE AN ELECTRICALLY CONTINUOUS LOW RESISTANT GROUND
<br />M. TESTING AND COMPLETING.
<br />PATH. CONTINUITY TESTS SHALL BE MADE TO VERIFY THE CONTINUITY OF THE
<br />N. OBTAINING AND PAYING FOR ALL REQUIRED LICENSES, PERMITS, INSPECTIONS AND FEES.
<br />23. DEMOLITION
<br />GROUNDING SYSTEM & ALL GROUND FAULT RETURN PATHS.
<br />5. WORK NOT INCLUDED. THE FOLLOWING ELECTRICAL SYSTEM RELATED WORK WILL BE
<br />A.
<br />CONTRACTOR SHALL REMOVE EXISTING EQUIPMENT, FIXTURES, DEVICES, ETC. AS
<br />B.
<br />EQUIPMENTGROUND CABLES SHALL BE 1/C COPPER, WITH 600V TYPE XHHW OR
<br />PROVIDED BY THE OWNER, GENERAL CONTRACTOR, OR OTHER SUBCONTRACTORS WORKING
<br />INDICATED IN THE WORK AREA AND ALL ASSOCIATED CONDUIT, BOXES,
<br />THHN/THWN INSULATION.
<br />DIRECTLY WITH THE OWNER:
<br />CABLES, ETC. SHALL BE REMOVED TO THEIR POINTOF ORIGIN &JOR DESTINATION.
<br />29. SEPARATELY MOUNTED CIRCUIT BREAKERS:
<br />A. IMAGING EQUIPMENT INSTALLER'. EQUIPMENT CABLING, EQUIPMENT, CONNECTIONS,
<br />g.
<br />UNLESS NOTED OTHERWISE, CONCEALED RACEWAYS ARE ALLOWED TO REMAIN,
<br />CONTROL WIRING, DEVICES, ETC.
<br />EXCEPT, WIRING SHALL REMOVED EXISTING CONCEALED RACEWAYS ARE
<br />A.
<br />CIRCUIT BREAKERS SHALL BE BOLT -ON, MOLDED -CASE, THERMAL MAGNETIC,
<br />ALLOWED TO BE RE -USED IF IN GOOD CONDITION &SUITABLE FOR THE NEW
<br />QUICK MAKE -QUICK BREAK TYPE WITH TRIP INDICATING HANDLES, SUITABLE FOR
<br />fi. BEFORE SUBMfTT1NG BID, EXAMINE EXISTING BUILDING AND EQUIPMENT CONDITIONS TO
<br />INSTALLATION.
<br />USE AS SERVICE ENTRANCE EQUIPMENT WHERE REQUIRED. CIRCUIT BREAKERS
<br />DETERMINE EFFECT ON EXECUTION OF THE ELECTRICAL WORK AND INCLUDE COSTS IN
<br />SHALL BE PROVIDED WITH HANDLE LOCKING DEVICES WHERE REQUIRED.
<br />BID.
<br />C.
<br />EXISTING FEEDERS, CIRCUITS, CONDUITS, CABLES, ETC. INTERRUPTED DUE TO THE
<br />MULTI -POLE BREAKERS SHALL BE SINGLE -HANDLE, INTERNAL COMMON TRIP. MAIN
<br />SYSTEM UPGRADE SHALL BE RE -CONNECTED AS REQUIRED TO MAINTAIN THE
<br />AND/OR FEEDER AND BRANCH CIRCUIT BREAKERS SHALL BE SERIES SHORT
<br />7. EXISTING CIRCUITS INDICATED ON THE PLANS ARE BASED ON WHAT WAS SHOWN
<br />ORIGINAL FUNCTION.
<br />CIRCUIT RATED. PROVIDE PADLOCKING DEVICES ON CIRCUIT BREAKERS WHERE
<br />T
<br />THE ORIGINAL CONSTRUCTION DRAWINGS AND MAN NOT BE EXACTLY HOW THE ACTUAL
<br />REQUIRED.
<br />CONSTRUCTION WAS DONE. THE CONTRACTOR SHOULD EXPECT THAT SOME AMOUNT OF
<br />D.
<br />ALL SURPLUS MATERIAL REMOVED DURING THE DEMOLITION SHALL BE INSPECTED
<br />CIRCUIT TRACING TO DETERMINE WHO THE ACTUAL CIRCUITS ARE INSTALLED WILL BE
<br />BY THE OWNER, AND THOSE ITEMS SELECTED SHALL REMAIN THE PROPERTY OF
<br />B.
