HVAC GENERAL NOTES <br />1. VERIFY SITE CONDITIONS. <br />2. THERMOSTAT LOCATIONS: VERIFY ALL WALL MOUNTED CONTROL LOCATIONS WITH <br />ARCHITECT/GC. <br />3. CODES: COMPLY WITH ALL LOCAL & STATE GOVERNING CODES. <br />4. COORDINATE DUCTWORK AND GRILLE LOCATIONS WITH LIGHTING AND OTHER RELATED TRADES <br />WITH ARCHITECT APPROVAL. VERIFY CLEARANCES & CEILING ELEVATIONS BEFORE <br />INSTALLATION. <br />5. DRAWINGS ARE SCHEMATIC IN SOME AREAS AND MAY NOT SHOW EXACT ROUTING OR EVERY <br />OFFSET WHICH MAY BE REQUIRED. <br />6. SEISMIC BRACING: PROVIDE TO MEET LOCAL CODE REQUIREMENTS. REFER TO THE ASHRAE <br />STANDARDS "PRACTICAL GUIDE TO SEISMIC RESTRAINT", 2021. <br />7. EXHAUST FAN TERMINATION: SHALL NOT BE LESS THAN 3 FEET FROM A PROPERTY LINE OR <br />OPENINGS INTO A BUILDING, E.G., OPERABLE WINDOWS AND DOORS, OR DISTANCE AS REQUIRED <br />PER LOCAL CODE. <br />8. TEST, ADJUST, & BALANCE: PROVIDE PROPER SYSTEM TESTING, ADJUSTING, AND BALANCING, <br />INCLUDING WRITTEN REPORTS TO BE PROVIDED TO OWNER. BALANCE TO WITHIN 10% OF DESIGN. <br />9. OPERATION & MAINTENANCE BOOKLET: PROVIDE 0 & M MANUAL TO OWNER. INCLUDE CUT <br />SHEETS ON MAIN EQUIPMENT AND CONTROLS, MAINTENANCE INSTRUCTIONS, AND MARKED UP <br />AS -BUILT DRAWING. <br />10. COMMISSIONING: PRIOR TO PASSING THE FINAL INSPECTION OR OBTAINING A CERTIFICATE OF <br />OCCUPANCY, PROVIDE THE EVIDENCE OF SYSTEM COMMISSIONING AND COMPLETION IN <br />ACCORDANCE WITH THE PROVISIONS OF SECTION C408 OF THE 2021 WSEC <br />11. WALK-THRU INSTRUCTION: PROVIDE ON SITE WALK-THRU FOR CUSTOMER TO DEMONSTRATE <br />OPERATION OF SYSTEM AND ANSWER QUESTIONS. <br />12. ROOF TOP UNITS ON CURB: SEAL HOLES AND CRACKS BETWEEN DUCT AND ROOF DECK INSIDE <br />FACTORY ROOF CURB FOR NOISE CONTROL. <br />13. GAS PIPE: SCHEDULE 40, BLACK STEEL. PAINT PIPE EXPOSED TO WEATHER. <br />14. SIZES: ALL PIPE SIZES SHOWN ARE MINIMUM. <br />15. PIPE HANGERS: SWIVEL LOOP STYLE, MICHIGAN NO.100 OR CLEVIS STYLE, NO.400 OR EQUAL <br />BRAND, WITH ALTHERED STEEL ROD SIZED PER INDUSTRY STANDARDS. <br />16. ELECTRICAL: ALL EQUIPMENT TO HAVE A POSITIVE MEANS OF DISCONNECT ADJACENT TO AND IN <br />SIGHT FROM EQUIPMENT SERVED. PROVIDE A 120 VOLT RECEPTACLE LOCATED WITHIN 25 FEET <br />OF EQUIPMENT FOR SERVICE & MAINTENANCE PURPOSES (2021 IMC SECTION 301.10). LINE <br />VOLTAGE WORK BY OTHERS. <br />17. SUSPENDED MECHANICAL EQUIPMENT AND APPLIANCES SHALL HAVE RIGID VERTICAL HANGERS <br />AND BE BRACED IN BOTH HORIZONTAL DIRECTIONS. <br />DUCT NOTES <br />1. DUCT CONSTRUCTION AND INSTALLATION PER LATEST SMACNA STANDARDS <br />AND THE 2021 IMC AS REQUIRED BY THE LOCAL CODE. PROVIDE METAL DUCT, <br />EXCEPT AS NOTED. <br />2. BALANCING DAMPERS: PROVIDE ON ALL SUPPLY RUN OUT DUCTS UP STREAM <br />OF