ELECTRICAL SPECIFICATIONS:
<br /> PART 1-GENERAL MALFUNCTION AT NO ADDITIONAL COST TO THE OWNER. PART 3-EXECUTION GENERAL NOTES:
<br /> PART2-PRODUCTS
<br /> 1.1 GENERAL CONDITIONS 3.1 INSTALLATION OF ELECTRICAL EQUIPMENT 1. COMPLY WITH NEC AS ADOPTED AND AMENDED BY LOCAL
<br /> 2.1 MATERIAL AHJ VECA
<br /> A. THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL A. INSTALL EQUIPMENT IN ACCORDANCE WITH
<br /> PERMITS,MATERIALS,EQUIPMENT,LABOR,SUPERVISION,TOOLS, A. MATERIALS SHALL E NEW,FREE DEFECTS AND OF MANUFACTURER'S INSTRUCTIONS,NECA STANDARD OF 2. ALL EXISTING WORK IS BASED ON RECORD DRAWINGS AND
<br /> EXPENSES,TRAVEL,AND ITEMS NECESSARY FOR THE CURRENT MANUFACTURE..EXISTING MATE
<br /> RIALS SHALL NOT BE INSTALLATION AND IN ACCORDANCE WITH THE UL LISTING FOR THE HAS NOT BEEN FIELD VERIFIED IN FULL.THE ELECTRICAL
<br /> CONSTRUCTION,INSTALLATION,CONNECTION,TESTING AND REUSED UNLESS SPECIFICALLY NOTED OTHERWISE. EQUIPMENT OR MATERIAL. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING INFORMATION ml
<br /> ELECTRIC&TECHNOLOGIES
<br /> OPERATION OF ALL ELECTRICAL WORK FOR THIS PROJECT,AS
<br /> INTENDED BY THE CONTRACT DOCUMENTS. 2.2 WIRE AND CABLE(600 VOLT AND LESS) ALL DISCONNECTS,FUSES,CIRCUIT BREAKERS SHALL BE RELEVANT FOR THE SCOPE OF THIS PROJECT.
<br /> PROVIDED AS INDICATED AND FOR PROPER PROTECTION OF THE
<br /> B. THE GENERAL CONDITIONS,SUPPLEMENTARY CONDITIONS A. PRODUCTS SHALL COMPLY WITH UL 44 AND UL 83 SINGLE EQUIPMENT SERVED.PROVIDE ALL FLEXIBLE CONDUIT,BOXES, 3. ALL SCOPE NOT IDENTIFIED FOR DEMOLITION OR
<br /> AND SPECIAL CONDITIONS ARE A PART OF THIS CONTRACT AND CONDUCTOR INSULATED WIRE. PULL BOXES,FITTINGS,SEALS,AND OTHER MATERIALS REQUIRED MODIFICATIONS IS EXISTING TO REMAIN.REFER TO MECHANICAL
<br /> APPLY TO THIS SECTION AS FULLY AS IF REPEATED HEREIN. FOR A COMPLETE AN OPERATIONAL SYSTEM. DRAWINGS FOR DEMOLITION SCOPE OF WORK.
<br /> B. WIRE AND CABLE FOR USE ON SYSTEMS OF 600 VOLTS AND THE WORK UNDER THIS DIVISION INCLUDES FURNISHING ALL CONSULTANTS
<br /> 1.2 CODES AND REGULATIONS LESS SHALL BE 600 VOLT WITH NEC TYPE THHN/THWN OR XHHW PERMITS,MATERIALS,EQUIPMENT,LABOR,SUPERVISION,TOOLS 4. ALL WORK SHALL BE DONE WITH MAXIMUM CARE EXERCISED
<br /> INSULATION FOR BRANCH CIRCUITS AND FEEDERS SMALLER THAN AND ITEMS NECESSARY FOR THE CONSTRUCTION,INSTALLATION, DURING DEMOLITION AND MODIFICATIONS PROCESS.ANY
<br /> A. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH #2AWG.XHHW INSULATION SHALL BE USED FOR#2AWG AND CONNECTION,TESTING AND OPERATION OF ALL ELECTRICAL ACCIDENTAL OR INTENTIONAL DAMAGE TO EQUIPMENT TO REMAIN
<br /> APPLICABLE REQUIREMENTS OF THE AUTHORITY HAVING LARGER FEEDER CONDUCTORS. WORK FOR THIS PROJECT,AS INTENDED BY THE CONTRACT SHALL BE REPAIRED AT NO ADDITIONAL COST TO THE OWNER.