<br />CIRCUIT BREAKERS SHALL BE IDENTIFIED WITH LAMINATED NAMEPLATES, BLACK
<br />REQUIRED.
<br />THE OWNER. ALL REMAINING SURPLUS MATERIALS SHALL BE REMOVED FROM THE
<br />FACE, WHITE CORE, ENGRAVED WITH MINIMUM 1/41NCH LETTERS.
<br />SITE & DISPOSED OF BY THE CONTRACTOR ACCORDING TO ALL APPLICABLE
<br />8. THE CONTRACTOR SHALL COORDINATE THE WORK AND COOPERATE WITH THE OWNER,
<br />REGULATIONS.
<br />30. WIRING DEVICES
<br />OTHER TRADES, AND SYSTEM CONTRACTORS TO HAVE THE WORK COMPLETED TO THE
<br />BESTADVANTAGE, INSURE THERE ARE NO INTERFERENCES, PROVIDE REASONABLE
<br />24. RACEWAYS
<br />A.
<br />WIRING DEVICES SHALL BE HOSPITAL GRADE, RED COLOR ON CRITICAL BRANCH AND
<br />OPPORTUNITY FOR THE OTHER TRADES AND CONTACTORS TO COMPLETE THEIR WORK
<br />IVORY COLOR ON NORMAL BRANCH.
<br />AND TO NOT DELAY THE WORK.
<br />A.
<br />RACEWAYS SHALL BE OF THE TYPES LISTED BELOW, UNLESS NOTED OTHERWISE:
<br />B.
<br />GENERAL PURPOSE OUTLETS SHALL BE STRAIGHT BLADE, 15 AMP, 125 VOLT
<br />9. THE ELECTRICAL PLAN DRAWINGS ARE GENERAL IN FORM AND DO NOTATTEMPTTO SHOW
<br />COMPLETE DETAILS OR LIST EVERY ITEM OF THE ELECTRICAL SYSTEMS, THE BUILDING
<br />1. ELECTRICAL METALLIC TUBING (EMT) - CONCEALED ABOVE GRADE AND EXPOSED IN
<br />C.
<br />GROUND FAULT INTERRUPTER (GFI) TYPE RECEPTACLES SHALL BE DUPLEX CLASS
<br />CONSTRUCTION OR THE VARIOUS EQUIPMENT (NEW OR EXISTING)', HOWEVER, THE ROUTING
<br />UTILITY ROOMS AND OTHER NON-PUBLIC AREAS NOT READILY VISIBLE TO BUILDING
<br />q, 15 AMP, 125 VOLT.
<br />OF RACEWAYS AND CIRCUITS, AND THE LOCATIONS OF EQUIPMENT, DEVICES, FIXTURES,
<br />OCCUPANTS.
<br />ETC. REPRESENT THE DESIRED FINISHED ARRANGEMENT; EXCEPT, AS GOVERNED BY
<br />D.
<br />FLUSH MOUNTED DEVICES SHALL HAVE SMOOTH STAINLESS STEEL WALLPLATES.
<br />STRUCTURAL OR MECHANICAL CONDITIONS OR OBSTRUCTIONS.
<br />.
<br />2FLEX- SHALL BE USED FOR FINAL CONNECTIONS TO VIBRATING EQUIPMENT&
<br />MAY BE SUBSTITUTED FOR EMT WHEN RUN CONCEALED WITHIN WALLS &
<br />CEILINGS WITHIN THE LIMITS OF NEC 517,
<br />F.
<br />ALL OUTLETS SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER(S) FROM
<br />10. CONTRACTOR SHALL COORDINATE WORK TO AVOID DISTURBANCE TO BUILDING
<br />WHICH HE DEVICE IS FED. LABELS SHALL BE HEAVY DUTY ADHESIVE TYPE, CLEAR
<br />OPERATIONS AND PERSONNEL, AND TO ALLOW ACCESS FOR BOTH PERSON TO AND
<br />WITH BLACK LETTERS ON LIGHT COLORED DEVICES AND CLEAR WITH WHITE
<br />WITHIN ALL PORTIONS OF THE FACILITY AND VEHICLES TO THE FACILITY. ACCESS TO
<br />3. MC CABLE -MAY NOT BE USED, EXCEPT FOR FIXTURE WHIPS INACCESSIBLE
<br />LETTERS ON DARK COLORED DEVICES. LETTERING SHALL BE 1/4" MINIMUM.
