EXISTING DOAS HEAT RECOVERY VENTILATOR DEMOLITION SCHEDULE EXISTING HRV SPACE ASSIGNMENT
<br /> OUTDOOR EXHAUST ESP WATT/ MIN. MARK 15T FLOOR 2ND FLOOR 3RD FLOOR 4TH FLOOR
<br /> MARK MAKE MODEL LOCATION DESCRIPTION CFM CFM 1W.C• MTR HP CFM EFF. V/PH/A FLA MCA MOP WT. NOTES
<br /> HRV-1 RENEWAIRE HE1.5XINV 15T FLOOR P05 HEAT RECOVERY 690 790 0.40 (2)1.0 0.459 73% 205/1 6.2 14.0 15 400 1,2,3 HRV-1 OFFICES&HALLWAY 123
<br /> OFFICE AREA VENTILATOR HRV-2 APARTMENT5113,115,116,
<br /> HRV-2 RENEWAIRE EV4501N 15T FLOOR D05 HEAT RECOVERY 450 450 0.40 (1)0.5 0.89 72% 206/1 4.& 6.0 15 180 2,4 117,11b,119,120 CORRIDOR
<br /> APARTMENTS VENTILATOR 133&MAINT.114
<br /> HRV-3 RENEWAIRE HE1.5XINV NORTH 2ND, DOS HEAT RECOVERY 760 760 0.60 (2)1.0 0.664 71% 206/1 6.2 14.0 15 400 1,2,4 HRV-3 201,202,203,204,205,CORK. 301,302,303,304,305,COKR, 401,402,403,405, CORP.
<br /> 3RD,4TH FLR5 VENTILATOR 2235 3235 4235
<br /> HRY-4 RENEWAIKE HE1.5XINV NORTH 2ND, P05 HEAT RECOVERY 540 600 0.60 (2)1.0 0.664 71% 205/1 6.2 14.0 15 400 1,2,4 HRV-4 206,207,208,209,222 JAN. 300,307,308,309,322 JAN. 404,406,408,409,422 JAN,
<br /> 3RD,4TH FLR5 VENTILATOR
<br /> HRV-5 RENEWAIRE HE1.5XINV SOUTH 2ND, D05 HEAT RECOVERY 760 760 0.60 (2)1.0 0.604 71% 208/1 6.2 14.0 15 400 1,2,4 HRV-5 210,211,212,213,214,215 310,311,312,313,314,315 410,411,412,413,414
<br /> 3RD,4TH FLRS VENTILATOR
<br /> HRV- RENEWAIRE HE1.5XINV SOUTH 2ND, DOS HEAT RECOVERY 825 825 0.60 (2)1.0 0.664 71% 208/1 6.2 14.0 15 400 1,2,4 HRV-6 223 217,218,219,220,GORR. 323 317,318,319,320,CORK. 423 417,418,419,420,CORP.
<br /> 6
<br /> 3RD,4TH FLR5 VENTILATOR ( ) 2 N 3 N 4 N
<br /> NOTES:
<br /> 1wT/CFM 15 FOR THE ENTIRE UNIT(2-FANS).
<br /> 2.PROVIDE WITH EC MOTORS.
<br /> 3.PROVIDE MOTORIZED OUTSIDE AIR AND EXHAUST AIR DAMPERS,DAMPERS CL05ED WHEN HRV UNIT 15 OFF.HRV-1 SHALL HAVE OPERATING SCHEDULE FOR OCCUPIED/UNOCCUPIED MODES.
<br /> 4.HRV-2,HRV-3,HRV-4,HRV-5&HRV-6 OPERATE CONTINUOUSLY 24/7 AND HAVE NO 15ACKDRAFT MOTORIZED DAMPERS.OPERATE ALL HRV UNIT FANS SERVING APARTMENTS AT 60%OF DESIGN
<br /> AIR FLOW DURING NIGHT-SET SACK SCHEDULE.
<br /> NEW INTAKE AND EXHAUST FAN SCHEDULE (N) NOTES
<br /> MARK MAKE MODEL LOCATION SERVES DESCRIPTION CFM .SP MTR HP FAN BHP FEG V/PHIA FLA MCA MOP WT. NOTES 1. EX15TING DDC CONTROL 5Y5TEM5 BY
<br /> "W.C. RPM WATTS ALERTON AND AT5.COORDINATE TO RE-U5E
<br /> IF-1 COOK 1355QN17PEC 15T FLOOR OFFICE,HALLWAY 123,APARTMENT5:113,115,116,117,115,119,120,CORRIDOR 133 CENTRIFUGAL 5QUARE INLINE 1140 0.6 3/4 1071 159 N/A 2051 5.5 0.9 15 96 AND RE-CONFIGURE EXISTING CONTROL
<br /> MECH.ROOM AND MAINTENANCE ROOM 114 EC MOTOR DIRECT DRIVE INTAKE (<1HP) POINTS.PROVIDE UPDATED GEOGRAPHIC5.
<br /> FAN REMOTE SITE ACCE55 DOES NOT CURRENTLY
<br /> EXISTS.