<br /> JURISDICTION AND THE UTILITY FURNISHING SERVICES FOR THE 1. USE TYPE THHNITHWN CONDUCTORS FOR ALL BRANCH DOCUMENTS.
<br /> SPECIFIC FACILITY LOCATION. POWER AND LIGHTING CIRCUITS. 5. UNLESS OTHERWISE REQUESTED BY THE OWNER ALL
<br /> 2. USE TYPE XHHW IN AMBIENT TEMPERATURES BELOW 32°F. 3.2 INSTALLATION OF RACEWAY AND FITTINGS REMOVED ELECTRICAL EQUIPMENT,DEVICES,AND MATERIALS
<br /> B. CODES GOVERNING THIS WORK INCLUDE BUT ARE NOT USE TYPE XHHW-2 FOR ALL WIRING CONNECTED TO GFCI SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR. EVIDENCE
<br /> LIMITED TO THE LATEST ADOPTED EDITION OF THE FOLLOWING: BREAKERS. A. INSTALL RIGID STEEL CONDUIT WHERE EXPOSED TO EBD
<br /> BASED
<br /> NFPA 70(NATIONAL FIRE PROTECTION ASSOCIATION) WEATHER,PLACED UNDERGROUND,IN OR UNDER CONCRETE OR
<br /> NATIONAL ELECTRICAL CODE(NEC)AS AMMENDED BY C. ALL GROUNDING CONDUCTORS SHALL BE INSULATED. MASONRY CONSTRUCTION,IN CONTACT WITH EARTH AND AS 6. ALL WORK SHALL BE DONE ON DE-ENERGIZED EQUIPMENT DESIGN
<br /> WASHINGTON CITIES(2020 WCEC) ONLY AND ALL LOTO(LOCK-OUT TAG OUT)PROCEDURES SHALL BE
<br /> NFPA 72(NATIONAL FIRE PROTECTION ASSOCIATION) D. MC OR HCF-MC CABLE SHALL BE PERMITTED FOR LIMITED INDICATED ON PLANS. FOLLOWED AS REQUIRED PER NEC AND OSHA. SERVICES
<br /> NATIONAL FIRE ALARM AND SIGNALING CODE USE AS FOLLOWS:
<br /> NFPA 101(NATIONAL FIRE PROTECTION ASSOCIATION)LIFE B. EMT MAY BE USED IN ABOVE GRADE INTERIOR DRY
<br /> SAFETY CODE 1. TEMPORARY POWER PROVISIONS LOCATIONS AND WHERE PROTECTED FROM PHYSICAL DAMAGE.
<br /> CITY OF EVERETT ORDINANCES AND REGULATIONS 2. EQUIPMENT CONNECTIONS TO COMPENSATE FOR MOVEMENT
<br /> WSEC-2021 COMMERCIAL AND VIBRATION. C. FLEXIBLE METAL CONDUIT SHALL BE USED WHERE REQUIRED
<br /> 3. TERMINAL CONNECTIONS TO LIGHT FIXTURES NOT TO TO MAKE CONNECTIONS TO VIBRATING OR ROTATING EQUIPMENT. `�'"pF WASgJ
<br /> 1.3 STANDARDS EXCEED 6 FEET IN LENGTH.
