Laserfiche WebLink
411 Hydraulic Overview <br />Job Number: 1 <br />Report Description: Residential (3) <br />Job <br />Job Number <br />Design Engineer <br />1 <br />Job Name: <br />Gebremariam AFH (Convert Garage) <br />Phone <br />FAX <br />Address 1 <br />1725 106th St. SW <br />State C.Mfioation/License Number <br />Add...2 <br />Everett, WA <br />AHJ <br />Address 3 <br />Job Site/BufldmNor- <br />Density <br />0.05gpm/ft2 <br />Area of Application <br />256ft2 (Actual 157ft2) <br />Most Demanding Sprinkler Data <br />Hose Streams <br />4.9 K-Factor 12.96 at 7.000 <br />0.00 <br />Coverage Per Sprinkler <br />Number Sprinklers Calwlated Number U Sprinklere Calculated <br />256ft2 <br />1 0 <br />System Pressure Demand <br />System Flow Demand <br />25.466 <br />12.96 <br />Total Demand <br />12.96 @ 25.466 <br />Pressure Result <br />+60.705 (70.4%) <br />Supplies <br />Check Point Gauges <br />Node Name Flow m Hose Flow(gpm) Static si Residual(psi) <br />Identifier Pressure(psi) K-Factor(K) Flow m <br />1 Water Supply 20.00 92.000 79.000 <br />Gebremariam AFH Fire Sprinkler Plan <br />Water Supply at Node 1 (20.00, 0.00, 92.000, 79.000) <br />----------t <br />1 <br />100 <br />Static <br />Pressure 92.000 <br />80 <br />0.00 <br />@ 79.000 <br />70 <br />60 <br />N <br />Q <br />°' 50 <br />fn <br />to <br />a 40 <br />30 <br />12.96 @ 25.466 <br />20 <br />System demand curve <br />10 <br />0 <br />16 24 32 <br />40 <br />048 <br />12 20 28 <br />36 <br />Water flow, gpm <br />L� © M.E.P.CAD, Inc. 41 AutoSPRINK 2019 v15.1.25.0 2/21/2024 3:06:03PM Page 1 <br />