|
EXISTING MECHANICAL EQUIPMENT ELECTRICAL CONNECTION (MEEC)SCHEDULE MECHANICAL EQUIPMENT ELECTRICAL CONNECTION (MEEC) SCHEDULE
<br /> q20NF1'D'/VFD+NFD
<br /> TARTFRI BHP HP STARTER/
<br /> MARK DESCRIPTION VOLTS/PH HPIKW MCA CONNECT CONDUCTOR PANEL-CIRCUIT NOTES MARK DESCRIPTION VOLTS/PH HP KW WATTS WATTS MCA MOP DISCONNECT CONDUCTOR PANEL-CIRCUIT NOTES
<br /> PH-1 RANGE HOOD 120/1 .1 WA 2#12,#12 GND APT 4.6 PH-1 RANGE HOOD 120/1 .1 N/A 2#12,#12 GND APT 4,6
<br /> RH-2 RANGE HOOD 120/1 .2 WA 2#12.#12 GNP.1/2"C. Fl-32 RH-2 RANGE HOOD 120/1 .2 N/A 2#12,#12 GNP,1/2"C. Pl-32
<br /> HP-1 VRF HEAT PUMP 208/3 43.5 FD 4#8.#10 GND,3/4"C. H4A-246 8 HP-1 VRF HEAT PUMP 208/3 43.8 46 FD 4#8,410 GND,3/4"C. H4A-2,4,6 8
<br /> F/5 FIRE SMOKE DAMPER 12011 .2 EA M5 2#12.#12 GND.1/2"C. Hl-12 4 F/5 FIRE SMOKE DAMPER 120/1 .2(EA) M5 2#12,412 GNP,1/2"C. Hl-12 4
<br /> 5F-1 SUPPLY FAN 208/3 1.5 HP 7.5 3#12.#12 GND.1/2"C. H46-20,22.24 8,9 5F-1 5UPPLY FAN 208/3 1.5 HP 75 20 NFD/VFD+NFD 3#12,412 GNP,1/2"C. H45-2022,24 8,9
<br /> FC-1 HEAT PUMP INDOOR HEAD 208/1 0.4 MS 2#12,#12 GND.1/2"C. H1-36,36 5 FC-1 HEAT PUMP INDOOR HEAD 208/1 Oh M5 2#12,#12 GNP,1/2"C. 1-11-36,38 5
<br /> FC-2 HEAT PUMP INDOOR HEAD 205/1 1 0.4 1 2#12,#12 GNP,1/2"C. H1-36,38 5 FC-2 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,412 GND,1/2"C. 1-11-36,38 5
<br /> FC-3 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,#12 GND.1/2"C. Hl-36,38 5 FC-3 HEAT PUMP INDOOR HEAD 205/1 OA 2 412,412 GNP,1/2"C. 111-36,38 5
<br /> FC-4 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12.#12 GND.1/2"C. H1-36,38 5 FC-4 HEAT PUMP INDOOR HEAD 205/1 0.4 1 2#12,92 GND,1/2"C. 1-11-36,38 5
<br /> FC-5 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,#12 GND,1/2"C. H1-36.38 5 FC-5 HEAT PUMP NDOOR HEAD 208/1 OA 2#12,#12 GND,1/2"C. Hi-36,39 5
<br /> FG6 HEAT PUMP INDOOR HEAD 201 0.4 2#12,#12 GNP.1/2"C. H-36,38 5 FC-6 HEAT PUMP INDOOR HEAD 206/1 0.4 2#12,#12 GNP,1/2"C. H1-36,38 5
<br /> FC-% HEAT PUMP INDOOR HEAD 2085/11 0.4 2#12.#12 GNP,1/2"C. Hl-36,38 5 FC-7 HEAT PUMP INDOOR HEAD 205/1 OA 2#12,#12 GNP,1/2"C. H1-36,38 5
<br /> FC-8 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,#12 GND,1/2"C. Hl-36.38 5 FC-8 JHEATPUMP INDOOR HEAD 208/1 0.4 2#12,#12 GNP,1/2"C. 1-11-36,38 5
<br /> FC-9 HEAT PUMP INDOOR HEAD 208/1 1 0.4 2#12,#12 GNP.1/2"C. 1-11-36,38 5 FC-9 HEATPUMP INDOOR HEAD 208/1 04 2 412,#12 GNP,1/2"C. Hl-36,38 5
<br /> FC-10 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12.#12 GNP.1/2"C. Hl-36,38 5 FC-10 HEATPUMP INDOOR HEAD 208/1 OA 2 412,#12 GNP,1/2"C. 1-17-36,38 5