<br /> 4. LIGHTING AND BRANCH CIRCUITS. Fp
<br /> D. ALL RIGID STEEL CONDUIT INSTALLED IN CONTACT WITH
<br /> A. ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE 5. CONCEALED AREAS INDOORS. EARTH SHALL BE PVC COATED OR OTHERWISE PROTECTED WITH A
<br /> UNDERWRITER'S LABORATORIES LISTED AND INSTALLED IN BITUMASTIC MATERIAL. `
<br /> ACCORDANCE WITH THE LISTING AND LABELING OF THE 2.3 RACEWAY AND BOXES A 57724
<br /> EQUIPMENT. ��� IST
<br /> A. RIGID STEEL CONDUIT,ZINC COATED;ANSI C80.1:ALL E. MINIMUM SIZE OF CONDUIT SHALL BE CODE SIZE FOR THE �S'd/10 AL
<br /> B. INSTALLATION SHALL CONFORM TO THE NECA(NATIONAL FITTINGS SHALL BE SCREW THREAD TYPE,COUPLINGS,LOCKNUTS, NUMBER AND SIZE OF CONDUCTORS UNLESS A LARGER SIZE IS
<br /> ELECTRICAL CONTRACTORS ASSOCIATION)STANDARD OF BUSHINGS,ETC.SHALL BE HOT DIPPED GALVANIZED. INDICATED ON THE PLANS. 9I` ``�
<br /> INSTALLATION. /�
<br /> B. ELECTRICAL METALLIC TUBING,ZINC COATED:ANSIC80.3: F. WHERE PENETRATIONS ARE MADE THROUGH PARTITIONS, MEDICAL AIR COMPRESSOR 1.4 SUBMITTALS COUPLINGS AND CONNECTORS SHALL BE STEEL GALVANIZED, PROVIDE SEALING MATERIAL TO MAINTAIN THE FIRE RATING OF R COMPRESSOR
<br /> R
<br /> COMPRESSION TYPE WITH GLAND SEALING RINGS. THE PARTITION.FOR EXTERIOR WALLS PROVIDE SLEEVES AND REPLACEMENT
<br /> A. ELECTRONIC COPIES,IN.PDF FORMAT,OF MATERIALS LIST, SEALING TO PREVENT WATER AND MOISTURE PENETRATION AND
<br /> SHOP DRAWINGS AND DATA SHEETS SHALL BE SUBMITTED TO THE C. FLEXIBLE METAL CONDUIT:UL 1:FLEXIBLE METAL CONDUIT TO PREVENT VARMINT AND INSECT INTRUSION.
<br /> ENGINEER FOR REVIEW.SUBMITTALS SHALL BE MADE,AND SHALL BE GALVANIZED STEEL OR ALUMINUM.WHERE EXPOSED TO
<br /> FAVORABLE REVIEW SECURED BEFORE MATERIAL AND EQUIPMENT DAMP OR WET LOCATIONS FLEXIBLE CONDUIT SHALL BE 3.3INSTALLATION OF CONDUCTORS AND EQUIPMENT PROVIDENCE REGIONAL MEDICAL CENTER
<br /> IS INSTALLED. LIQUID-TIGHT WITH OUTER SUITABLE LIQUID-TIGHT FITTINGS LISTED CONNECTIONS
<br /> FOR THE PURPOSE. COLRY CAMPUS-C-WING
<br /> B. MATERIALS LIST SHALL INCLUDE:DEVICES,DISCONNECTS, A. ALL WIRING SHALL BE INSTALLED IN CONDUIT,WIREWAYS, 17OO 13TH STREET
<br /> LIGHT FIXTURES,LIGHTING CONTROL DEVICES AND OTHER ITEMS D. OUTLET AND JUNCTION BOXES:OUTLET AND JUNCTION A- ALL
<br /> EXCEPT WHERE OTHER RACEWAY SYSTEMS ARE
<br /> SPECIFIED OR CALLED FOR ON THE DRAWING.THE LIST SHALL BOXES SHALL BE GALVANIZED,ONE-PIECE PRESSED OR WELDED EVERETT,WA 98201
<br /> INCLUDE MANUFACTURE,TYPE AND SUCH OTHER DESCRIPTIVE STEEL,KNOCKOUT TYPE EXCEPT AS OTHERWISE NOTED OR SPECIFICALLY CALLED FOR.
<br /> DATA AS MAY BE REQUIRED TO DETERMINE THE ACCEPTABILITY OF SPECIFIED.