<br /> IF-2 COOK 1555QN17PEC 4TH FLOOR APARTMENTS:201,202,203,204,205,206,207,206,209,222 JANITOR KM, CENTRIFUGAL 5QUARE INLINE 1300 0.65 3/4 1264 255 N/A 2061 5.5 6.9 15 96
<br /> MECH.ROOM CORRIDOR 2235, APARTMENTS 301,302,303,304,305,CORRIDOR 3235 AND EC MOTOR DIRECT DRIVE INTAKE (<1HP)
<br /> APARTMENTS:401,402,403,404,405,CORRIDOR 4235, FAN
<br /> IF-3 COOK 1355QN17PEC 4TH FLOOR APARTMENT5:210,211,212,213,214,215,216,217,218,219,220,CORRIDOR 223N, CENTRIFUGAL SQUARE INLINE 1585 0.75 3/4 1408 343 N/A 206A 5.5 6.9 15 96
<br /> MECH.ROOM APARTMENTS:310,311,312,313,314,315,316,317,318,319,320,CORRIDOR 323N, EC MOTOR DIRECT DRIVE INTAKE
<br /> APARTMENTS:410,411,412,413,414,415,416,417,418,419,420,CORRIDOR 423N FAN
<br /> EF-1 COOK 1355QN17PEC 15T FLOOR OFFICE,HALLWAY 123,APARTMENT5:113,115,116,117,115,119,120,CORRIDOR 133 CENTRIFUGAL SQUARE INLINE 1240 0.6 3/4 1122 150 N/A 20&/1 5.5 6.9 15 96
<br /> LAUNDRY ROOM AND MAINTENANCE ROOM 114 EC MOTOR DIRECT DRIVE (<1HP)
<br /> EXHAUST FAN s Inc
<br /> .c.ring Servi
<br /> EF-2 COOK 1355QN17PEC 4TH FLOOR APARTMENT5:201,202,203,204,205,206,207,208,209,222 JANITOR KM, CENTRIFUGAL SQUARE INLINE 1560 1.15 3/4 1293 272 N/A 208/1 5.5 6.9 15 96 l E vole ngineeRonan eam� i wn ec.1
<br /> MECH.ROOM CORRIDOR 2235, APARTMENTS 301,302,303,304,305,CORRIDOR 3235 AND EC MOTOR DIRECT DRIVE (<1HP)
<br /> APARTMENT5:401,402,403,404,405,CORRIDOR 4235. EXHAUST FAN
<br /> EF-3 COOK 13550.N17DEC 4TH FLOOR APARTMENTS:210,211,212,213,214,215,216,217,218,219,220,CORRIDOR 223N, CENTRIFUGAL 5QUARE INLINE 1555 1.15 3/4 1405 343 N/A 205/1 5.5 6.9 15 96
<br /> MECH.ROOM APARTMENT5:310,311,312,313,314,315,316,317,318,319,320,CORRIDOR 323N, EC MOTOR DIRECT DRIVE (<1HP)
<br /> APARTMENT5:410,411,412,413,414,415,416,417,418,419,420,CORRIDOR 423N EXHAUST FAN Clares Place-
<br /> NOTES: Ventilation ReVISl011
<br /> 1.
<br /> 6200 12th Dr.SE
<br /> Everett,Washington 98203
<br /> NEW LOUVER SCHEDULE ,DEAN
<br /> FREE AREA VEL. S.P. SIZE NEW DUCT HEATER SCHEDULE SCHEDULE
<br /> MARK MAKE MODEL DESCRIPTION (eQ•ft•1 CFM (ft./min.) In.w.c..) (IN"xH'AD'� NOTES MARK MAKE MODEL LOCATION DESCRIPTION CFM DUCT SIZE DELTA WxH T kW V/PH FLA MCA MOP WT. NOTES
<br /> `
<br /> L-1 RUSKIN ELF6611DO OUTSIDE AIR LOUVER 1.34 1140 852 0.09 1800X6 1,2 DH-1 INDEECO 227F30 15T FLOOR MECH. INTAKE DUCT SLIP-IN HEATER W/ 1140 IOX14 25 9 208/3 25 31.25 35 130 1 "eo J1p°es
<br /> L-2 RUSKIN ELF6425DD OUTSIDE AIR LOUVER 2.23 1300 585 0.04 18X42X6 1,2 ROOM 3-5TAGE HEAT PosE`
<br /> L-3 RUSKIN ELF642500 OUTSIDE AIR LOUVER 2.23 15&5 852 0.06 18X42X6 1.2 DH-2 INDEECO 227F30 4TH FLOOR MECH. INTAKE DUCT SLIP-IN HEATER W/ 1300 16X16 25 11 205/3 30.5 38.125 40 260 1
<br /> L-4 RUSKIN ELF6425DD EXHAUST AIR 1.48 1240 838 0.08 1800X6 1
<br /> ROOM 3-5TAGE HEAT 01-19-2024
<br /> NOTES: DH-3 INDEECO 227F30 4TH FLOOR MECH. INTAKE DUCT 5LIP-IN HEATER W/ 1585 16X16 25 13 208/3 36 45 50 260 1
<br /> 1.PR VIDE WITH BIRD SCREEN. ROOM 3-5TAGE HEAT
<br /> 2.RE-U5E EXISTING LOUVER IF FEASIBLE. NOTES: MECHANICAL
<br /> 1. PROVIDE WITH DUCT T-STAT AND ALL CONTROLS.
<br /> SCHEDULES
<br /> Date
<br /> 19 January 2024
<br /> Rev
<br /> Drawn by:
<br /> IK
<br /> Checked by(P.M.):
<br /> Checked by(O.C.):
<br /> JH
<br /> Project No.
<br /> M5. 1 ;;