GENERAL NOTES <br /> MECHANICAL SHALL PROVIDE AND INSTALL STARTER <br /> AND DISCONNECT SWITCH. ELECTRICAL SHALL PROVIDE <br /> ONLY A SINGLE POINT CONNNECTION. <br /> SAFETY SHOWER HEAT TRACE JUNCTION BOX. <br /> 3. UNLESS OTHERWISE NOTED ALL WIRING SHALL BE 1/2"C <br /> — 2#12 THHN/THWN. <br /> 4. CONDUCTORS SHOWN: #12 AWG, STRANDED COPPER, <br /> INSULATION TYPE THHN/THWN, UNLESS OTHERWISE NOTED. <br /> 5. COLOR CODE CONDUCTORS: IDENTIFY CONDUCTORS WHICH <br /> DO NOT HAVE APPROPRIATEDLY COLORED INSULATION <br /> WITH COLOR TAPE WHEREVER CONDUCTORS ARE <br /> ACCESSIBLE. IDENTIFY INSULATED GROUND CONDUCTORS <br /> IN ACCORDANCE WITH THE LATEST NEC (USING TAPE). <br /> COLOR CODE AS FOLLOWS: <br /> E 208Y 120V 480Y 277V <br /> AO (LEFT BUS IN PNL) BLACK BROWN <br /> BO (CENTER BUS IN PNL) RED ORANGE <br /> 1 CO (RIGHT BUS IN PNL) BLUE YELLOW <br /> PANEL B/37a NEUTRAL WHITE GRAY <br /> 3/4"C — 2#10, 1#10G 4 EQUIPMENT GROUND GREEN GREEN <br /> ISOLATED GROUND GRN/YEL* GRN/YEL* <br /> *GREEN WITH YELLOW TRACER <br /> BADGE READER ENC OSURE DDC PANE (BY MECHANICAL) <br /> BUDING FACP 1 <br /> PANEL B/21b e/ 0 6. DYMO LABEL EACH RECEPTACLE, JUNCTION/OUTLET BOX <br /> BUFF AND SWITCH WITH CIRCUIT IDENTIFICATION. <br /> REPEATER RA F K <br /> PANEL A/8a,10b,12c <br /> 14a isb 140 16b 7. POST NEW PANEL SCHEDULES UPON COMPLETION OF <br /> t sb <br /> b JOB. <br /> GFl sb 9b 14a EF-02 8. IDENTIFY PANELS WITH LAMINATED PHENOLIC NAMEPLATESEC>CU-01—308 96 EL B/260,30c 16b 106 AS DETAILED. <br /> � 3VS54(45-308 PANEL A) 2 9 <br /> B/11c 14a L9> 24"x36"x13"D CHATSWORTH ENCLOSURE SHALL BE <br /> \ NE L B/29c / 19a TUFF BOOK <br /> / WATER CO ER 2VS54(45-308 PANEL B) B/24c 2DO CABINETS. INSTALLED WITH TOP AT 6'-0" ABOVE FINISHED FLOOR <br /> PANEL B/19a WITHIN CREW SHELTER. (2) DEDICATED 120V DUPLEX <br /> Z O /20a,22b 22b RECEPTACLES (TWO EACH SIDE, IN LOWER REAR <br /> PANEL B/11c EF-01— W 1 �18c CORNERS, STACKED, ON SIDE WALLS) SHALL BE <br /> 12 HE — PANEL B/23c,286,320 70 Ded. INSTALLED. <br /> PLASMA TV+66"AFF, 57 1/2" <br /> 2 FROM ELECT, ROOM OPENING <br /> 10 #6 BARE STRANDED COPPER CONDUCTOR SHALL BE <br /> 5c <br /> wP GFI — F +24"AFF 2c INSTALLED FROM ANTENNA LIGHTING ARRESTOR LUG TO <br /> WP GF CHATSWORTH ENCLOSURE P GFI <br /> WATER HEA isb GROUND ROD. GROUND CONDUCTOR SHALL BE ROUTED <br /> A W/30A DISCO b L ] PANEL B/130,15b UP TO 9'-0" ABOVE