<br /> EACH ITEM. B. INSTALL WIRING ONLY AFTER RACEWAY INSTALLATION HAS
<br /> E. PROVIDE FIRE-STOPPING WHERE CONDUIT PASSES THROUGH BEEN COMPLETED CLEANED AND DRIED.
<br /> C. SHOP DRAWINGS AND DATA SHEETS FOR EQUIPMENT AND A RATED ASSEMBLY.
<br /> SYSTEMS SHALL BE SUBMITTED WHERE REQUIRED IN THE C. PULLING LUBRICANTS APPROVED BY THE WIRE OR CABLE
<br /> SPECIFICATIONS FOR THOSE ITEMS.INCLUDE INFORMATION ON 2.4 WIRING DEVICES(PROVIDE DEVICES PER DRAWINGS) MANUFACTURE MAY BE UTILIZED.
<br /> EACH COMPONENT,WIRING DIAGRAMS,LAYOUTS,DIMENSIONS
<br /> AND SUFFICIENT OTHER DATA TO ESTABLISH COMPLIANCE WITH A. CIRCUITING: D. MAKE ALL CONNECTIONS AND SPLICES REQUIRED FOR
<br /> THE SPECIFICATIONS AND ACCEPTABILITY OF THE EQUIPMENT OR 1. 480/277V BRANCH CIRCUIT WIRING SHALL BE IN SEPARATE COMPLETE AND OPERABLE ELECTRICAL INSTALLATION.
<br /> SYSTEM. CONDUITS FROM 2081120V CIRCUIT WIRING. CONNECTIONS AND SPLICES SHALL BE MADE ONLY IN JUNCTION,
<br /> D. PROVIDE PRODUCT DATA AND SHOP DRAWINGS FOR THE 2.5 ENCLOSURES PULL OR OUTLET BOXES OR IN WIREWAYS,SWITCHBOARDS AND
<br /> FOLLOWING: PANELBOARDS HAVING CODE SIZED GUTTER SPACE OR
<br /> CROSS-SECTIONAL AREA.WIRES#8 AND SMALLER CONNECTIONS
<br /> A. ENCLOSED SWITCHES AND CIRCUIT BREAKERS: NEMA AS 1, SHALL BE MADE WITH SPRING TYPE CONNECTORS;WIRES#6 AND
<br /> 1. FUSED DISCONNECT SWITCHES NEMA KS 1,NEMA 250,AND UL 50,TO COMPLY WITH LARGER,CONNECTIONS SHALL BE MADE WITH SPLIT-BOLT OR
<br /> ENVIRONMENTAL CONDITIONS AT INSTALLED LOCATION. COMPRESSION TYPE SOLDERLESS CONNECTORS,INSULATED AND
<br /> 1.5 SUBSTITUTIONS 1. INDOOR,DRY AND CLEAN LOCATIONS: NEMA 250,TYPE 1. TAPED.
<br /> A. NO SUBSTITUTIONS ARE ALLOWED.ALTERNATIVE
<br /> 2. OUTDOOR LOCATIONS: NEMA 250,TYPE 3R. CONSTRUCTION
<br /> 3. WASH-DOWN AREAS: NEMA 250,TYPE 4X,STAINLESS STEEL.
<br /> MANUFACTURERS WILL BE CONSIDERED FOR ELECTRICAL E. UPON COMPLETION OF WORK,UPDATED ALL PANEL
<br /> EQUIPMENT SPECIFIED AND SHOWN HEREIN.THE SPECIFIED 4. OTHER WET OR DAMP,INDOOR LOCATIONS: NEMA 250,TYPE DIRECTORIES WITH CORRECT CIRCUIT INFORMATION.PROVIDE DOCUMENTS
<br /> MANUFACTURER'S EQUIPMENT SETS THE LEVEL OF QUALITY FOR 4. PRINTED CIRCUIT DIRECTORIES IN PANELS AFFECTED BY THE
<br /> THE WORK. 5. INDOOR LOCATIONS SUBJECT TO DUST,FALLING DIRT,AND PROJECT. PEN AND INK CHANGES TO THE EXISTING DIRECTORIES
<br /> DRIPPING NONCORROSIVE LIQUIDS: NEMA 250,TYPE 12. ARE NOT ACCEPTABLE.
