Laserfiche WebLink
6 of 23 ' <br /> A PROJECT NO. SHEET NO. <br /> �'4111P <br /> � S240102-1 XR <br /> % r <br /> PROJECT 7423 Lower Ridge Rd, Everett, WA <br /> LONGITUDE SUBJECT Foundation Stabilization/Jacking <br /> ONE TWENTY° <br /> ENGINEERING&DESIGN BY PAM DATE 03/05/24 <br /> Ideal Foundation Systems2-7/rQ Helical Pile(0.203-inch wall thickness)-Soil Capacity per ESR-3750 • <br /> DIGGA 6K Drive Head Torque Correlation Factor, IC, Ultimate Axial Compressive Allowable Axial Compressive <br /> Pressure Torque,T Compression Capacity, P,=K,`T Capacity, P,=0.51P, <br /> (psi) ( ) <br /> (ft.') (kips) (kips) <br /> 500 1,554 9 14.0 7.0 <br /> 600 1,865 9 16.8 8.4 <br /> 700 2,176 9 19.6 9.8 <br /> 800 2,486 9 22.4 11.2 <br /> 900 2,797 9 25.2 12.6 <br /> 1000 3,108 9 28.0 14.0 <br /> 1100 3,419 9 30.8 15.4 <br /> 1200 3,730 9 33.6 16.8 <br /> 1300 4,040 9 36.4 18.2 <br /> 1400 4,351 9 39.2 19.5 <br /> 1500 4,662 9 42.0 21.0 <br /> 1600 4,973 9 44.8 22.4 <br /> 1700 5,284 9 47.6 23.8 <br /> 1800 5,594 9 50.3 25.2 <br /> 1900 5,905 9 53.1 26.6 <br /> 2000 6,216 9 55.9 28.0 <br /> MAX 2100 6,527 9 58.7 29.4 <br /> i.)DIGGA 6K Drive Head differential pressure display to torque output has been pulled from the attached conversion charts provided by DIGGA. <br /> ii.)Per Table 5A of ESR-3750,the maximum installation torque rating of a 2-7/8"0 helical pile(0.203-inch wall thickness)is 8,300ft•Ibs.Per Ideal <br /> Manufacturing,Inc.,the maximum installation torque rating of a 2-7f8"0 helical pile(0.203-inch wall thickness)is 8,000 ft'Ibs.Final installation torque shall not <br /> exceed the lesser of these limiting values. <br /> iii.)Piles shall reach a torque that correlates with an allowable capacity that meets or exceeds the maximum allowable load demand as listed in the structural <br /> package,but shall not exceed the maximum allowable capacity for any part of the pile assembly. <br /> iv.)Refer to ESR-3750 and Ideal Manufacturing,inc.documents for additional information and requirements. <br /> v.)Definitions per ESR-3750: <br /> T=Final Installation torque in ft"lbs;the last torque reading taken during pile installation,using,for example,the torque reading <br /> instruments connected to the installation equipment. <br /> IC,=Torque correlation factor per ESR-3750 <br /> Pa=Ultimate axial compressive capacity(in kips)of helical pile <br /> Pa=Allowable axial compressive capacity(in kips)of helical pile <br /> vi.)For torque readings between those listed,use the following equation to determine the allowable capacity:P,=(T'K0)/2 <br /> vii.)1 kip=1,000 lbs <br /> L120 ENGINEERING&DESIGN <br />