Laserfiche WebLink
UL Current Draw Data <br /> UL Max.Strobe Current Draw(mA RMS) UL Max.Horn Current Draw(mA RMS) <br /> 8-17.5 Volts 16-33 Volts 8-17.5 Volts 16-33 Volts <br /> Candela DC DC FWR Sound Pattern dB DC DC FWR <br /> Candela 15 87 41 60 Temporal High 39 44 54 <br /> Range 30 153 63 86 Temporal Low 28 32 54 <br /> 75 N/A 111 142 Non-Temporal High 43 47 54 <br /> 95 N/A 134 164 Non-Temporal Low 29 32 54 <br /> 115 N/A 158 191 3.1 KHz Temporal High 39 41 54 <br /> 150 N/A 189 228 3.1 KHz Temporal Low 29 32 54 <br /> 177 N/A 226 264 3.1 KHz Non-Temporal High 42 43 54 <br /> 3.1 KHz Non-Temporal Low 28 29 54 <br /> Coded High 43 47 54 <br /> 3.1 KHz Coded High 42 43 54 <br /> UL Max.Current Draw(mA RMS),Ceiling Horn Strobe,Candela Range(15-177 cd) <br /> 8-17.5 Volts 16-33 Volts <br /> DC Input 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd <br /> Temporal High 103 167 71 90 143 165 187 217 254 <br /> Temporal Low 96 165 54 71 137 161 185 211 249 <br /> Non-Temporal High 106 173 71 90 141 165 187 230 273 <br /> Non-Temportal Low 95 166 54 71 124 161 170 216 258 <br /> 3.1 K Temporal High 111 164 69 94 147 163 184 229 257 <br /> 3.1 K Temporal Low 103 163 54 88 143 155 185 212 252 <br /> 3.11K Non-Temporal High 111 172 69 94 144 164 202 229 271 <br /> 3.1 K Non-Temporal Low 103 169 54 88 131 155 187 217 259 <br /> 16-33 Volts <br /> FWR Input 15cd 30cd 75cd 95cd 115cd 150cd 177cd <br /> Temporal High 107 135 179 198 223 254 286 <br /> Temporal Low 78 101 151 172 199 229 262 <br /> Non-Temporal High 107 135 179 198 223 254 286 <br /> Non-Temportal Low 78 101 151 172 199 229 262 <br /> 3.1 K Temporal High 108 135 179 200 225 255 289 <br /> 3.1 K Temporal Low 79 101 150 171 196 229 260 <br /> 3.11K Non-Temporal High 108 135 179 200 225 255 289 <br /> 3.1 K Non-Temporal Low 79 101 150 171 196 229 260 <br /> Horn Strobe Tones and Sound Output Data <br /> 8-17.5 16-33 <br /> Switch Volts Volts <br /> Position Sound Pattern dB DC DC FWR <br /> 1 Temporal High 84 89 89 <br /> 2 Temporal Low 75 83 83 <br /> 3 Non-Temporal High 85 90 90 <br /> 4 Non-Temporal Low 76 84 84 <br /> 5 3.1 KHz Temporal High 83 88 88 <br /> 6 3.1 KHz Temporal Low 76 82 82 <br /> 7 3.1 KHz Non-Temporal High 84 89 89 <br /> 8 3.1 KHz Non-Temporal Low 77 83 83 <br /> AVDS868-02•12/01/2017•Page 3 <br />