<br />OFFICE SPACES, CLASSROOMS, ETC. WILL NOT BE ALLOWED WHEN THEY ARE OCCUPIED.
<br />CEILING SPACE.
<br />SELF-ADHESIVE CIRCUIT NUMBERS, MASKING TAPE, PLASTIC PUNCH TYPE "DYMO"
<br />S ANY AND ALL COSTS INCURRED FO NON STANDARD HOURS, DOUBLE SHIFTS, OVERTIME,
<br />LABELS, ETC. ARE NOTACCEPTABLE.
<br />ETC. OR ANY OTHER COSTS ASSOCIATED WITH COMPLETING THE PROJECT WITHIN THE
<br />COMPLETION TIMES REQUIRED SHALL BE INCLUDED WITHOUT INCREASE IN CONTRACT
<br />g
<br />RACEWAYS AND CABLES THROUGHOUT THE FACILITY SHALL BE RUN CONCEALED IN
<br />31. CONTROL
<br />STATIONS AND DEVICES
<br />SUM.
<br />THE WALLS, ABOVE THE CEILING OR BELOW THE FLOOR WHERE POSSIBLE, EXCEPT,
<br />EXPOSED WITHIN UTILITY &OTHER NON-PUBLIC SPACES. WITHIN PUBLIC SPACES,
<br />A.
<br />PUSHBUTTONS, SELECTOR SWITCHES, POTENTIOMETERS, INDICATING LIGHTS, ETC.
<br />11. THE COMPLETED INSTALLATION SHALL DONE IN A NEAT& WORKMANLIKE MANNER,
<br />WHERE DUE TO THE BUILDINGS CONSTRUCTION, IT IS NOT POSSIBLE TO ROUTE
<br />SHALL BE HEAVY-DUTY TYPE, OIL -TIGHT TYPE. CONTACTS SHALL BE RATED MINIMUM
<br />SHALL SUITABLE FOR THE LOCATION, AND SHALL BE ACCORDANCE ALL LAWS,
<br />,
<br />RACEWAYS &CABLES CONCEALED, RACEWAYS MA BE RUN EXPOSED WHEN
<br />300 VOLT, 10 AMP AC AND DC CONTINUOUS. INDICATING LIGHTS SHALL BE PROVIDED
<br />&
<br />RULES ®ULATIONS IN EFFECT ATTHE SITE (INCLUDING THE LATEST EDITIONS OF
<br />N
<br />APPROVED BY ARCHITECT EXPOSED RACEWAYS SHALL BE RUN AS NEATLY &
<br />WITH THE LENS COLOR INDICATED. VOLTALL HIGHER INDICATING LIGHTS SHALL BE
<br />THE NATIONAL ELECTRICAL CODE, THE WASHINGTON STATE RULES ®ULATIONS
<br />UNOBTRUSIVELY AS POSSIBLE, SUPPORTED AS REQUIRED, PARALLEL OR AT RIGHT
<br />DEVICES
<br />TRANSFORMER TYPE. CONTROL DEVICES SHALL BE ALLEN-BRADLEY BULLETIN 800T,
<br />FOR INSTALLING ELECTRIC WIRES & EQUIPMENT, AND THE WASHINGTON STATE
<br />ANGLES TO CEILINGS, WALLS & STRUCTURAL MEMBERS.
<br />OR APPROVED EQUAL
<br />ENERGY CODE).
<br />C.
<br />RACEWAYS SHALL BE SIZED SO THAT THE CABLE FILL DOES NOT EXCEED 40%,
<br />B.
<br />CONTROL STATIONS, DEVICES, ETC. SHALL BE FLUSH MOUNTED WITH HEAVY DUTY
<br />12. CONTRACTORS ARE RESPONSIBLE FOR DETERMINING THE FIRE RATINGS
<br />EXCEPT, MINIMUM CONDUIT (& EQUIVALENT SURFACE METAL RACEWAY) SIZES
<br />STEEL COVERS AND BOXES AS REQUIRED.
<br />FOR WALLS, PARTITIONS AND OTHER BUILDING STRUCTURES. INSTALLATION OF
<br />I STALL TI
<br />SHALL BE AS FOLLOWS, UNLESS NOTED OTHERWISE:
<br />NEW SYSTEM COMPONENTS MUST MAINTAIN THE EXISTING FIRE RESISTIVE
<br />C.
<br />EMERGENCY SHUTDOWN PUSHBUTTON (EPO) SHALL BE SURFACE MOUTNED, GUARDED
<br />RATING OF THE PENETRATED BUILDING ELEMENT.