<br /> WORK AND EQUIPMENT NOT MEETING THE LEVEL OF QUALITY
<br /> SHALL BE REJECTED.THE ENGINEER HAS DISCRETION TO ACCEPT 2.6 GROUNDING 3.4 GROUNDING
<br /> OR REJECT THE ALTERNATIVE MANUFACTURER'S EQUIPMENT.
<br /> 1.6 PERMITS AND DRAWINGS A. PROVIDE COPPER GROUNDING. A. PERMANENTLY AND EFFECTIVELY GROUND ALL CONDUIT,
<br /> BOXES,ENCLOSURES AND EQUIPMENT TO COMPLY WITH NEC 250
<br /> A. PERMITS AND INSPECTIONS SHALL BE OBTAINED, B. PROVIDE DEDICATED NEUTRAL(NO SHARED NEUTRALS)WITH AND ALL APPLICABLE CODES AND REGULATIONS.
<br /> COORDINATED AND PAID FOR BY THE ELECTRICAL CONTRACTOR. ALL BRANCH CIRCUITS IN EACH CONDUIT.USE OF MULTI-POLE
<br /> BREAKERS OR BREAKER TIES IN LIEU OF DEDICATED NEUTRALS IS B. PROVIDE AN INSULATED EQUIPMENT GROUNDING
<br /> B. THE CONTRACTOR SHALL PAY ALL FEES AND TAXES FOR THE NOT PERMITTED. CONDUCTOR IN ALL RACEWAYS SIZED IN ACCORDANCE WITH NEC
<br /> TOTAL COST OF CONSTRUCTION,INCLUDING CONTRACTOR AND TABLE 250.122 WHETHER SPECIFICALLY CALLED FOR ON THE
<br /> OWNER FURNISHED MATERIALS AND EQUIPMENT AS SHOWN AND C. ALL CONDUITS WILL BE PROPERLY BONDED WITH INSULATED PLANS OR NOT.
<br /> SPECIFIED. GROUND WIRE RUN WITH CONDUCTORS.
<br /> 3.5 PROTECTION OF PREMISES
<br /> C. THE CONTRACTOR SHALL OBTAIN AND PAY THE PLAN REVIEW D. ALL PANELS AND TRANSFORMERS MUST HAVE A DEDICATED
<br /> FEE. EQUIPMENT GROUNDING CONDUCTOR IN ADDITION TO ELECTRODE A. CONTRACTOR SHALL CLEAN WORK AREA AND REMOVE ALL
<br /> D. THE CONTRACTOR SHALL PAY FOR PLAN REVIEW FEES AND OR BUILDING GROUNDS AS REQUIRED PER CODE. CONSTRUCTION DEBRIS DAILY PRIOR TO LEAVING THE PREMISES.
<br /> RE-INSPECTIONS RESULTING FROM SUBSTITUTIONS. FEES DUE TO
<br /> SUBSTITUTIONS SHALL BE AT NO COST TO THE OWNER. 2.7 EQUIPMENT IDENTIFICATION B. THE CONTRACTOR SHALL PROTECT ALL EXISTING SURFACES,
<br /> MATERIALS,EQUIPMENT AND PROPERTY FROM DAMAGE AS
<br /> E. THE CONTRACTOR SHALL INCLUDE APPLICABLE PLAN A. ENCLOSED CIRCUIT BREAKERS,DISCONNECT SWITCHES, RESULT OF CONSTRUCTION ACTIVITIES. DAMAGED SURFACES,
<br /> REVIEW FEES AND RE-INSPECTION FEES IN CHANGE ORDER RECEPTACLES AND LIGHT SWITCHES: PRINTED LABEL WITH MATERIALS,EQUIPMENT AND PROPERTY SHALL BE REPAIRED TO
<br /> PROPOSALS. (PANEL)NAME AND CIRCUIT NUMBER.(EXAMPLE:"PP4.23"FOR EXISTING CONDITIONS AT NO COST TO THE OWNER.
