EROSION CONTROL NOTES.• <br />1. APPROVAL OF THIS EROSION/SEDIMENTATION CONTROL (ESC) PLAN DOES <br />NOT CONSTITUTE AN APPROVAL OF PERMANENT ROAD OR DRAINAGE DESIGN <br />(E.G. SIZE AND LOCATION OF ROADS, PIPES, RESTRICTORS, CHANNELS, <br />RETENTION FACILITIES, UTILITIES). <br />2. THE IMPLEMENTATION OF THESE ESC PLANS AND THE CONSTRUCTION, <br />MAINTENANCE, REPLACEMENT, AND UPGRADING OF THESE ESC FACILITIES IS <br />THE RESPONSIBILITY OF THE APPLICANT/CONTRACTOR UNTIL ALL CONSTRUCTION <br />IS COMPLETED AND APPROVED AND VEGETATION/LANDSCAPING IS ESTABLISHED. <br />3. THE BOUNDARIES OF THE CLEARING LIMITS SHOWN ON THIS PLAN SHALL <br />BE CLEARLY FLAGGED IN THE FIELD PRIOR TO CONSTRUCTION. DURING THE <br />CONSTRUCTION PERIOD, NO DISTURBANCE BEYOND THE FLAGGED CLEARING <br />LIMITS SHALL BE PERMITTED. THE FLAGGING SHALL BE MAINTAINED BY THE <br />APPLICANT/CONTRACTOR FOR THE DURATION OF CONSTRUCTION. <br />4. THE ESC FACILITIES SHOWN ON THIS PLAN MUST BE CONSTRUCTED IN <br />CONJUNCTION WITH ALL CLEARING AND GRADING ACTIVITIES, AND IN SUCH A <br />MANNER AS TO ENSURE THAT SEDIMENT AND SEDIMENT LADEN WATER DO <br />NOT ENTER THE DRAINAGE SYSTEM, ROADWAYS, OR VIOLATE APPLICABLE WATER <br />QUALITY STANDARDS. <br />5. THE ESC FACILITIES SHOWN ON THIS PLAN ARE THE MINIMUM <br />REQUIREMENTS FOR ANTICIPATED SITE CONDITIONS. DURING THE CONSTRUCTION <br />PERIOD, THESE ESC FACILITIES SHALL BE UPGRADED AS NEEDED FOR <br />UNEXPECTED STORM EVENTS AND TO ENSURE THAT SEDIMENT AND <br />SEDIMENT -LADEN WATER DO NOT LEAVE THE SITE. <br />6. THE ESC FACILITIES SHALL BE INSPECTED ROUTINELY AND MAINTAINED <br />BY THE APPLICANT/CONTRACTOR TO ENSURE THEIR CONTINUED FUNCTIONING, <br />ESPECIALLY AFTER STORM EVENTS. <br />7. THE ESC FACILITIES ON INACTIVE SITES SHALL BE INSPECTED AND <br />MAINTAINED A MINIMUM OF ONCE A MONTH OR WITHIN THE 48 HOURS <br />FOLLOWING A MAJOR STORM EVENT. <br />8. AT NO TIME SHALL MORE THAN ONE FOOT OF SEDIMENT BE ALLOWED TO <br />ACCUMULATE WITHIN A TRAPPED CATCH BASIN. ALL CATCH BASINS AND <br />CONVEYANCE LINES SHALL BE CLEANED PRIOR TO PAVING. THE CLEANING <br />OPERATION SHALL NOT FLUSH SEDIMENT LADEN WATER INTO THE DOWNSTREAM <br />SYSTEM. <br />9. STABILIZED CONSTRUCTION ENTRANCES SHALL BE INSTALLED AT THE <br />BEGINNING OF CONSTRUCTION AND MAINTAINED FOR THE DURATION OF THE <br />PROJECT. ADDITIONAL MEASURES MAY BE REQUIRED TO ENSURE THAT ALL <br />PAVED AREAS ARE KEPT CLEAN FOR THE DURATION OF THE PROJECT. <br />10. THE CONTRACTOR SHALL PROVIDE PERIODIC STREET CLEANING TO <br />REMOVE DEBRIS AND SEDIMENT TRACKED OFF THE SITE. <br />11. APPROPRIATE MEASURES SHALL BE TAKEN TO STOP SEDIMENT FROM <br />ENTERING SURFACE WATER BODIES IF THE PROPOSED BMPS FAIL. <br />12. BARE AND/OR DISTURBED SOILS SHALL REMAIN UNCOVERED AND/OR <br />UNSTABILIZED FOR NO MORE THAN 2 