BACKFEED BREAKER SIZING <br /> MAX. CONTINUOUS OUTPUT 13.31A @ 240V <br /> 13.31 1XI 1.25 1 = 116.64AMPS 120A BREAKER-OK <br /> SEE 705.12 OF 2020 NEC <br /> 200 Xj 1.20 1 = 1240 <br /> 240 - 200 1 = 140A ALLOWABLE BACKFEED <br /> of wAs002880 <br /> $j� <br /> ISTER�� <br /> �,s,SjONALE�G� <br /> EXPIRES FEBRUARY 25,2026 <br /> STAMPED 06/12/2024 <br /> CLIENT: <br /> RONALD WATSON <br /> 2120 48TH ST SE,EVERETT,WA 98203 <br /> AHJ:CITY OF EVERETT <br /> (E)UTILITY UTILITY:SNOHOMISH PUD <br /> (E)200A RATED METER METER:76362395 <br /> MAIN SERVICE PANEL APN:005004-001-021-02 <br /> 1PH,120/240V 60HZ PHONE:(818)625-3242 <br /> (E)200A/2P MAIN EMAIL:RONW91340@GMAIL.COM <br /> BREAKER <br /> (TOP FED) <br /> SYSTEM: <br /> SYSTEM SIZE(DC):11 X 410=4.510 kW <br /> SYSTEM SIZE(AC):3.190 kW @ 240V <br /> MODULES:11 X HANWHA QCELL:Q.PEAK <br /> DUO ELK ML-G10+410 <br /> MICROINVERTERS:11 X ENPHASE <br /> BRANCH CABLES INTEGRAL TO TO OTHER LOADS IQ8PLUS-72-2-US <br /> INVERTERS 1#6 AWG,BARE (N)30A RATED T <br /> COPPER GROUND (N)ENPHASE VISIBLE LOCKABLE LABELEDDIS •/r\I <br /> JUNCTION COMBINER BOX EATON DG221URB(OR • <br /> ENPHASE IQ8PLUS-72-2-US EQUIVALENT) <br /> MICROINVERTERS BOX KNIFEBLADE,LOCKABLE, (N)20A/2P PV BREAKER <br /> NEMA 3R ^ NEMA 3R,UL LISTED • <br /> f 1 TO UTILITY <br /> STRING-1 (N)20A/2P OVERHEAD <br /> 11 HANWHA QCELL:Q.PEAK DUO BLK N _ ______ ----------_--- --- • ----- ------------------_------- FEED <br /> ML-G10+410 1' -- I ^ ` <br /> (N)15A/2P I II REVISIONS <br /> Q GATEWAY NO. REVISED BY DATE <br /> 3-#10 AWG,THWN-2 3-#10 AWG,THWN-2 L------------ <br /> 2-#10 AWG,THWN-2 1-#10 EGO,THWN-2 1-#10 EGO,THWN-2 <br /> 1-#10 EGO,THWN-2 IN 3/4"OR LARGER EMT IN 3/4"OR LARGER EMT - - - <br /> IN 3/4"EMT CONDUIT CONDUIT CONDUIT - - - <br /> freedom- <br /> FOREVER <br /> FREEDOM FOREVER LLC <br /> 43445 BUSINESS PARK DR#110,TEMECULA, <br /> CA 92590 <br /> Tel:(800)385-1075 <br /> GREG ALBRIGHT <br /> �� g�N— <br /> CONTRACTOR LICENSE: <br /> ELECTRICAL ADMINISTRATOR ALBRIG*807C1 <br /> NOTE: <br /> CONDUIT AND CONDUCTORS SPECIFICATIONS ARE BASED <br /> ON MINIMUM CODE REQUIREMENTS AND ARE NOT MEANT THREE LINE DIAGRAM <br /> TO LIMIT UP-SIZING AS REQUIRED BY FIELD CONDITIONS JOB NO: DATE: DESIGNED BY: SHEET: <br /> 449034 6/12/2024 Z.C. PV-4 <br />