FINISHED GRAD AND ALONG <br /> SWITCH 3/4"G—13o,15#12G ob EXTERIOR OF BUILDING TO LIGHT POLE VIA UNISTRUT <br /> SUPPORT WITH COAX CABLE TO ANTENNA LIGHTING <br /> ANEL A/70,9b,11c 1 ARRESTOR. <br /> 1E60 E500 <br /> 11 #6 GROUND CONDUCTOR SHALL CONNECT TO GROUND <br /> T I PANEL B/5c <br /> 1>AHU-01-308 <br /> �G I ��� �� 3/4"C — 2#10, 1#10G ROD USING GROUND ROD CLAMP. <br /> \I 33b 12 HEAT TRACE SHALL BE APPLIED TO ALL EXPOSED <br /> P�NEL A/2a,4b,6c GFI <br /> (WITH SUPPLY FAN) 7a DED. PANEL B/80,10b,12c <br /> � G WATER PIPING ABOVE GRADE AND OUTSIDE CREW <br /> \ / 35c SHELTER, INCLUDING BACKFLOW PREVENTOR ON <br /> GFI 70 7a NORTHWEST CORNER OF CREW SHELTER. <br /> 12c 10b 1 c 106 <br /> 13 SAFETY SHOWER SHALL HAVE HEAT TRACE. CIRCUIT <br /> 2 0 1 SHALL BE CONNECTED TO HEAT TRACE USING POWER <br /> 13 CONNECTION KIT. SEE MECHANICAL DRAWING FOR <br /> #6 BARE COPPER GND. P NEL B/33b,35c T SAFETY SHOWER LOCATION. <br /> 10 ANTENNAE LIGHTING ARRESTOR. GR UND ROD <br /> 30KVA XFMR CONSTRUCTION NOTES <br /> REMOVE EXISTING BUILDING FACP, FOCUS <br /> PANEL AND ASSOCIATED CONDUIT BACK TO <br /> J—BOX. <br /> PLAN VIEW [Z::�' EXTEND POWER CIRCUIT AND WIRE TO NEW <br /> N BUILDING FACP. SEE SHEET E260 FOR MORE <br /> SCALE: 1/4"-1'-0" DETAILS. <br /> E <br /> Timothy C.4 Eastman- g* <br /> NICETCert' aim <br /> Ire Alarm Weterfi -Level IV 4' 2' 0 2' 4' <br /> rtifcation Expires:March 01,2025 <br /> PERMIT SUBMITTAL SCALE: 1/4"=1'-O" <br /> 03.03.24 PO Box 1138 <br /> AUBURN,WA 98071 <br /> SEATRONICS 253-939-6060 <br /> FIRE PROTECTION SERVICES JOB NO.of BwG xB. <br /> 9132326 9132326-1E60 <br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE ACCEPTABIHTY DRAWN DATE SUBTITLE CURRENT REVISION SYMBOL DATE <br /> RECORD DRAWING J#577613-02 HNTB/HAE HNTB/CAA 07.01.09 E FIRE ALARM PANEL REPLACEMENT SEA 03.03.24 THIS DESIGN AND/OR CHECKED POWER PLAN 9132326 E 03.03.24 0 <br /> SPECIFICATION IS APPROVED //� <br /> A POWER POLE INSTALLATION 9458179 BDH TT/BAB 10.23.09BOE//VG® APPROVED BY DEPT. DATE N IN TITLE SHEET 1 E60 L <br /> B BADGE READERS INSTALLATION 10118615 BDH TT/FB 07.16.10 CHECKED <br /> NO <br /> C STANDARDIZE POWER 10679136 BDH TT/FB 09.03.10 :#APPROVED BUILDING 45-308 JOB No. coMP45-308-1E60 <br /> D 1NETWORK ENTERPRISE UPGRADE— 18 W1874860 MDK AKC/BAO 08.23.13 APPROVED ELECTRICAL MASTER EVERETT, WA,DWG No. 45-308-1E60 <br />