DAYS FROM OCTOBER 1 THROUGH APRIL <br />30, AND FOR NO MORE THAN 7 DAYS FROM MAY 1 THROUGH SEPTEMBER 30. <br />SW 1/4, SE 1/4, SEC.13, T.28N., R.4E., W.M. <br />CITY OF EVERETT, SNOHOMISH COUNTY, WA <br />i <br />i <br />i <br />cn N89' 12'20 "E <br />-- -- -- <br />\ 200.00' <br />l \ / EX CB <br />l \ i RIM=573.64' <br />l \ IE 12" DIP(W)=571.58' <br />cl <br />0 <br />TAXI 00869400000400 <br />i <br />S D INSTALL DEPRESSION AREA NEAR NEW <br />\ CBI WALL AREA TO TEMPORARILY CONTAIN <br />/ �c SURFACE WATER RUNOFF DURING <br />/ o �3 \ CONSTRUCTION. HELD WATER SHALL BE <br />IE 4" PVC(SW)=573.70'(lBR) PERIODICALLY PUMPED AND HAULED TO A <br />'- CITY APPROVED DISPOSAL SITE. <br />/ \ TAXI 00480200700600 9' WALL <br />TOP=575 0 <br />Z. TOE=566.0 <br />I � I a (5 CLF) r <br />PROPOSED BUILDING <br />d>< I ° a C \� FOOTPRINT - 566 _ <br />w " (5 CLF) g • 1 '2 "E 90 00'GLF <br />N89 12 20 Ewag <br />REMOVE EX. DWY CUT 40.0 ' S F�� F� _ SF <br />SF SF SF SF SF <br />AND REPLACE WITH <br />co <br />SIDEWALK DTL PER <br />C.O.E. <br />° / G / � N TAX# 00869400000300 <br />T.B.M. 9 <br />ELEV 574.64 CAP EXISTING SIDE SEWER ° I 573.65(MR) <br />AT PROPERTY LINE UNTIL IT ) \ <br />MAGNETIC NAIL SET WEST SIDE OF IS REUSED FOR NEW UNIT <br />VERTICAL DATUM: EAST BACK OF WALK, 6 NORTH SS \ <br />NAVD88 OF TELEPHONE PEDESTAL. DISCONNECT EXISTING \�TE4�PRARY CONSTRUCTION V` <br />N <br />WATER METER BEHIND ENTRANCE PER S DTL 1 3-1 C- / <br />METER AT PROPERTY LINE T�/ \ "vs <br />�' <br />LEGEND INSTALL CB INSER S ON ALL <br />NEW CBS AFTER INSTALL 2 <br />FENCE (AS NOTED) ST DTL 210 s� / \ 7 I I E �" PVC (W) = 5 73. (Tf�R) - T WALL <br />I / s / h / o TOP=575.0 <br />SS '> EXISTING SANITARY SEWER I BI h� •l / C BI o TOE=566.0 <br />RELOCATE EX. POWER <br />SD EXISTING STORM DRAIN VAULT TO NEW, PLANTER <br />EXISTING WATER LINE II- / - W 576 \TP 2 - �- - <br />11 <br />U) <br />EXISTING VERTICAL CURB <br />z <br />TAX# 00869400000200 <br />EDGE OF PAVEMENT oo 71 <br />TP-1 <br />EXISTING CONTOURS <br />- <br />ROW CENTER LINE <br />PROPERTY LINE <br />- <br />- RIGHT OF WAY <br />- - <br />EXISTING LOT LINES <br />❑ <br />EX. CATCH BASIN (CB) <br />EX. CULVERT INLET <br />O <br />EX. SANITARY SEWER MANHOLE (SSMH) <br />N <br />EX. WATER VALVE <br />® <br />EX. WATER METER <br />EX. FIRE HYDRANT <br />-0- <br />EX. POWER POLE <br />&-- <br />EX. UTILITY POLE ANCHOR <br />OT <br />EX. TELEPHONE PEDESTAL <br />©E <br />EX. ELECTRIC JUNCTION BOX <br />7,11777117T�/� <br />rr <br />EXISTING BUILDING <br />a <br />EXISTING CONCRETE <br />m <br />EXISTING TREE <br />EXISTING TREE TO BE REMOVED <br />(rBR) <br />TO BE REMOVED <br />XXX <br />PROPOSED CONTOURS <br />T..E.S.C. LEGEND <br />Lj--- CATCH BASIN INSERT <br />MU MULCHED WHEN UNWORKED <br />CLEARING LIMITS <br />SF SILT FENCE <br />TEMPORARY CONSTRUCTION ENTRANCE <br />TP-# • SOIL TEST PIT (BY GEOTECH CONSULTANTS INC) <br />GRADING QUANTITIES <br />cur.