<br /> FC-11 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,#12 GND,112"C. HI-36,38 5 FC-11 HEAT PUMP INDOOR HEAD 205/1 OA 2#12,#12 GNP,1/2"C. Hi-36,38 5
<br /> FC-12 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12.#12 GND,1/2"C. H1-36.38 5 FC-12 HEATPUMP INDOOR HEAD 208/1 0.4 2#12,#12 GN D,1/2"C. HI-36,38 5 NEW WORK
<br /> FC-13 HEAT PUMP INDOOR HEAD 20511 0.4 2#12,#12 GND,1/2"C. H1-36a'8 5 FC-13 HEAT PUMP INDOOR HEAD 208/1 OA 2#12,#12 GN D,1/2'.C. HI-36,38 5
<br /> FC-14 HEAT PUMP INDOOR HEAD 208/1 0.4 2#12,#12 GNP.1/2"C. H1-36,38 5 FC-14 HEAT PUMP INDOOR HEAD 208/1 OA 2#12,#12 GND,1/2"C. HI-36,38 5
<br /> FC-15 HEAT PUMP INDOOR HEAD 20&A 0.5 2#12,#12 GND,1/2"C. H1-36,88 FL_iey Ij94L9 n UNWQeuenn &I� &*+Leno QML1/'J.f_ —
<br /> — -z
<br /> IF-1 INTAKE FAN 208/1 3/4 HP 159 630 15 2#12,#12 GND,1/2"C. 1-17-39,41 I
<br /> t EF-1 EXHAUST FAN 208/1 3/4 HP 180 630 15 2#12,#12 GND,1/2"C. H1-63,65
<br /> PH-1 DUCT HEATER 208/3 SKIN 35 NOTE% 3#8,#10 GND,3/4"C. 1-17-67,69,71 7
<br /> IF-2 INTAKE FAN 205/1 3/4 HP 255 630 15 2#12,#12 GND,1/2"C. H4A-8,10
<br /> I EF-2 EXHAUST FAN 208/1 3/4 HP 272 630 15 2#12,#12 GND,1/2"C. H4A-12,14
<br /> 5-1 DOMESTIC WATER BOILER 205/3 18 KW 50 NFD 3#8,#10 GND,3/4"C. Hi-44,46.48 OH-2 DUCT HEATER 205/3 11 KW 40 NOTE 7 3#8,#10 GN D,3/4"C. H4A-50,52,54 %
<br /> HP-2 DOMESTIC WATER HEAT PUMP 205/3 28 50 FD 3#8,#10 GND,3W'C. H45-2628.30 6 IF-3 INTAKE FAN 206/1 3/4 HP 343 630 15 2#12,#12 GND,1/2"C. H46-10,12 I
<br /> CP-1 CIRC PUMP 208/1 b25 KW 20 M5 2#12.#12 GND.1/2"C. Hi-43.45
<br /> EF-3 EXHAUST FAN 208/1 3/4 HP 343 63O 15 2#12,#12 GND,1/2"C. H4B-14,16
<br /> GP-2 CIRC PUMP 208/1 825 KW 20 M5 2#12,#12 GND,1/2"C. H1-47,49 PH-3 DUCT HEATER 208/3 13 KW 45 NOTE% 3#8,#10 GND,3/4"C. H46-61,63,66
<br /> CP-3 CIRC PUMP 120/1 1 A85 KW 20 M5 1 2#12,#12 GND,1/2"C. H1-42
<br /> Bi - ^k,A.TE1i65Q "' /3 - -5 CGrw"NG,3kF" "1-96446a
<br /> NOTES: HP-2 DOMESTIC WATER HEATPUMP 208/3 28 50 FO 3#8,#10 GND,3/4"C. H46-2628,30 8
<br /> 1. SEE ENLARGED PLANS FOR CONNECTIONS AND CIRCUITS.MULTIPLE QUANTITY THROUGHOUT PLANS. CP-1 CIRC PUMP 205/1 .825 KW 20 M5 2#12,#12 GND,1/2"C. H1-43,45
<br /> 2.STARTER/DISCONNECT ABBREVIATIONS:NFL)=NON FUSED 015CONNECT(K5-1 TYPE);Me=MOTOR RATED SWITCH W/PAD-LOCL DOG-EAR COVER CP-2 CIRC PUMP 205/1 .825 KW 20 M5 2#12.#12 GND,1/2"C. H1-47,49
<br /> M=MANUAL MOTOR STARTER W/THERMAL PROTECTION AND PAD-LOCK DOG-EAR COVER;RIB=RELAY IN BOX W/PILOT LIGHT.FO=FUSED 015CONNECT(TYPE KS-1);VFD CP-3 I CIRC PUMP 120/1 .0&5 KW 20 M5 2#12,412 GNP,1/2"C. HI-42
<br /> =VARIABLE FREQUENCT DRIVE NOTES:
<br /> 3 SEE SEPARATE SCHEDULE FOR WALL HEATERS 1. SEE ENLARGED PLANS FOR CONNECTIONS AND CIRCUITS.MULTIPLE QUANTITY THROUGHOUT PLANS.
