Seatronics, Inc. Boeing 45-312 Section 1 <br />Job: 9132326 Fire Alarm System Submittal Manual Page 2 <br />SYSTEM SEQUENCE OF OPERATION <br />1. ALARM CONDITIONS: <br />1.1 ACTIVATION OF ANY SPOT TYPE SMOKE DETECTOR, MANUAL PULL STATION: <br />a. CAUSE THE ALARM INDICATOR LAMP ON THE FACP TO ILLUMINATE. <br />b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br />c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH ALARM POINT LOCATION <br />INFORMATION. <br />d. DISPLAY ALARM POINT LOCATION ON THE REMOTE ANNUNCIATORS. <br />e. CAUSE BUILDING FIRE ALARM STROBES AND HORN/STROBES TO ACTIVATE. <br />f. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT AN ALARM <br />SIGNAL TO THE TYCO CENTRAL STATION MONITORING COMPANY. <br />2. SUPERVISORY CONDITIONS: <br />2.1 ACTIVATION OF ANY FIRE SPRINKLER TAMPERS SHALL: <br />a. CAUSE THE SUPERVISORY INDICATOR LAMP ON FACP TO ILLUMINATE. <br />b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br />c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH SUPERVISORY POINT <br />LOCATION INFORMATION. <br />d. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT A <br />SUPERVISORY SIGNAL TO THE TYCO CENTRAL STATION MONITORING COMPANY. <br />3. FAULT / TROUBLE CONDITIONS: <br />3.1 CONDITIONS IN THE SYSTEM THAT MAY CAUSE FAILURE, OR IMPAIR OPERATION OF THE <br />SYSTEM SHALL CAUSE THE FOLLOWING: <br />a. CAUSE THE TROUBLE INDICATOR LAMP ON THE FACP TO ILLUMINATE. <br />b. CAUSE THE INTERNAL SOUNDER DEVICE IN THE FACP TO ACTIVATE. <br />c. DISPLAY PROPER MESSAGE ON FACP LCD DISPLAY WITH TROUBLE LOCATION <br />INFORMATION. <br />d. DISPLAY TROUBLE POINT LOCATION ON THE REMOTE ANNUNCIATORS <br />e. TRANSMIT A TROUBLE SIGNAL TO CENTURYLINK'S REMOTE MONITORING STATION. <br />f. ACTIVATE THE FACP DIGITAL DIALER/COMMUNICATOR AND TRANSMIT A TROUBLE <br />SIGNAL TO THE CENTRAL STATION MONITORING COMPANY. <br />THE FOLLOWING IS AN ABBREVIATED LIST OF THE TYPES OF FAULTS THAT WILL CAUSE <br />A TROUBLE CONDITION TO REPORT TO THE FACP. <br />a. OPEN, SHORTED OR GROUNDED WIRING ON ANY DETECTION CIRCUIT. <br />b. OPEN, SHORTED OR GROUNDED WIRING ON ANY MANUAL CIRCUIT. <br />c. ANY MISSING OR REMOVED ADDRESSABLE DEVICE SUCH AS SMOKE DETECTORS, <br />POINT MONITORING MODULES OR MANUAL STATIONS. <br />d. OPEN, SHORTED OR GROUNDED WIRING ON ANY NAC (HORN/STROBE) CIRCUIT. <br />e. ACTIVATION OF ANY PANEL "BYPASS" OR "OVERRIDE" FUNCTION. <br />f. CONTROL PANEL STAND-BY BATTERY FAULT. <br />g. LOSS OF PRIMARY 120 VAC POWER TO PANEL FOR MORE THAN 90 SECONDS. <br />h. LOSS OF 24VDC POWER. <br />i. FAILURE OF THE SYSTEM DIALER/COMMUNICATOR TO PROPERLY "CHECK -IN" TO THE <br />CENTRAL STATION MONITORING COMPANY ONCE EVERY 24 HOURS OR LOSS OF <br />EITHER OR BOTH PHONE LINES CONNECTED TO THE DIALER. <br />Seatronics, Inc. PO BOX 1138 Auburn, WA 98001 253-939-6060 <br />