DIFFUSERS. <br />3. DUCT INSULATION: DUCTS, SHAFTS AND PLENUMS SHALL BE INSULATED TO <br />MINIMUM OF R-8 AND IN ACCORDANCE WITH THE SECTION C403.2.8 OF 2021 <br />WSEC. <br />4. DUCT SEALING -GENERAL: 0 TO 2" STATIC PRESSURE- SEAL ALL TRANSVERSE <br />JOINTS AND LONGITUDINAL SEAMS ON ALL DUCTS. ABOVE 2"-SEAL SEAMS, <br />JOINTS AND WALL PENETRATIONS. INSIDE BUILD: DURODYNE "DDS-181" GRAY <br />OR APPROVED EQUAL PER UL 181 A-M, 181B-M LISTED. OUTSIDE: <br />POLYURETHANE, MAMECO VULKEM 116. OR APPROVED EQUAL. <br />5. TURN VANES: PROVIDE SINGLE THICKNESS TURN VANES (SEE DETAIL) IN ALL <br />MAJOR SQUARE DUCT ELBOWS, TEES, OR TURNS WITH INSIDE RADIUS LESS <br />THAN 3/4 DUCT WIDTH. SQUARE BRANCH DUCT TAPS SHALL BE 45 DEGREE <br />TYPE PER SMACNA STANDARD. <br />6. FLEX DUCT (INSULATED): FOR GRILLE RUN OUTS UP TO 6 FT. LONG, EXCEPT AS <br />NOTED. PROVIDE ADJUSTABLE METAL ELBOWS ON ALL TURNS, UNLESS A <br />SMOOTH FULL RADIUS TURN IS MADE. SECURE CORE WITH APPROVED NYLON <br />OR METAL WORM DRIVE CLAMPS. NO DUCT TAPE JOINTS & SCREWS ALLOWED. <br />7. SOUND LINER: PROVIDE SOUND LINED METAL SUPPLY & RETURN DUCTS AS <br />SHOWN ON PLANS. MANVILLE PERMACOTE LINACOUSTIC FLEXIBLE <br />FIBERGLASS LINER, WITH ACRYLIC SURFACE TREATMENT OR EQUAL. <br />FABRICATE AND INSTALL PER DUCT LINER STANDARD OF NORTH AMERICAN <br />INSULATION MANUFACTURER'S ASSOC. OUTSIDE AIR DUCT IS NOT <br />INSULATED THROUGH UNCONDITIONED AREA. <br />8. FLEX CONNECTORS: PROVIDE ON ALL DUCT HOOK-UPS TO ISOLATE AIR <br />HANDLING EQUIPMENT. (NEOPRENE COATED FIBERGLASS FABRIC TYPE) <br />9. DUCT SIZE CHANGES: ROUND GALVANIZED DUCTS MAY BE SUBSTITUTED FOR <br />RECTANGULAR DUCTS THAT ARE NOT LINED. PROVIDE CIRCULAR <br />EQUIVALENT OF RECTANGULAR DUCT. OTHER EQUIVALENT RECTANGULAR <br />DUCT SIZES MAY BE SUBSTITUTED TO BETTER FIT SPACE. <br />10. TEMPORARY DUCT CLOSURE: SEAL OFF DUCTWORK DURING CONSTRUCTION <br />TO KEEP OUT CONSTRUCTION DUST, ESPECIALLY FLOOR BOOTS AND LOW <br />WALL OPENINGS. <br />HEAT PUMP UNIT <br />SCHEDULE <br />TAG <br />TOT <br />CAAPACITPACIT ING Y <br />BTU/H <br />HEATING <br />CAPACITY <br />BTU/H <br />ELECTRICAL <br />REFRIGERANT <br />CONNECTIONS <br />SOUND <br />(DBA) <br />REFRIGERANT <br />MANUFACTURER /MODEL # <br />WEIGHTNOTES <br />(LBS) <br />OUTDOOR UNIT <br />COMPRESSOR <br />SEER <br />EER <br />VOLTS PH/HZ <br />MCA <br />MOCP <br />RLA <br />GAS PIPE <br />LIQ PIPE <br />CU-215A <br />18,000 <br />18,900 <br />208-230 / 1 / 60 <br />15.8 <br />1 20 <br />- <br />18.9 <br />12.5 <br />Y8" x 2 <br />Y4" x 2 <br />50-51 <br />R - 32 <br />DAIKIN 2MXS18NMVJUA <br />123 <br />1,2 <br />NOTES: <br />1. INSULATE EXTERIOR REFRIGERATION LINES WITH UV PROTECTED 1"ARMAFLEX, INTERIOR REFRIGERATION LINES WITH 