<br /> 2.STARTER/DISCONNECT ABBREVIATIONS NFD=NON FUSED D15CONNECT(K5-1 TYPE);M5=MOTOR RATED SWITCH W/PAD-LOCL DOG-EAR COVER Engineering Services Inc.
<br /> 4 MULTIPLE LOCATION SEE PLAN DRAWINGS. 9eso uo,."coca ee aamn.my.i.,wn Seim
<br /> M=MANUAL MOTOR STARTER W/THERMAL PROTECTION AND PAD-LOCK DOG-EAR COVER,RIB=RELAY IN BOX W/PILOT LIGHT.FD=FUSED DISCONNECT(TYPE K5-1);VFD=VARIABLE Phone:P08.842894J w<m�t.:.....euntEn9.cam
<br /> 5 PROVIDE D 15CONNECT AT BRANCH MANIFOLD FOR ALL HEATPUMP HEADS SERVED BY MANIFOLD. FREQUENCT DRIVE
<br /> 6 SEE APARTMENT PANELSCHEDULE5.
<br /> 3 SEE SEPARATE SCHEDULE FOR WALL HEATERS
<br /> 8 NEMA 3R FOR OUTDOOR MOUNTED DISCONNECT 4 MULTIPLE LOCATION SEE PLAN DRAWINGS.
<br /> 9 SEMA 3F FOR
<br /> M SEE ROOF PLAN. 5 PROVIDE DISCONNECT AT BRANCH MANIFOLD FOR ALL HEATPUMP HEADS SERVED BY MANIFOLD, Glares Place
<br /> 10 LOCATE VFD SERVING SF-1PRE55URIZATI0N FAN IN MECHANICAL ROOM 415.PROVIDED 15Y ELECTRICAL.COORDINATE WITH MECHANICAL.VFP SHALL 13E 13Y A55,PAN I fO`_= = =A1ENiP""='�"�6Gu1.E5. Ventilation Revision
<br /> F055 OF SQUARE D.THEY SHALL HAVE ALL REQUIRED LINE FILTERS AND CONTROL INTERFACE FOR DDC SYSTEM(COORDINATE WITH BUILDING CONTROLS FOR ALL %PROVIDE UNIT 0I5CONNECT. J
<br /> 6 NEMA 3R FOR OUTDOOR MOUNTED DISCONNECT,
<br /> 9 SECONDARY DISCONNECT,SEE ROOF PLAN. 620012th Dr.SE
<br /> 10 LOCATE VFD SERVING 5F-1 PKE55UFJZATION FAN I N MECHANICAL ROOM 415.PROVIDED BY ELECTRICAL,COORDINATE WITH MECHANICAL.VFD SHALL BE BY ADS,DAN F055 OR SQUARE D. Everett,Washington 98203
<br /> NEW WORK THEY SHALL HAVE ALL REQUIRED LINE FILTERS AND CONTROL INTERFACE FOR DDC SYSTEM COORDINATE WITH BUILDING CONTROLS FOR ALL REQUIREMENTS.A MANUAL 15YPA55 15 NOT
<br /> ,DEAN e'
<br /> oy sca
<br /> 'O ry III
<br /> 9, a�„a e180.5 q
<br /> YAK` t *L6
<br /> TONAL
<br /> 01-19-2024
<br /> Electrical
<br /> Schedules
<br /> Data
<br /> 19 January 2024
<br /> Revisions
<br /> Drawn by:
<br /> IK
<br /> p Checked by(P.M.):
<br /> E
<br /> Checked by(Q.C.):
<br /> JH
<br /> n
<br /> Project No.
<br /> g
<br /> R
<br /> E5. 1 ;;
<br />
|