Laserfiche WebLink
AD • • • • • <br /> PAD-5-CDC <br /> Model PAD-5-CDC is the Conventional Zone Module used with PAD-5 notification-extender units. <br /> Specifically, each Model PAD-5-CDC supports four (4) 'Class A' or four (4) 'Class B' conventional- <br /> detection zone-input circuits. The address for Model PAD-5-CDC must be the next sequential <br /> (numerical)address to that of the connected Model PAD-5-MB main board. 2 <br /> Up to 30 Siemens conventional smoke detectors are supported, per zone. <br /> All information, per circuit, is displayed from the Operating Unit of the Siemens Modular FRCP. <br /> Each Model PAD-5-CDC supports Siemens and other-branded smoke detectors, as well as one (1) <br /> beam detector per zone. Additionally, Model PAD-5-CDC provides optional alarm verification by <br /> circuit,as well as consistent ground fault detection. lZ•• " ' ' <br /> Mounted to a PAD-5-MB <br /> Main Board <br /> PAD-5 Enclosures Power Supplies <br /> There are two (2) types of unit enclosures There are also two (2) types of power- <br /> available for Siemens PAD-5 power units I limited power supplies for Siemens <br /> extenders. The one-height-unit (1 HU) PAD-5 power units I extenders. (170W) <br /> enclosure, Model PAB-ENCL, is the basic The Model FP2011-U1 power supply <br /> enclosure. provides up to 6 Amps. at 170 Watts of <br /> Each 1HU enclosure can hold one (1) 170W main power to PAD-5, and Model <br /> 012-U1 provides up to 9 Amps. at <br /> or one (1) 30OW Siemens power supply; FP2 FP2 Watts. <br /> one (1) PAD-5 main board, and one (1) <br /> adapter plate,and one(1) Model PAD-5-CDC 7 HU Enclosure Additionally, the power supplies <br /> or one (1) Model PAD-5-CLSA. The two- can recharge and maintain backup <br /> height-unit (2HU) enclosure, Model PAB2- charge for the two (2) back-ups <br /> ENCL, allows for more versatility. Each 2HU batteries. The 170W power supply, (up to 170W) <br /> enclosure can house up to two (2) PAD-5 Model FP2011-U1, can provide <br /> main boards and power supplies. battery-backup charge of 7A(up to :':":'•': ui ; <br /> A red version of each enclosure is also 35AH), and the 300W power • <br /> furnished: Model PAB-ENCL-R for the 1HU supply, Model FP2012-U1, provides <br /> enclosure and Model PAB2-ENCL-R) for the battery-backup charge of 35AH (up <br /> 2HU enclosure. to 100AH) � <br /> (up to 300W) <br /> 2 HU Enclosure <br /> Status Indicator • • • Options <br /> Battery Charging Status: 7Yellow <br /> • PAD-5 Model CLSA <br /> CIRCUIT MAIN BOARD EXPANSION CARD EOL <br /> NAC 1 Status: uu REQUIRED <br /> TYPE 1 2 3 4 5 6 7 8 <br /> NAC 2 Status: llow <br /> Sync Coded v, I/ � ✓ ✓ ✓ Yes <br /> NAC 3 Status: Yellow Pattern 2.2k—240 <br /> NAC 4 Status: Yellow Auxiliary <br /> Power ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ — <br /> Auxiliary Output Status: Yellow Output <br /> 3.3VDC Status: Releasing* ✓ F <br /> Yes <br /> to 24kS2 <br /> Main Microprocessor Status: Yellow Shorting ✓ Yes <br /> P2 Loop Status: .- Device Input ✓ ✓ ✓ ✓ ✓ [�H� <br /> 2.2k—24kS2 <br /> *denotes Circuits 7 and 8 are not used for either <br /> Aux.Pwr.or NAC Output when PAD-5 is <br /> configured for releasing <br /> Siemens <br /> Smart Infrastructure— Building Products —3— usa.siemens.comlfire <br />