1/2" ARMAFLEX <br />2. ELECTRICAL CONNECTION (BY OTHERS) <br />AIR HANDLER SCHEDULE <br />TAG <br />SERVICE LOCATION <br />NOMINAL <br />TONS <br />GAS PIPE <br />CONNECTION <br />LIQUID PIPE <br />CONNECTION <br />CONDENSATE <br />CONNECTION <br />WEIGHT <br />(LBS) <br />COOLINGTOTAL <br />(BTU/H) <br />HEATING <br />(BTU/H) <br />MANUFACTURER/ <br />MODEL # <br />ELECTRICAL <br />VOLTS / PH / HZ <br />NOTES <br />AH-1A <br />OFFICE <br />.75 <br />%" <br />y" <br />%" <br />28 <br />9000 <br />DAIKIN FTXS09WVJU9 <br />208 - 230 / 1 / 60 <br />1-3 <br />AH-2A <br />OPEN OFFICE <br />.75 <br />%° <br />Y4" <br />%" <br />28 <br />9000 <br />DAIKIN FTXS09WVJU9 <br />208 - 230 / 1 / 60 <br />1-3 <br />NOTES: <br />1. INSTALL GOBI CONDENSATE PUMP. <br />2. SET THERMOSTAT TO 70"F, COOLING ONLY. <br />3. INTERIOR UNIT IS POWERED FROM OUT DOOR UNIT WITH CONTINUOUS WIRING. COORDINATE WITH ELECTRICIAN. <br />LEGAL DESCRIPTION: <br />SECTION 18 TOWNSHIP 29 RANGE 05 QUARTER SW BLDG ONLY LOC ON LAND PARCEL <br />29051800300800 <br />TAX PARCEL NUMBER: <br />29051800301300 <br />SCOPE OF WORK: <br />1. LIKE FOR LIKE REPLACEMENT OF EXISTING CONDENSER ON THE ROOF AND <br />EXISTING AIR -HANDLERS ON THE 1ST FLOOR. <br />a VICINITY MAP <br />NTS <br />SHEETINDEX <br />SHEET# <br />DRAWING TITLE <br />M-1 <br />LEGEND & ABBREVIATIONS, VICINITY MAP, NOTES, EQUIPMENT SCHEDULE <br />M-2 <br />EXISTING ROOF PLAN <br />M-3 <br />INTERIOR SECTION / DETAILS <br />SYMBOLS SCHEDULE <br />SYMBOL <br />DESCRIPTION <br />SYMBOL <br />DESCRIPTION <br />® ® <br />SUPPLY DUCT <br />® <br />SMOKE DETECTOR <br />0 E] <br />RETURN/EXHAUST DUCT <br />❑T <br />TIMER 0-4 HR ADJUSTABLE <br />r� <br />SOUNDLINED DUCT <br />Q <br />THERMOSTAT <br />Sf-1 <br />MANUALDAMPER <br />0 <br />SENSOR <br />MOTORIZED DAMPER <br />SENSOR (CEILING MOUNT) <br />M <br />z <br />EXHAUSTFAN <br />FLEX DUCT <br />m <br />EXHAUST UP <br />TURNING VANES <br />------ 0 <br />PIPE/DUCT UP <br />END CAP <br />J <br />PIPE/DUCT DOWN <br />® <br />SUPPLY DIFFUSER/MAKEUP AIR <br />PIPE TEE DOWN <br />GRILLE <br />O <br />PIPE TEE UP <br />RETURN/EXHAUST/TRANSFER <br />GRILLE <br />VALVE <br />® <br />BACKDRAFT DAMPER <br />BALANCING VALVE <br />® <br />DUCT REDUCERS <br />- <br />HIDDEN/EXISTING EQUIPMENT <br />SIDEWALL SUPPLY/MAKEUP <br />NEW EQUIPMENT <br />SIDEWALL RETURN/EXHAUST <br />CONTINUATION BREAKLINES <br />XX-# <br />EQUIPMENTTAG <br />CD <br />DEMO <br />REVISION CLOUD <br />AIR TERMINAL LEGEND <br />XX 8x8 NECK SIZE, WxH, SQUARE OR <br />GRILLE, REGISTER, 140 RECTANGULAR <br />DIFFUSER IN LEGEND <br />AIR QUANTITY (CFM) <br />XX 80 NECK SIZE ROUND <br />140 <br />AIR QUALITY (CFM) <br />AIR TERMINAL LEGEND NOTES: <br />1. ALL DUCT <br />AND GRILLE SIZES