<br />A. 3/4" -BRANCH CIRCUITS, EXCEPTAS NOTED OTHERWISE.
<br />HEAD, RED COLOR, WITH AUDILHARY CONTACTS AND ENGRAVED NAMEPLATE INDICATING
<br />13. ALL SYSTEMS, EQUIPMENT, DEVICES, RACEWAYS, CABLES, ETC. INDICATED ARE
<br />D.
<br />ELECTRICAL METALLIC TUBING SHALL BE ELECTRO-GALVANIZED STEEL
<br />ITS FUNCTION.
<br />NEW UNLESS NOTED OTHERWISE.
<br />D
<br />TERMINAL BLOCKS CLAMP OR SCREW TYPE SHALL BEPROVIDED FOR ALL EXTERNAL
<br />E.
<br />NO CONDUIT SHALL BEND MORE THAN 270 DEGREES BEFORE THE END OF ITS
<br />WIRES ENTERING CONTROL STATIONS, ETC. WHERE SUITABLE TERMINALS ARE NOT
<br />14. ALL ELECTRICAL MATERIALS SHALL BE "UL" (UNDERWRITER'S LABORATORIES, INC.)
<br />RUN. BENDS IN CONDUITS SHALL BE MADE WITHOUT FLATTENING, KINKING OR
<br />AVAILABLE ON THE DEVICE. CONTROL WIRES SHALL NOT BE SPLICED OR TAPPED USING
<br />LISTED, LABELED AND APPROVED FOR THE SERVICE INTENDED WHERE UL STANDARDS
<br />REDUCING THE CROSS -SECTIONAL AREA OF THE CONDUIT. CONDUIT CUTS SHALL
<br />WIRE NUTS WITHOUTAPPROVAL FROM THE ENGINEER.
<br />HAVE BEEN ESTABLISHED. ALL ELECTRICAL MATE RHAL SHALL BE NEW UNLESS
<br />BE MADE SQUARE WITH A PROPER CUTTING TOOL. THE INSIDE AND OUTSIDE OF
<br />SPECIFICALLY NOTED OTHERWISE.
<br />ALL CONDUIT ENDS SHALL BE REAMED TO ELIMINATE BURRS AND ROUGH EDGES,
<br />E.
<br />EACH DEVICE SHALL HAVE A SUITABLE LEGEND.
<br />THEN WIPED CLEAN.
<br />15. ALL OPERATIONS SHALL BE CONDUCTED IN A MANNER TO AVOID THE RISK OF HARM TO
<br />F.
<br />CONTROL STATIONS, ETC. SHALL BE IDENTIFIED WITH LAMINATED PLASTIC NAMEPLATES,
<br />PERSONS OR DAMAGE TO PROPERTY. DAMAGE SHALL IMMEDIATELY BE REPAIRED.
<br />F.
<br />SUITABLE BUSHINGS SHALL BE USED ON ALL CONDUIT TERMINATIONS.
<br />BLACK FACE, WHITE CORE, ENGRAVED WITH MINIMUM 1181NCH LETTERS
<br />CONSTRUCTION EQUIPMENT & TOOLS SHALL BE IN GOOD OPERATING CONDITION, AND
<br />DESCRIBING ITS FUNCTION.
<br />BE DESIGNED FOR THE WORK REQUIRED. VERIFY WITH STRUCTURAL ENGINEER
<br />G.
<br />CONDUITSYSTEMS SHALL BE COMPLETE, SNAKED AND CLEANED BEFORE
<br />ACCEPTABLE LOCATIONS FOR CORE DRILLING FLOORS, WALLS, ETC. FOR CONDUIT
<br />PULLING ANY CABLE.
<br />32. LIGHTING
<br />ROUTING
<br />25. RACEWAY FITTINGS
<br />A.
<br />LIGHT EMITTING DIODE (LED) LUMINAIRES SHALL HAVE A LUMINOUS EFFICIENCY OF
<br />16. POWER INTERRUPTIONS (WHETHER TO THE ENTIRE SYSTEM ORTO INDIVIDUAL
<br />AT LEAST 100 LUMENS/W, AN ESTIMATED LIFE OF AT LEAST60,000 HOURS AT70%
<br />BUILDINGS, PANELS, EQUIPMENT, DEVICES, ETC.) SHALL BE KEPTTO AN ABSOLUTE
<br />A.
