Laserfiche WebLink
Final Calculations - Hazen-Williams <br /> A-PEX Design Services Inc. Page 8 <br /> BENTON SQUARE BLDG E -Two Head Calculation (H.3 & H.1) Date 1/18/2024 <br /> Node1 Elev1 K Qa Nom Fitting Pipe CFact Pt <br /> to or Ftng's Pe ******* Notes ****** <br /> Node2 Elev2 Fact Qt Act Eqv. Ln. Total Pf/Ft Pf <br /> T.33 108 -2.06 1 Utr 2.0 4.382 150 19.576 <br /> to 0.0 2.000 0.0 <br /> T.32 108 3.89 0.862 0.0 6.382 0.0108 0.069 Vel = 2.14 <br /> 0.0 <br /> T.32 3.89 19.645 K Factor= 0.88 <br /> T.36 116 2.96 1 Utr 2.0 2.000 150 15.062 <br /> to 0.0 2.000 0.0 <br /> T.37 116 2.96 0.862 0.0 4.000 0.0065 0.026 Vel = 1.63 <br /> 0.0 <br /> T.37 2.96 15.088 K Factor= 0.76 <br /> T.33 108 2.06 1 0.0 1.000 150 19.576 <br /> to 0.0 0.0 0.0 <br /> T.34 108 2.06 0.862 0.0 1.000 0.0030 0.003 Vel = 1.13 <br /> 0.0 <br /> T.34 2.06 19.579 K Factor= 0.47 <br /> Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 <br />