<br /> PANEL PP4,CIRCUIT 23)
<br /> 1.7 RECORD DRAWINGS NORMAL POWER:%"BLACK LETTERS 3.6 TESTING OF ELECTRICAL SYSTEMS
<br /> EQUIPMENT BRANCH POWER:''/,"RED LETTERS
<br /> A. ON A SET OF CONTRACT DRAWINGS KEPT AT THE SITE A. EQUIPMENT INSTALLED OR MODIFIED UNDER THIS SECTION
<br /> DURING CONSTRUCTION,MARK ALL WORK THAT IS INSTALLED SHALL BE INSPECTED AND TESTED FOR PROPER OPERATION IN
<br /> DIFFERENTLY FROM THAT SHOWN,INCLUDE ANY REVISED 2.8 FUSIBLE SWITCHES ACCORDANCE WITH APPLICABLE NETA ACCEPTANCE TESTING MARK DATE DESCRIPTION
<br /> CIRCUITRY,MATERIAL OR EQUIPMENT.UPON CONCLUSION OF THE STANDARDS.
<br /> WORK,DELIVER TO THE OWNER REPRESENTATIVE A SET OF A. TYPE GD,GENERAL DUTY,SINGLE THROW,100A AND PROJECT NO:B24-1103
<br /> SIGNED AND DATED"AS-BUILT"DRAWINGS. SMALLER;UL98 AND NEMA KS 1,HORSEPOWER RATED,WITH B. SYSTEMS SHALL BE TESTED FOR SHORT CIRCUITS,OPEN CADDWG FILE:eol.owc
<br /> CARTRIDGE FUSE INTERIORS,LOCKABLE HANDLE WITH CIRCUITS,PHASE ROTATION AND SHALL BE FREE FROM
<br /> 1.8 WARRANTY CAPABILITY TO ACCEPT TWO PADLOCKS,AND INTERLOCKED WITH MECHANICAL AND ELECTRICAL DEFECTS. DRAWN BY:CMB
<br /> COVER IN CLOSED POSITION.
<br /> CHMD BY:JGG
<br /> A. ALL WORK SHALL INCLUDE A WARRANTY FOR A MINIMUM
<br /> PERIOD OF ONE YEAR FROM THE DATE OF ACCEPTANCE BY THE B. TYPE HD,HEAVY DUTY,SINGLE THROW,LARGER THAN 100A: C. THE CONTRACTOR SHALL CORRECT DEFICIENCIES AND COPYRIGHT:
<br /> OWNER.THE WARRANTY PERIOD FOR CERTAIN ITEMS SHALL BE UL 98 AND NEMA KS 1,HORSEPOWER RATED,WITH CLIPS OR BOLT PROVIDE RETESTING AT NO EXPENSE TO THE OWNER AND
<br /> LONGER,AS INDICATED IN THE SPECIFICATIONS FOR THOSE ITEMS. PADS TO ACCOMMODATE FUSES,LOCKABLE HANDLE WITH ENGINEER UNTIL THE EQUIPMENT AND SYSTEM IS SATISFACTORY
<br /> CAPABILITY TO ACCEPT THREE PADLOCKS,AND INTERLOCKED TO THE OWNER AND THE ENGINEER. SHEET TITLE
<br /> B. SHOULD ANY MALFUNCTION DEVELOP DURING THE WITH COVER IN CLOSED POSITION. ELECTRICAL SPECIFICATIONS
<br /> WARRANTY TIME PERIOD DUE TO DEFECTIVE MATERIAL,FAULTY
<br /> WORKMANSHIP,OR NON-COMPLIANCE WITH PLANS, C. ACCESSORIES:
<br /> SPECIFICATIONS,CODE OR DIRECTIONS OF THE OWNER OR
<br /> OWNER'S REPRESENTATIVE,THE CONTRACTOR SHALL FURNISH 1. CLASS R FUSE KIT:PROVIDES REJECTION OF OTHER FUSE
<br /> ALL NECESSARY LABOR AND MATERIALS TO CORRECT THE TYPES WHEN CLASS R FUSES ARE SPECIFIED.
<br /> E0.1