Laserfiche WebLink
st liPIPING MATERIAL SCHEDULE LASTDPD VIBRATION ISOLATION/SEISMIC SCHEDULE 2223 UPDATED: °�W� A <br /> Hermanson <br /> PIPE SERVICE I LOCATION I MATERIAL I JOINT METHOD(S) I REMARKS UNIT BASIS OF DER BASE SEISMIC <br /> COIL CONDENSATE -_-__ <br /> TAG SERVES DESIGN' INCH TYPE RESTRAINT REMARKS <br /> •_ _ABOVE GROUND py_S$Cf,4Q SOLVENT CEMENTED IF NOT IN A RA PLENUM.SOLIDCO1E(N41FOAM3 ___ ERV-X FLOOR MOUNTED ENERGY RECOVERY UNITS KNC RSP 0.125 - LAG BOLT/WEDGE ANCHOR 4,10 Building Today,Defining Tomorrow <br /> MFG INSTALL INSTRUCTIONS MUST BE FOLLOWED,MUST BE LISTED AND ODU-X VRF OUTDOOR UNITS - - - LAG BOLT/WEDGE ANCHOR 5,10 <br /> ABOVE GROUND CPVC(1/2'TO 2') CPVC CEMENT LABELED FOR USE IN RETURN AIR PLENUMS,AND PROVIDE FIELD APPLIED IOU- STRUCTURE HUNG FAN COIL UNITS KNC RH 0.3 - CABLE RESTRAINT _ 5,10,15 Hem m wm LL wm�ca„ <br /> LABEL ON PIPE NOTING'PLENUM RATED' NA DUCTWORK - - CABLE RESTRAINT 5,8,15 1221 Ind Avenue Hort, <br /> - SOLDER --- Kent.WAIESl°n SPAS] <br /> ABOVEGROUND COPPER(DW'7____ _I _ _. _ _.._ GENERAL ALL TRADES TO CONFIRM EQUIPMENT REQUIREMENTS(ELECTRICAL,WEIGHT,SIZE,ETC..)WITH APPROVED SUBMITTALS Txi:(205)575-97W <br /> ABOVE GROUND COPPER(L OR M1 1 PRESSFIT(51.12L1 <br /> /2 2,5DLDER -_ PRIOR TO INSTALLATION;FIELD COORDINATE FINAL LOCATION&INSTALL PER MANUFACTURERS REQUIREMENTS Fax <br /> (Na) <br /> )575-s& <br /> REFRIGERANT 1 OR EQUAL ISOLATION(ISSN,MASON,VIBRAC UETICS OR AS APPROVED),CONFIRM INSTALL METHOD WITH FIELD PRIOR TO ORDER <br /> ALL ���( ) BRAZED,PRESSER(MAXIPRO, p(OVIDE NITROGEN PURGE IF BRAZED 4 INTERNAL ISOLATION PROVIDED INTEGRAL WITH UNIT v«w namz.s n SE <br /> Contractor AW l:VERILV=.TC521 <br /> ZOOMLOIX OR EQUAL) 5 PROVIDE FLEXIBLE HOSES FOR PIPING CONNECTIONS ATLE UNIT <br /> -.--._- _ _ -_-._ _ 8 CONFIRM EQUIPMENT RPM,REFER TO'REQUIRED DEFLECTION BASED ON RPM'SPREADSHEET TO OETEREMI NE PROPER DEFLECTION <br /> BRAZED,PRESSER(MAXIPRO, 10 SEISMIC RESTRAINT AS REQUIRED BY CODE AND/OR LOCAL AUTHORITY HAVING JURISDICTION OR PER SMACNA GUIDELINES' <br /> ALL PRE-INSULATED COPPER LINE SETSPROVIDE NITROGEN PURGE IF BRAZED <br /> ZOOMLOCK OR EQUAL) 'SUSPENDED EQUIP WITH IP=1.0 AND>20LBS REQUIRES SEISMIC BRACING-IF THE COMPONENT/EQUIPMENT IS RIGIDLY ATTACHED TO THE DUCT AND THE DUCT IS BRACED,THEN <br /> 309 BRAIDED STAINLESS STEEL BRAZED,PRESSFIT(MA SIPRO, AD.COMPONENTS/EQUIP>75LES REQUIRE INDEPENDENT VERTICAL SUPPORTS AND SEISMIC BRACING.EQUIP WITH IP=1.5 AND<20L3S AND <br /> ALL <br /> WITH PTFE LINER _ ZOOMLOOS ORE UAL se0 PSI MIN WORKING PRESSURE REQUIRED FLEXIBLY CONNECTED MAY BE OMITTED Q C H C S N 0 H CO <br /> • <br /> 15 DEFLECTION AS REQUIRED PER ASHRAE APPLICATIONS,CHAPTER 48 BASED ON STRUCTURE ITEM WILL BE SUPPORTED FROM(VERIFY