<br />CONNECTORS, COUPLINGS, ETC. FOR EMTSHALL BE STEEL SET -SCREW TYPE,
<br />LUMEN MAINTENANCE, AND SHALL INCLUDE A MINIMUM 5-YEAR WARRANTY ON
<br />MINIMUM, AND SHALL NOT BE DONE WITHOUT PRIOR APPROVAL, 2 WEEKS
<br />EXCEPT, STEEL RAINTIGHT COMPRESSION TYPE IN POTENTIALLY WET OR DAMP
<br />THE ENTIRE LUMINAIRE INCLUDING THE DRIVER. THE LUMINAIRE AND LEDS SHALL
<br />ADVANCED SCHEDULING & COORDINATION MEETING WITH THE OWNER. SECONDARY
<br />LOCATIONS.
<br />HAVE BEEN TESTED IN ACCORDANCE WITH LM-79 AND LM-80.
<br />VERIFICATION THAT POWER INTERRUPTION WILL OCCUR IS ALSO REQUIRED 48 HOURS
<br />PRIOR TO THE DATE OF OCCURRENCE.
<br />26. BOXES
<br />B.
<br />FIXTURES, LUMINAIRES, POLES, ETC. SHALL INCLUDE ALL NECESSARY MOUNTING
<br />AND CONNECTING ACCESSORIES.
<br />17. CABLE, BOXES, ETC. SHALL BE STORED OFF THE GROUND, PROTECTED FROM THE
<br />A.
<br />BOXES SHALL ACCOMMODATE ANY DEVICES TO BE INSTALLED AND SHALL BE
<br />WEATHER IN RACKS OR BINS, OR ON SHELVES. EQUIPMENT, WIRING DEVICES, CIRCUIT
<br />SIZED AS REQUIRED BY THE APPLICABLE CODES FOR NUMBERAND SIZE OF
<br />C.
<br />CONTRACTOR & LIGHTING FIXTURE SUPPLIER SHALL VERIFY DESCRIPTION &
<br />BREAKERS, ETC. SHALL BE STORED INDOORS IN A DRY, WARM AREA, FREE OF DUST &
<br />CONDUITS AND CABLES ENTERING AND LEAVING, EXCEPTMINIMUM AS NOTED
<br />CATALOG NUMBERS IN LIGHTING FXTURE SCHEDULE ON THE DRAWINGS MATCH
<br />ONE IN WHICH CONDENSATION WILL NOTOCCUR.
<br />BELOW.
<br />AND MOUNTING REQUIREMENTS ARE CORRECT ADVISE ENGINEER OF ANY
<br />CONFLICTS OR DISCREPANCIES.
<br />18. EQUIPMENT, BOXES, ETC. SHALL BE INSTALLED PLUMB & TRUE, AND BE FIRMLY
<br />B.
<br />INDOOR BOXES ABOVE GRADE IN DRY LOCATIONS SHALL BE STANDARD STAMPED
<br />SUPPORTED EITHER DIRECTLY OR INDIRECTLY BY A SOUND & SAFE STRUCTURAL
<br />GALVANIZED STEEL TYPE, SUITABLE FOR EMBEDMENT IN CONCRETE AND/OR
<br />33. LIGHTING CONTROLS
<br />MEMBER.
<br />MASONRY WHERE REQUIRED.
<br />A.
<br />LINE VOLTAGE DIMMER SWITCHES SHALL BE COMBINATION SINGLE POLE OR 3-WAY SWITCH
<br />19. ROUTING OF EXISTING CONDUITS INDICATED IS APPROXIMATE ONLY.
<br />C.
<br />UNLESS NOTED OTHERWISE, LARGER SIZE PULL AND JUNCTION BOXES SHALL BE
<br />WITH SLIDE DIMMER, 120/277V RATED SWITCH WITH SEPARATE 0-10V CONTROL OUTPUT,
<br />FABRICATED FROM CODE GAUGE GALVANIZED STEEL.
<br />SUITABLE FOR USE AS A STAND-ALONE WALL BOXSWITCH, IVORY COLOR WITH STAINLESS
<br />20. VERIFY ALL EQUIPMENT, DEVICE, ETC. LOCATIONS WITH THE OWNER PRIOR TO
<br />WALL PLATE. SWITCHES SHALL BE WATTSTOPPER CD4FBL, GREENGATE WBSD-01CM-Cl, OR
<br />ROUGH -IN.
<br />D.
<br />SWITCH, OUTLET, DEVICE, ETC. BOXES SHALL BE SINGLE OR GANGED TO
<br />APPROVED EQUAL.