• ado curds. <br />CALL TWO (2) fru: 1,000 curds. <br />BUSINESS DAYS (GRADING <br />OT AQUANTITIES <br />COUNT FORARE <br />S0I�SGWELLING & CALCULATIONS WHICH <br />RINKAGE) <br />BEFORE YOU DIG EXCESS CUT MAY BE SPREAD ON SITE. <br />8-1-1 ALL MATERIAL REMOVED FROM SITE SHALL BE HAULED TO A CITY <br />APPROVED SITE. <br />a TP-3 / P <br />• PROPOSED BUILDING T M 0 A Y <br />FOOTPRINT 5 OC PI 1 \ <br />l / PLASTIC <br />COVERING can c9 <br />F S S SF SF SF SF SF S <br />N89' 12- <br />0 "E <br />-------- -- <br />--------40. 0 <br />N 9.12'20 "E 190.00' g TAX# 00869400000100 <br />/ 56 <br />T / h�� h�� h�0 SILT FENCE PER STD DTL 214 <br />REMOVE EX. DWY CUT I <br />AND REPLACE WITH , l / CLEARING LIM TS <br />SIDEWALK PER C.O.E. / / / TAXI 00480200700800 8.5' WALL I <br />I STD DTL 317 I / , TOP=575.0 <br />TOE=566.5 <br />---- S.60' Lo L \ <br />I <br />EX SS <br />\ RIM=57 .OS' <br />IE IN(S)=566.08' N89'12'20"E <br />IE IN(W=566.22' <br />IE OUT( )=565.83' _ 200.00' 80' CAT. N <br />BUFFER <br />I� I <br />ss <br />^lo <br />9 Z <br />W.10' DEED FOR R.O.W. <br />CAT/IL. WETLAND <br />EX. CULVERT OUTLET (DELINEATION BY OTHERS) <br />/ CAT Ill. WETLAND <br />/ - - - - N89' 12'20 "E - (DELINEATION BY OTHERS) - - - - <br />- I 200.00' � o <br />o <br />Lo <br />los Z <br />VEGETATIVE COVER BEFORE CLEARING & GRADING: UTILITY CONFLICT NOTE.• W E S <br />ENTIRE SITE IS RESIDENTIAL LANDSCAPING. CAUTION.WAs� / (425) <br />1 <br />VEGETATIVE COVER AFTER CLEARING & GRADING' THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION, DIMENSION, AND 356-2700 <br />.� LA N D USE �� or <br />ALL DISTURBED AREAS SURROUNDING NEW SFR, S WILL BE DEPTH OF ALL EXISTING UTILITIES WHETHER SHOWN ON THESE PLANS OR NOT, BY h CONSULTANTS <br />RESIDENTIAL LANDSCAPING. POTHOLING THE UTILITIES AND SURVEYING THE HORIZONTAL AND VERTICAL LOCATION PRIOR " <br />TO CONSTRUCTION. THIS SHALL INCLUDE CALLING UTILITY LOCATE ® B-1-1 AND <br />THEN POTHOLING ALL OF THE EXISTING UTILITIES AT LOCATIONS OF NEW UTILITY CROSSINGS '�p�'�� 57009 ,��v PLANNING o ENGINEERING o SURVEYING <br />SOILS.- TO PHYSICALLY VERIFY WHETALERWOOD URBAN LAND COMPLEX AS SHOWN ON THESE PLANSH ER ARE BASOR ED UPON CONFLICTS THE UNVERIF� DA ES PUBLIC INFORMATION I AND �S, GIO IONS OF SAID UTILIT <br />S T ��y�s� <br />ARE SUBJECT TO VARIATION. IF CONFLICTS SHOULD OCCUR, THE CONTRACTOR SHALL NAL * 9740 EVERGREEN WAY *EVERETT * WA * 98204 <br />CONSULT WESI LAND USE CONSULTANTS, LLC TO RESOLVE ALL PROBLEMS PRIOR TO VISIT OUR WEBSITE AT. WWW. WESI.CO <br />PROCEEDING WITH CONSTRUCTION. 03-15-2022 <br />4 E °o 88TH ST 8.9f 88Tj9TH <br />T <br />�Q eei►+ Ft W = � c' S7 E Q L <br />eLusKousF Win, sr ST <br />90TH ST a N ST SW TRENT PL TH <br />SW - _ a 91 ST PL sF <br />S <br />9kn 91Si _� 800 PL SW Q o 92N ST <br />93RD ST <br />......