PRIOR TO ORDER) SOUTH EVERETT <br /> NOTE BOLD IL UNDERLINE REPRESENTS THE HERMANSON CORPORATE STANDARD MATERIAL AND JOINT METHOD FOR EACH SERVICE TYPE <br /> MINIMUM PIPE INSULATION LAST UPDATED: 08/18/22 ANNEX <br /> FLUID DESIGN INSULATION CONDUCTIVITY NOMINAL PIPE DIAMETER(INCH) <br /> OPERATING CONDUCTIVITY MEAN TEMP 1 TO 1-1/2 TO 4 TO 8531 EVERGREEN WAY <br /> TEMP°F RANGE RATING°F <I' <1-1/2' <4 <8 >-8 EVERETT,WA 98208 <br /> HEATING SYSTEMS'(STEAM,CONDENSATE,HYDRONIC HOT WATER) <br /> >350 0.32-0.34 250 4.5 5.0 5.0 5.0 I 5.0 <br /> 251-350 0.29-0.32 200 3.0 4.0 4.5 4.5 I 4.5 <br /> 201-250 0.27-0.30 150 2.5 2.5 2.5 3.0 3.0 <br /> 141-200 0.25-0.29 125 1.5 1.5 2.0 2.0 2.0 <br /> 105-140 0.21-0.28 100 1.0 1.0 I 1-5 1.5 1.5 <br /> DOMESTIC HOT WATER,DOMESTIC HOT WATER RECIRCULATION' <br /> NA I 0.21-0.28 I 100 I 0.5,0.75' I 1.0,1.25 5 I l.s,2.0' 1 2.0 I 2.0 otltTonOA,V <br /> DOMESTIC COLD WATER'AND HORIZ RAIN LEADERS TO VERTICAL RAIN LEADER(TO PREVENT CONDENSATION ONLY) <br /> NA I 0.21-0.27 I 75 I U.S I U.S I 0.5 J 0.5 I Os o e`wAs4,<�'�s/ <br /> COOLING SYSTEMS'(CHILLED WATER,BRINE AND WATERSIDE ECONOMIZER SYSTEMS') <br /> 40-60 0.21-0.27 75 U.S U.S 1.0 1.0 I 1.0 } <br /> <40 0.20-0.26 75 U.S 1.0 1.0 1.0 1.5 _ <br /> REFRIGERANT PIPING(SEATTLE ONLY) *yrkh;N�t:p-'cna <br /> IN COND SPACE 0.21-0.26 75 0.5 0.5 0.5 0.5 0.5 <br /> OUT COND SPACE 0.21-0.26 75 1.0 1.0 1.0 1.0 1.0 <br /> UNLINED <br /> STORAGE TANKS ALL SIZED R-12.5° - - - - - <br /> NOTES: <br /> GENERAL ALL PIPING EXPOSED TO WEATHER TO BE PROTECTED FROM SUNLIGHT,MOISTURE,WIND AND MAINTENANCE DAMAGE <br /> AND SHIELDED FROM SOLAR DEGREDATION,ADHESIVE TAPED ARE NOT ALLOWED <br /> 1 NOT REQUIRED FOR STRAINERS,CONTROL VALVES&BALANCING VALVES ASSOCIATED WITH PIPING 1.OR LESS IN DIE ISSUE FOR PERMIT <br /> 2 TYPICAL CONDENSER WATER PIPE IN NON-ECONOMIZER SYSTEMS IS NOT INSULATED <br /> 3 SEE R403 FOR RESIDENTIAL INSTALLATIONS <br /> 4 FOR PIPING SMALLER THAN 1-1/2 INCH AND LOCATED IN PARTITIONS WITHIN CONDITIONED SPACES,REDUCTION OP <br /> INSULATION THICKNESSES BY 1 INCH SHALL BE PERMITTED,BUT NOT TO A THICKNESS OF LESS THAN 1 INCH <br /> 5 DOMESTIC HOT WATER DIRE INSULATION SHALL HAVE A MINIMUM WALL THICKNESS OF NOT LESS THAN THE DIAMETER Key Plan <br /> OF THE PIPE FOR PIPE UP TO 2 INCHES IN DIAMETER.INSULATION WALL THICKNESS SHALL NOT BE LESS THAN 2 INCHES <br /> FOR A PIPE OF 2 INCHES OR MORE IN DIAMETER.NOTE THAT THIS IS PER UPC SECTION 609.11.2.IN JURISDICTIONS <br /> THAT REQUIRE DOMESTIC HOT WATER PIPING TO BE INSULATED PER THE ENERGY CODE,USE THE 105-140 ROW <br /> FROM HEATING SYSTEMS ABOVE. <br /> 6 SEATTLE ONLY:UNFIRED TANKS USED TO STORE WATER AT TEMPERATURES ABOVE 1301 SHALL INCLUDE A <br /> MINIMUM OF R-2 ADDITIONAL