Laserfiche WebLink
Mechanical Specifications <br /> Fully Modulating Economizer Start Kit <br /> This accessory shall be field installed and be composed Extra compressor starting capacity for single phase <br /> of the following items:0-100%fresh air damper, equipment. <br /> damper drive motor,fixed dry bulb enthalpy control, Control Options <br /> and low voltage pigtails for electrical connections. Standard Indoor Thermostats <br /> Solid state enthalpy or differential enthalpy control is <br /> optional. Economizer operations shall be controlled by Two stage heating/cooling or one stage heating/cooling <br /> the preset position of the enthalpy control.A thermostats shall be available in either manual or <br /> barometric relief damper shall be standard with the automatic changeover. <br /> economizer and provide a pressure operated damper Programmable Electronic Night Setting Thermostat <br /> that shall be gravity closing and prohibit entrance of Programmable electronic thermostat shall provide <br /> outside air on equipment"off"cycle.Economizer heating setback and cooling setup with 7-day <br /> requires BAYRLAY004A relay kit to interface the <br /> economizer to the heat pump. programming capability. 1H/1C or 2H/2C models <br /> available. <br /> Manual Outside Air Dampers <br /> Rain hood and screen shall be field installed.Suitable <br /> for up to 25% outside air. <br /> ETAUS Unitary Small HP AHRI Standard 210/240 <br /> Intertek <br /> The manufacturer optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, <br /> the leader in creating and sustaining safe, comfortable and energy efficient environments, the manufacturer offers a <br /> broad portfolio of advanced controls and HVAC systems, comprehensive building services, and parts. For more <br /> information,visit www.IRCO.com. <br /> The manufacturer has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. <br /> ©2014 Tra n e /.^w,/4WCC4060A—SUB-IE-EN 11 Dec2015 ,-../Ingersoll Rand <br /> Supersedes 4WCC4060A—SUB-1D-EN (June2015) `� <br />