Johnson <br /> # <br /> Controls <br /> Testing Procedure for Devices <br /> GENERAL: <br /> FOR ALL DEVICES(SUPPLIED BY JOHNSON CONTROLS)VISUALLY VERIFY PROPER LOCATION AND INSTALLATION. <br /> SMOKE DETECTOR: <br /> ACTIVATE THE DEVICE USING A SMOKE GENERATOR AND VERIFY ALARM CONDITION ON PANEL. RESET PANEL AND VERIFY RESET OF <br /> SMOKE DETECTOR AND PANEL. TEST FOR ALARM VERIFICATION IF APPROPRIATE. <br /> HEAT DETECTOR: <br /> FIXED TEMPERATURE REPLACEMENT ELEMENT-REMOVE ELEMENT ON HEAT DETECTOR TO INITIATE ALARM AND VERIFY ALARM CONDITION <br /> AT PANEL. REINSTALL ELEMENT,RESET SYSTEM,AND VERIFY. <br /> NON-REPLACEABLE ELEMENT-NON-REPLACEABLE ELEMENT HEAT DETECTORS CAN ONLY BE TESTED FOR CONTINUITY. <br /> RATE-OF-RISE DETECTORS-RATE OF RISE DETECTORS ARE TESTED WITH A HEATER OR BLOW DRYER UNTIL THEY INITIATE ALARM,THEN <br /> ALLOWED TO COOL. RESET PANEL AND VERIFY. <br /> PULL STATIONS: <br /> ACTIVATE STATION WITH THE T-HANDLE,VERIFY ALARM AND LABEL FOR LOCATION,RESET STATION,RESET PANEL. <br /> DUCT DETECTOR: <br /> (IF PROVIDED BY JOHNSON CONTROLS)WITH AIR HANDLING UNIT TURNED ON,OPEN ONE OF THE TEST PORT HOLES BY REMOVING THE RED <br /> COVER ON THE DUCT DETECTOR/SENSOR HOUSING. USING AN EXTENDED NOZZLE ON THE SMOKE DETECTOR AEROSOL TESTER SPRAY A <br /> FOUR TO EIGHT SECOND BURST OF AEROSOL THROUGH THE TEST PORT BUT NOT DIRECTLY AT THE DETECTOR/SENSOR HEAD. THE <br /> NOZZLE OF THE SMOKE DETECTOR AREOSOL TESTER SHOULD NOT EXTEND BEYOND THE INLET TUBE. AEROSOL IS SPRAYED INTO THE <br /> STREAM OF INCOMING AIR AND NOT DIRECTLY INTO DETECTOR/SENSOR. VERIFY ALARM,TEST ALL INDICATORS OR MANUAL TEST <br /> SWITCHES,RESET DETECTOR,RESET PANEL,TEST SAMPLE AND REFERENCE TUBE FOR POSITIVE AIR FLOW. (IF NOT PROVIDED BY <br /> JOHNSON CONTROLS)VERIFY THAT ZONE CIRCUIT IS PRESENT AT THE DEVICE. <br /> AUDIBLES AND VISIBLES: <br /> ACTIVATE ALARM AND CONFIRM THAT ALL INDICATING APPLIANCES,AUDIBLES AND VISIBLES,ARE OPERATING. <br /> DOOR HOLDERS: <br /> VERIFY THAT DOORS CLOSE ON ALARM. <br /> VALVE SUPERVISORY SWITCHES(TAMPER): <br /> (IF PROVIDED BY JOHNSON CONTROLS)ACTIVATE SWITCH BY MOVING VALVE OFF NORMAL,VERIFY STATUS CHANGE,RESET SWITCH, <br /> RESET PANEL. (IF NOT PROVIDED BY JOHNSON CONTROLS)VERIFY THAT ZONE CIRCUIT IS PRESENT AT THE SWITCH. <br /> FLOW SWITCHES AND PRESSURE SWITCHES: <br /> (IF PROVIDED BY JOHNSON CONTROLS)ACTIVATE SWITCH(WITH SPRINKLER CONTRACTOR PRESENT)BY A FLOW OF WATER,VERIFY <br /> STATUS CHANGE,RESET SWITCHES,RESET PANEL. (IF NOT PROVIDED BY JOHNSON CONTROLS)VERIFY THAT ZONE CIRCUIT IS PRESENT <br /> AND SUPERVISED AT THE SWITCH. <br /> FAN/DAMPER CONTROL CIRCUITS: <br /> VERIFY(WITH HVAC CONTRACTOR PRESENT)THAT THE CONTROL CIRCUIT IS OPERATING,AND THE DEVICES IS BEING CONTROLLED IN <br /> ACCORDANCE WITH THE SPECIFIED SEQUENCE OF OPERATION. <br /> ELEVATOR CONTROL CIRCUITS: <br /> VERIFY(WITH ELEVATOR CONTRACTOR PRESENT)THAT THE ELEVATOR IS BEING CONTROLLED IN ACCORDANCE WITH THE SPECIFIED <br /> SEQUENCE OF OPERATION. <br /> TRAINING: <br /> JOHNSON CONTROLS SHALL PROVIDE A ONE TRAINING SESSION TO THE CUSTOMER. <br /> WARRANTY: <br /> THE SYSTEM SHALL BE PROVIDED WITH A ONE YEAR HARDWARE WARRANTY. <br /> Fire,Security,Communications,Workforce Solutions,Sales Service <br /> Offices Representatives in Principle Cities throughout the World <br />