ARE IN INCHES UNLESS NOTED OTHERWISE. <br />2. -/- ARROWS INDICATE AIR PATTERN FOR <br />CEILING DIFFUSERS. NO ARROWS INDICATE <br />FOUR WAY PATTERN. <br />ABBREVIATIONS <br />ABBREVIATION <br />DEFINITION <br />ABBREVIATION <br />DEFINITION <br />AFF <br />ABOVE FINISHED FLOOR <br />NTS <br />NOT TO SCALE <br />ADJ <br />ADJACENT <br />01 <br />OUTSIDE AIR <br />BD, BDD <br />BACKDRAFT DAMPER <br />OAI <br />OUTSIDE AIR INTAKE <br />BS <br />BIRD SCREEN <br />OTS <br />OPEN TO STRUCTURE <br />BSC <br />BIOLOGICAL SAFETY CABNET <br />(R) <br />RELOCATED <br />BWG <br />BOTTOM WALL GRILL <br />RA <br />RETURN AIR <br />CFH <br />CHEMICAL FUME HOOD <br />RD <br />ROUND DIFFUSER <br />CFM <br />CUBIC FEET PER MINUTE <br />RG <br />RETURN GRILLE <br />IDS <br />DUCT BOARD <br />SA <br />SUPPLY AIR <br />ON <br />DOWN <br />SD <br />SMOKE DETECTOR <br />EA <br />EXHAUST AIR <br />SC <br />SOUND CAN <br />EC <br />END CAP <br />SHC <br />SENSIBLE HEATING CAPACITY <br />EG <br />EXHAUST GRILL <br />SL <br />SOUNDLINED DUCT <br />ERV <br />ENERGY RECOVERY <br />VENTILATOR <br />TC <br />TOTAL COOLING <br />(E) / EXIST <br />EXISTING <br />TG <br />TRANSFER GRILLE <br />FC <br />FLEX CONNECTOR <br />TV <br />TRANSFER VANES <br />L, S <br />LIQUID, SUCTION <br />TWG <br />TOP WALL GRILLE <br />MG <br />MAKEUP GRILLE <br />TYP <br />TYPICAL <br />N <br />NECK <br />VD <br />VOLUME DAMPER <br />(N) <br />NEW <br />VEL <br />VELOCITY <br />NIC <br />NOT IN CONTRACT <br />WH <br />WATER HEATER <br />w KEYPLAN - AREA OF WORK <br />S N SCALE:NTS <br />E <br />Air Conditioning <br />Heating <br />Controls <br />Sales <br />C Service <br />Installation <br />"QUALITY ASSURED" <br />pacific air control, inc. <br />1916 220th Street BE Suite M101 <br />Bothell, WA 98011 <br />ph: (206)682-6393 fax: (206)340-2270 <br />Contractor's License No.: PACIFAC230P8 <br />www.pacificaircontrol.com <br />NW <br />w <br />W <br />W <br />LL <br />O <br />LL <br />0 <br />a- <br />r <br />Z <br />W <br />2 <br />�W <br />V <br />Q <br />J <br />a - <br />NW <br />w <br />Z <br />5W <br />^G <br />I.i <br />W <br />O <br />W00 <br />_ CV <br />a) <br />LU <br />Q <br />W <br />w <br />�j W <br />00 <br />CV W <br />ti <br />T <br />o GATE DREVIDEGN <br />617124 REVIW SET <br />THIS DRAWING IS THE SOLE PROPERTY OF PACIFIC <br />CONTROL, INC. ANY REPRODUCTION, DUPLICATION, <br />ADDITIONS AND/OR MODIFICATIONS REQUIRE THE <br />WRITTEN APPROVAL OF PACIFIC AIR CONTROL, INC. <br />RiDIECT MANAGER DESIGNED BY <br />DID RML/DD <br />➢RAMN BY CHECKED BY <br />RML DO <br />SCAT£ PROJECT ND. <br />AS NOTED 240541 <br />ORANING TIRES <br />LEGEND & ABBREVIATIONS <br />VICINITY MAP, NOTES, <br />EQUIPMENT SCHEDULES <br />M-1 <br />1 OF 3 <br />