SOLAR MODULE SPECIFICATIONS AC CONDUCTOR AMPACITY CALCULATIONS: <br /> HYUNDAI SOLAR HIS-S365XG(BK) FROM JUNCTION BOX TO COMBINERBOX4: ' <br /> MANUFACTURER/MODEL# (365W)MODULES <br /> AMBIENT TEMPERATURE ADJUSTMENT FOR EXPOSED CONDUIT <br /> VMP 34.3 PER NEC 310.15(B)(2): 7/8 (ABOVE ROOF) <br /> EXPECTED WIRE TEMP (°C): 26° WIRESERVICES LLC NUTZ ELECTRICAL <br /> IMP 10.64 TEMP CORRECTION PER TABLE 310.15(B)(1): 1.0 <br /> VOC 41.3 #OF CURRENT CARRYING CONDUCTORS: 4 13023 NE HWY 99 STE.7 PMB#264 <br /> ISC 11.28 CONDUIT FILL CORRECTION PER NEC 310.15(C)(1): 0.80 VANC WA98686 <br /> Phone:3 60-60-609-2714 <br /> MODULE DIMENSION 69.06"L x 40.86"W x 1.57"D(In Inch) CIRCUIT CONDUCTOR SIZE: 10 AWG Email:solar@wirenutzelectric.com <br /> CIRCUIT CONDUCTOR AMPACITY: 40A WA LIC#WIRENNE892J6 <br /> OR CCB#189913 <br /> INVERTER SPECIFICATIONS REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(A&B): <br /> MANUFACTURER/MODEL# ENPHASE ENERGY IQ8PLUS-72-2-US 1.25 X# MICRO-INVERTERS (MAX. BRANCH LENGTH)X MAX OUTPUT CURRENT <br /> NOMINAL OUTPUT VOLTAGE 240 VAC 1.25 X 10 X 1.21A= 15.13A <br /> NOMINAL OUTPUT CURRENT 1.21AI DERATED AMPACITY OF CIRCUIT CONDUCTOR PER NEC TABLE 310.15(B)(1): <br /> VERSION <br /> TEMP CORR. PER NEC TABLE 310.15(B)(1)X <br /> AMBIENT TEMPERATURE SPECS CONDUIT FILL CORR. PER NEC 310.15(C)(1)X DESCRIPTION DATE REV <br /> WEATHER STATION: SNOHOMISH CO CIRCUIT CONDUCTOR AMPACITY INITIAL RELEASE 07/07/2022 UR <br /> = <br /> RECORD LOW TEMP -5° 1.0 X 0.80 X 40 = 32.00A <br /> AMBIENT TEMP(HIGH TEMP 2%) 26° <br /> CONDUIT HEIGHT 0.9" RESULT SHOULD BE GREATER THAN 15.13A OTHERWISE LESS <br /> ROOF TOP TEMP 26° THE ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY <br /> CONDUCTOR TEMPERATURE RATE(ON ROOF) 90° <br /> CONDUCTOR TEMPERATURE RATE(OFF ROOF) 75° AC CONDUCTOR AMPACITY CALCULATIONS: <br /> MODULE TEMPERATURE COEFFICIENT OF Voc -0 27%/°c FROM COMBINER BOX 4 TO INTERCONNECTION: <br /> NUMBER OF CURRENT #OF INVERTERS: 20 <br /> PERCENT OF VALUES CARRYING CONDUCTORS IN EMT EXPECTED WIRE TEMP (°C): 26° <br /> .80 4-6 TEMP CORRECTION PER TABLE 310.15(B)(1): 1.0 <br /> 70 7-9 #OF CURRENT CARRYING CONDUCTORS: 3 <br /> CONDUIT FILL PER NEC 310.15(C)(1): 1.0 PROJECT NAME <br /> 50 10-20 CIRCUIT CONDUCTOR SIZE: 8 AWG 0 <br /> CIRCUIT CONDUCTOR AMPACITY: 50A D <br /> REQUIRED CIRCUIT CONDUCTOR AMPACITY PER NEC 690.8(B): U) p <br /> 1.25 X#MICRO-INVERTERS X MAX OUTPUT CURRENT= z z Z) O 0 W <br /> 1.25 X 1.21 X 20 = 30.25A <br /> Q J 0 O W <br /> DERATED AMPACITY OF CIRCUIT CONDUCTORS PER NEC TABLE 310.16: (7 } N �O U Lu <br /> TEMP CORR. PER NEC TABLE 310.15(B)(1)X Z W M p = W <br /> CONDUIT FILL CORR. PER NEC 310.15(C)(1)X 0 Z Q O C� LL <br /> CIRCUIT CONDUCTOR AMPACITY= 0 CN <br /> � 2i O <br /> 1.0 X 1.0 X 50 =50.00A W >- CD Q } <br /> RESULT SHOULD BE GREATER THAN 30.25A OTHERWISE LESS z N O O <br /> THE ENTRY FOR CIRCUIT CONDUCTOR SIZE AND AMPACITY _ COW *k Z 0 <br /> Q W a U) <br /> ELECTRICAL NOTES a w a > Q <br /> 1.)ALL EQUIPMENT TO BE LISTED BY UL OR OTHER NRTL, AND LABELED FOR ITS APPLICATION. J <br /> 2.)ALL CONDUCTORS SHALL BE COPPER, RATED FOR 600 V AND 90 DEGREE C WET ENVIRONMENT. _j <br /> 3.)WIRING, CONDUIT, AND RACEWAYS MOUNTED ON ROOFTOPS SHALL BE ROUTED DIRECTLY TO, AND LOCATED AS CLOSE AS POSSIBLE TO THE NEAREST RIDGE, HIP, OR VALLEY. <br /> 4.)WORKING CLEARANCES AROUND ALL NEW AND EXISTING ELECTRICAL EQUIPMENT SHALL COMPLY WITH NEC 110.26. <br /> 5.) DRAWINGS INDICATE THE GENERAL ARRANGEMENT OF SYSTEMS. CONTRACTOR SHALL FURNISH ALL NECESSARY OUTLETS, SUPPORTS, FITTINGS AND ACCESSORIES TO FULFILL SHEET NAME <br /> APPLICABLE CODES AND STANDARDS. ELECTRICAL <br /> 6.)WHERE SIZES OF JUNCTION BOXES, RACEWAYS, AND CONDUITS ARE NOT SPECIFIED, THE CONTRACTOR SHALL SIZE THEM ACCORDINGLY. CALCULATION <br /> 7.)ALL WIRE TERMINATIONS SHALL BE APPROPRIATELY LABELED AND READILY VISIBLE. <br /> 8.) MODULE GROUNDING CLIPS TO BE INSTALLED BETWEEN MODULE FRAME AND MODULE SUPPORT RAIL, PER THE GROUNDING CLIP MANUFACTURER'S INSTRUCTION. SHEET SIZE <br /> 9.) MODULE SUPPORT RAIL TO BE BONDED TO CONTINUOUS COPPER G.E.C. VIA WEEB LUG OR ILSCO GBL-4DBT LAY-IN LUG. ANSI B <br /> 10.)THE POLARITY OF THE GROUNDED CONDUCTORS IS NEGATIVE 11° X 17" <br /> ELECTRICAL CALCULATION SHEET NUMBER <br /> 1 SCALE: NTS PV-6 <br />