<br />ACCOMMODATE THE REQUIRED NUMBER OF DEVICES; EXCEPT, FLUSH MOUNTED
<br />BOXES SHALL BE MINIMUM 4 INCHES SQUARE FOR CONDUITS 1 INCH OR LESS AND
<br />4-11116 INCHES SQUARE FOR LARGER CONDUITS. BOXES CONTAINING A SINGLE
<br />DEVICE SHALL BE MINIMUM 1-1/2 INCHES DEEP. BOXES CONTAINING MULTIPLE
<br />DEVICES SHALL BE MINIMUM 2-1/8 INCHES DEEP. FLUSH MOUNTED BOXES SHALL
<br />BE EQUIPPED WITH PLASTER RINGS AND SUITABLE WALLPLATES. SURFACE
<br />MOUNTED BOXES SHALL HAVE RAISED SURFACE TYPE COVERS.
<br />ELECTRICAL LEGEND
<br />IL GHTM
<br />0Ad RECE55ED LED DOUNLIGHT
<br />(Aa = FIXTURE TYPE A CONTROLLED
<br />BY SWITCH 5a, TYPICAL.)
<br />LED TROFFER LUMINAIRE
<br />SWITCHING
<br />5
<br />SINGLE POLE SWITCH
<br />THREE-WAY SWITCH
<br />Fa
<br />LINE VOLTAGE DIMMER SWITCH
<br />5e�
<br />LINE VOLTAGE 3-WAY DIMMER SWITCH
<br />OUTLETS
<br />DUPLEX OUTLET
<br />DOUBLE DUPLEX OUTLET
<br />MISCELLANEOUS
<br />BRANCH CIRCUIT CONDUIT, CONCEALED (OR 61MILAR
<br />5LASHE5 • NO. OF CIRCUIT CONDUCTOR5 WHERE APPLICABLE)
<br />HOMERJN TO LOCATION NDICATED, CONCEALED (TYPICAL)
<br />- ---- +-----
<br />CABLE RUN 'OPEN' IN ACCE6615LE CEILING 6PACE
<br />(SLA5HE5 = N. 4 TYPE OF CABLES WHERE APPLICABLE)
<br />- - - - - - - - -
<br />UNDERFLOOR OR BELOW GRADE CONDUIT
<br />-----
<br />EXISTING CONDUIT WITH NEW CABLE
<br />C
<br />CONDUIT STUB UP TO ACCESSIBLE CEILING SPACE
<br />m
<br />JUNCTION BOX
<br />O3
<br />EMERGENCY POWER OFF BUTTON
<br />I�
<br />PANELBOARD
<br />Ex
<br />EXISTING TO REMAIN
<br />REX
<br />REPLACE EXISTING
<br />REL
<br />RELOCATE EXISTING
<br />GFI
<br />GROUND FAULT INTERRUPTING
<br />DRAWING INDEX
<br />SHEET
<br />DRAWING TITLE
<br />EO.1
<br />ELECTRICAL - SPECIFICATIONS, LEGEND & INDEX
<br />E1.1
<br />ELECTRICAL - 1st FLOOR OVERALL PLAN
<br />E2.1
<br />ELECTRICAL - POWER PLAN & SCHEDULES
<br />E3.1
<br />ELECTRICAL - LIGHTING PLAN & SCHEDULES
<br />E4.1
<br />ELECTRICAL- EQUIPMENT CONNECTION PLAN
<br />E6.1
<br />ELECTRICAL - POWER SYSTEM RISER DIAGRAM
<br />E6.2
<br />ELECTRICAL - POWER SYSTEM RISER DIAGRAM
<br />E6.3
<br />ELECTRICAL - POWER SYSTEM RISER DIAGRAM
<br />i727 Oakes Ave.
<br />Suite 100
<br />Everett, WA 95201
<br />REVISIONS
<br />R. p
<br />1Q ap WA A
<br />O� S�I4794�G
<br />ONAL T
<br />O
<br />0
<br />W
<br />U
<br />p
<br />U
<br />;a
<br />m
<br />(�
<br />W
<br />W
<br />Q
<br />OD
<br />70
<br />0
<br />3
<br />L
<br />0
<br />U
<br />0
<br />}L
<br />ILL
<br />�
<br />N
<br />r
<br />W
<br />2341
<br />DeAw KL
<br />BID SET
<br />1-23-24
<br />ELECTRICAL -
<br />SPECIFICATIONS,
<br />LEGEND &
<br />INDEX
<br />E0.1