_... <br />94TH _ .4 , - sw Ior <br />sr a 94TH <br />(ARCP�Bt AV) �� n N SE <br />SE <br />95THSE <br />95Tii ! [rrri �Lu� Iy2 f q g <br />ST ST sW I _ I pQ� FS IB ��� �' g�L r <br />96� Sr <br />97TH ST SE <br />a MID sr` f I��., J BTH Pt <br />� I dL T Ii5 q y 001JVA <br />c�ITH7 <br />100TH 5T� �. S � <br />2� 100THx 1 00 <br />ton <br />103R0 WL �r�r� `� rx <br />S <br />`0 RD <br />A 104TIl ST SW 2 � ' � � PL SE <br />✓,rH <br />1d _ w ST TE- 4TH <br />L,� Apo .......205T ¢ ST SW 105TH 5T SE 00 PL SE 104T <br />P � Q� � � 105TH <br />.� 106TH 106TH PL SW ST SW 106T'H ST SE ; { P <br />Boo goo W <br />� - ff 107TH PL SW . 107 1 ST SW 107TH ST SE PL 5L ', a <br />© ? I lOBTH ST carti[;[acs Rti. ,w io7 SF r �_ <br />VICINITY MAP <br />SCALE 1 " = 2000' <br />SCALE: 1 " = 20' <br />0 20 40 <br />BENCHMARK <br />ELEV-570.55' <br />VERTICAL DATUM: <br />NAVD88 <br />WCCS PT NO. 20743. MONUMENT IN CASE AT <br />INTERSECTION OF 4TH AVE. WEST AND 100TH ST. S.E. <br />T.B.M. <br />ELEV-S74. 64 r <br />VERTICAL DATUM: <br />NAVD88 <br />MAGNETIC NAIL SET WEST SIDE OF EAST BACK OF <br />WALK, 6' NORTH OF TELEPHONE PEDESTAL. <br />SOIL LOGS: <br />(PROVIDED BY GEOTECH CONSULTANTS INC) <br />TP-1 <br />0.0'-1.0' GRASSY TOPSOIL <br />1.0-4.5' BROWN SILTY SAND WITH GRAVEL TO <br />GRAY SLIGHTLY SILTY SAND WITH GRAVEL <br />TP-2 <br />0.0'-3.0' GRAY SILTY SAND WITH GRAVEL AND ROOTS (FILL) <br />3.0'-8.0' BROWN SILTY SAND WITH GRAVEL TO <br />GRAY SLIGHTLY SILTY SAND WITH GRAVEL <br />TP-3 <br />0.0'-1.0' GRASSY TOPSOIL <br />1.0'-5.0' BROWN SILTY SAND WITH GRAVEL TO <br />GRAY SLIGHTLY SILTY SAND WITH GRAVEL <br />SEDIMENT TRAP SIZING CALC. <br />2-YEAR PEAK RUNOFF RATE = <br />0.160 CFS. <br />FS (FACTOR OF SAFETY) = <br />2 <br />Vs (SETTLING VELOCITY) <br />= 0.00096 FT/SEC. <br />SURFACE AREA REQUIRED <br />= 333.33 SF. <br />DESIGNED SURFACE AREA <br />= 422 SF. <br />PLAN APPROVED <br />EVERETT <br />PUBLIC SERVICES DATE <br />PUBLIC WORKS <br />UTILITIES DRAINAGE DEPARTMENT <br />A PUBLIC WORKS PERMIT IS REQUIRED PRIOR TO <br />STARTING ANY CONSTRUCTION ON THIS <br />PROJECT. APPROVAL FOR THIS PROJECT <br />CITY ENGINEER IS CONDITIONAL PER CURRENT STANDARDS <br />AND EXPIRES UNLESS PERMIT <br />FOR CONSTRUCTION HAS BEEN ISSUED. <br />TAXACCOUNTNO. (S).• SITEADDRESS.- <br />00480200700700 9725 4TH AVE W <br />EVERETT, WA 98204 <br />GRADINGAND T.E'.S.C. PLANFOR.- <br />4THA VE TOWNHOMES <br />SW 1/4, SE 1/4, SEC.13, T.28N., R.4E., W.M. <br />CITY OF EVERETT, SNOHOMISH COUNTY, WA <br />DWN. BY DATE REV. BY DATE PROJECT MANAGER SCALE <br />JAJ 03106121 01 TAS 03115122 J. JARRELL 1 " = 20' <br />DWG. FILENAME CHK. BY F.B. NO. JOB NO. SHT. NO. <br />171620ABASE. DWG JAJ N/A 17-1620-A 2 OF 8 <br />