INSULATION FOR EVERY 10'F INCREASE IN STORED WATER TEMPERATURE OVER 130'F. <br /> 7 SEATTLE ONLY:FOR HEATED WATER CIRCULATION SYSTEMS,BOTH SUPPLY AND RETURN PIPE INSULATION SHALL BE <br /> AT MINIMUM 1 INCH THICKER THAN ROW IDS140 FROM HEATING SYSTEMS,ABOVE,EXCEPT WHERE PIPING IS <br /> CENTERED WITHIN A FRAMING CAVITY 4'DEEPER THAN THE PIPE THAT IS COMPLETELY FILLED WITH//ATT OR <br /> BLOW IN INSULATION. <br /> MINIMUM DUCT INSULATION LAST UPDATED 0S/03a1 <br /> INSULATION <br /> DUCT SYSTEM DUCT LOCATION AND USE R-VALUE REMARKS <br /> CLIMATE ZONE 4C <br /> SUPPLY AIR OR OUTSIDE THE SLIDING(OUTDOORS ANDEXPOSED TO WEATHER) R-8 1 <br /> RETURN AIR <br /> SUPPLY AIR OR UNCONDITIONED SPACE(ENCLOSED BUT NOT IN THE BUILDING CONDITIONED R-6 1 <br /> RETURN AIR ENVELOPE) <br /> SUPPLY AIR OR UNCONDITIONED SPACE(DUCT CONVEYS AIR THAT IS WITHIN 151 OF THE AIR <br /> RETURN AIR TEMPERATURE OF THE SURROUNDING UNCONDITIONED SPACE) R-3.3 2 Revisions <br /> SUPPLY AIR OR IN A BUILDING ENVELOPE ASSEMBLY R-16 3 <br /> RETURN AIR <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS LESS THAN NSF R-3.3 I <br /> SUPPLY AIR OR GREATER THAN 105°F) - -- <br /> SUPPLY AIR WITHIN CONDITIONED SPACE THAT THE DUCT DIRECTLY SERVES(SUPPLY DUCT NONE 1 <br /> WITHIN CONDITIONED SPACE(SUPPLY DUCT CONVEYS AIR THAT IS 55-F OR NONE <br /> SUPPLY AIR GREATER AND 105°F OR LESS) _ <br /> RETURN OR WITHIN CONDITIONED SPACE,DOWNSTREAM OF AN ENERGY RECOVERY MEDIA, R-0 - <br /> EXHADST AIR UPSTREAM OF AN AUTOMATIC SMUT OFF DAMPER <br /> RELIEF OR WITHIN CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC SHUT OFF R-16 - <br /> EXHAUST AIR DAMPER OUTSIDE AIR AIR INSIDE CONDITIONED SPACE AND UPSTREAM OF AN AUTOMATIC z2820 CFM R-16 4 <br /> SHUT OFF DAMPER <br /> OUTSDU AIR INSIDE CONDITIONED SPACE AND DOWNSTREAM OF AN AUTOMATIC z2800 CFM R-8 <br /> SHUT OFF DAMPER TO'VAC UNIT OR ROOM • <br /> OUTSIDE AIR INSIDE CONDITIONED SPACE <2800 CFM R-7 5 <br /> NOTED: - - <br /> 1 SEE ENERGY CODE SECTION C103.10.1.2 FOR DETAILS 05/09/23 BOG PERMY RESPONSE <br /> 2 SEE IMC SECTION 603.12 FOR ADDITIONAL REQUIREMENTS FOR CONDENSATION CONTROL AT DUCTWORK <br /> 3 DUCT OR PLENUM IS SEPARATED FROM BUILDING ENVELOPE ASSEMBLY WITH THE MINIMUM INSULATION VALUE 04/11/23 BDG ISSUE FOR PERMIT <br /> 4 WE ENERGY CODE SECTION 0103.10.1.1 FOR ADDITIONAL REQUIREMENTS Mn Dote By Description <br /> 5 SEE EXCEPTION 1 TO SECTION C103.10.1.1 FOR ADDITIONAL DETAILS <br /> Design Team <br /> Design BOG <br /> OrO.n EPR <br /> Checked DTN <br /> Pre Construction Number 21-22-22n0 <br /> Construction Number XX-XK-XXXXX <br /> Use Date 02/XX/23 <br /> CITY OF EVERETT CONSTRUCTION <br /> REVIEWED FOR PERMIT STANDARDS <br /> -HVAC <br /> FOR CITY USE <br /> M0.02 <br />