Laserfiche WebLink
tvNEUDORFER <br /> ENGINEERS <br /> Exhaust Fan Test Data <br /> Project No. 2024-0772 Project I.D. Clare's Place Ventilation Revisions <br /> Test Date 6/18/2024 Tested By Greg Neudorfer <br /> Area Served 1st Floor EXH Equipment I.D. EF-1 <br /> Unit Information <br /> Manufacturer Twin City Fans Model Number DSI-120AE <br /> Serial Number 58154-4-00001 Unit Location 1 st Floor Laundry <br /> Fan Quantity/Rotation 1 / Counterclockwise Drive Type Direct Drive <br /> Fan Test Data <br /> Total Design Airflow 1,240 CFM Total Actual Airflow 1,288 CFM <br /> Design TSP 0.60 in.wc Actual TSP 0.60 in.wc <br /> Actual Volts 210.0 Actual Amps 1.9 <br /> Design Fan RPM 1065 Actual Fan RPM 1063(1) <br /> Unit Pressure Data <br /> Exhaust Fan In/Out -0.340 in.wc / 0.260 in.wc I Exhaust Fan A P 0.600 in.wc <br /> Motor Information <br /> HP/RPM 3/4 / 1750 Motor Phase/Hz 3 / 60 <br /> Motor Rated Volts/FLA 208-230 / 4.5 Motor Eff./PF N/L / N/L <br /> General Notes <br /> Note (1) 1 The fanspeed is controlled by entering the target motor RPM into the attachable GridPoint Controller. <br /> Page 11 of 31 <br />