Laserfiche WebLink
14 1 Bosch IDS BOVA 2.0 Product Specifications <br /> 6 Suction Corrected Factor <br /> BOVA-Suction Line Connection Size 3/4 3/4 7/8 7/8 <br /> 3/4 STD 3/4 STD 7/8 STD 7/8 STD <br /> Suction Line Run-Feet <br /> 5/8 OPT 5/8 OPT 3/4 OPT 3/4 OPT <br /> Standard 1 1 1 1 <br /> 25' <br /> Optional 1 0.99 0.99 0.98 <br /> Standard 0.99 0.99 0.99 0.99 <br /> 50' <br /> Optional 0.99 0.98 0.98 0.97 <br /> Standard 0.99 0.98 0.98 0.97 <br /> 100' <br /> Optional 0.98 0.95 0.97 0.95 <br /> Standard 0.97 0.96 0.96 0.95 <br /> 150' <br /> Optional 0.96 0.93 0.95 0.93 <br /> Table 11 <br /> Std:Standard size <br /> Opt:Optional size <br /> aUsing suction line larger than shown in chart will result in poor oil return <br /> 1 and is not recommended. <br /> 7 Sound Data <br /> Sound Power Level Full Octave Linear Sound Power Level c: Power <br /> ,• �: ======== <br /> 1 ®= 11 = 111X111 :111Sound Blanket <br /> 56(Low) 26.1 28.9 37.5 44.4 48.1 42.5 47.1 40.7 <br /> 3 Ton <br /> 77(High) 48.4 54.3 60.5 66.2 68.7 63.6 62.3 53.7 Sound Blanket- <br /> 60(Low) 30.5 36.0 47.6 50.1 48.5 50.1 50.5 41.3 Standard <br /> 5 Ton <br /> 79(High) 51.6 47.6 62.3 67.0 68.6 64.2 64.6 56.5 <br /> Table 12 IDS Sound power level <br /> Data subject to change 04.2019 1 Bosch Thermotechnology Corp. <br />