Laserfiche WebLink
DN-6724:B3 <br /> FCM.1 (A) & FRMA (A) NOT 1 F 1 E R° <br /> Series 0 <br /> Control and Relay Modules by Honeywell <br /> Intelligent Addressable Devices <br /> General <br /> FCM-1(A)Control Module: The FCM-1(A)Addressable Con- <br /> trol Module provides Notifier intelligent fire alarm control pan- <br /> els a circuit for Notification Appliances (horns, strobes, <br /> speakers, etc.). Addressability allows the FCM-1(A)to be acti- <br /> vated, either manually or through panel programming, on a 0 <br /> select(zone or area of coverage) basis. <br /> FRM-1(A)Relay Module: The FIRMA(A) Addressable Relay T11 Eat PWR,-) O EaaaMiM <br /> Module provides the system with a dry-contact output for acti- T1UE.tPWR i1 <br /> vating a variety of auxiliary devices, such as fans, dampers, <br /> control equipment,etc.Addressability allows the dry contact to """' ..� <br /> be activated, either manually or through panel programming, TO",., <br /> on a select basis. <br /> .:, <br /> FlashScan® (U.S. Patent 5,539,389) is a communication pro TO <br /> A. Ill Ill <br /> tocol developed by NOTIFIER Engineering that greatly <br /> enhances the speed of communication between analog intelli <br /> 0 <br /> gent devices. Intelligent devices communicate in a grouped <br /> fashion. If one of the devices within the group has new infor <br /> mation, the panel CPU stops the group poll and concentrates <br /> on single points.The net effect is response speed greater than <br /> five times that of other designs. <br /> FCM-1(A) <br /> Features <br /> • Built-in type identification automatically identifies these • The FCM-1(A)is configured for a single Class B(Style Y)or <br /> devices to the control panel. Class A(Style Z) Notification Appliance Circuit. <br /> • Internal circuitry and relay powered directly by two-wire • The FRM-1(A) provides two Form-C dry contacts that <br /> SLC loop.The FCM-1(A)module requires power(for horns, switch together. <br /> strobes,etc.),or audio(for speakers). <br /> • Integral LED "blinks" green each time a communication is Operation <br /> received from the control panel and turns on in steady red Each FCM-1(A)or FRM-1(A) uses one of 159 possible module <br /> when activated. addresses on a SLC loop (99 on CLIP loops). It responds to <br /> • LED blink may be deselected globally(affects all devices). regular polls from the control panel and reports its type and <br /> • High noise immunity(EMF/RFI). status, including the open/normal/short status of its Notifica- <br /> • The FCM-1(A) may be used to switch 24-volt NAC power, tion Appliance Circuit (NAC). The LED blinks with each poll <br /> audio(up to 70.7 Vrms). received. On command, it activates its internal relay. The <br /> FCM-1(A) supervises Class B (Style Y) or Class A (Style Z) <br /> • Wide viewing angle of LED. notification or control circuits. <br /> • SEMS screws with clamping plates for wiring ease. Upon code command from the panel, the FCM-1(A) will dis- <br /> • Direct-dial entry of address 01— 159 for FlashScan loops, connect the supervision and connect the external power sup- <br /> 01 —99 for CLIP mode loops. ply in the proper polarity across the load device. The <br /> • Speaker, and audible/visual applications may be wired for disconnection of the supervision provides a positive indication <br /> Class B or A(Style Y or Z). to the panel that the control relay actually turned ON. The <br /> external power supply is always relay isolated from the com- <br /> Applications munication loop so that a trouble condition on the external <br /> power supply will never interfere with the rest of the system. <br /> The FCM-1(A) is used to switch 24 VDC audible/visual power, Rotary switches set a unique address for each module. The <br /> high-level audio (speakers). The FRM-1(A) may be pro- address may be set before or after mounting. The built-in <br /> grammed to operate dry contacts for applications such as door TYPE CODE (not settable)will identify the module to the con- <br /> holders or Air Handling Unit shutdown, and to reset four-wire trol panel, so as to differentiate between a module and a sen- <br /> smoke detector power. sor address. <br /> NOTE: Refer to the SLC Manual (PN 51253) for details regarding <br /> releasing applications with the FCM-1(A). Refer to the FCM-I-REL Specifications for FCM-1(A) <br /> datasheet(DN-60390)for new Flash5canO releasing applications. <br /> Normal operating voltage: 15 to 32 VDC. <br /> Construction Maximum current draw: 6.5 mA(LED on). <br /> • The face plate is made of off-white heat-resistant plastic. Average operating current: 350 pA direct poll,375 pA group <br /> • Controls include two rotary switches for direct-dial entry of poll with LED flashing, 485 pA Max. (LED flashing, NAC <br /> address(01-159). shorted.) <br /> DN-6724:B3.2/17/2011—Page 1 of 2 <br />