Laserfiche WebLink
:' 3 4 <br /> ELECTRICAL INSTALLATION NOTES: GREENFIELD GROUNDING NOTES: ., & <br /> 1. ALL GROUND ELECTRODE SYSTEMS(INCLUDING TELECOMMUNICATION,RADIO.LIGHTNING PROTECTION AND AC POWER GES'S)SHALL BE BONDED TOGETHER AT OR BELOW GRADE,BY TWO OR MORE COPPER BONDING CONDUCTORS IN ACCORDANCE WITH THE NEC. G P D GROUP <br /> 1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,NEC AND ALL APPLICABLE FEDERAL. <br /> STATE,AND LOCAL CODES/ORDINANCES. 2. THE CONTRACTOR SHALL PERFORM IEEE FALL-OF-POTENTAL RESISTANCE TO EARTH TESTING(PER IEEE 1100 AND 81)FOR GROUND ELECTRODE SYSTEMS,THE CONTRACTOR SHALL FURNISH AND INSTALL SUPPLEMENTAL GROUND Professional Corporation <br /> 2. CONDUIT ROUTINGS ARE SCHEMATIC.CONTRACTOR SHALL INSTALL CONDUITS SO THAT ACCESS TO EQUIPMENT IS NOT BLOCKED AND TRIP ELECTRODES AS NEEDED TO ACHIEVE A TEST RESULT OF 5 OHMS OR LESS. <br /> HAZARDS ARE ELIMINATED. 3. THE CONTRACTOR IS RESPONSIBLE FOR PROPERLY SEQUENCING GROUNDING AND UNDERGROUND CONDUIT INSTALLATION AS TO PREVENT ANY LOSS OF CONTINUITY IN THE GROUNDING SYSTEM OR DAMAGE TO THE CONDUIT AND 320 South Main Stteet,5aire 2531 <br /> PROVIDE TESTING RESULTS. Akron,OH 4011 <br /> 3. WILING,RACEWAY AND SUPPORT TMETHODS AND MATERIALS SHALL COMPLY WITH THE REQUIREMENTSIREDE NEC. NEC. 4. METAL CONDUIT AND TRAY SHALL BE GROUNDED AND MADE ELECTRICALLY CONTINUOUS WITH LISTED BONDING FITTINGS OR BY BONDING ACROSS THE DISCONTINUITY WITH#6 COPPER WIRE UL APPROVED GROUNDING TYPE CONDUIT s3a.s7z.zloa Fax z3o.57z.2to1 <br /> 4. ALL CIRCUITS SHALL BE SEGREGATED AND MAINTAIN MINIMUM CABLE SEPARATION AS REQUIRED BY THE NEC. CLAMPS. <br /> 4.1. ALL EQUIPMENTSHALL CO THE UNDERWRITERS LABORATORIES LABEL OF APPROVAL,AND SHALL CONFORM TO REQUIREMENT OF THE 5. METAL RACEWAY SHALL NOT BE USED AS THE NEC REQUIRED EQUIPMENT GROUND CONDUCTOR.STRANDED COPPER CONDUCTORS WITH GREEN INSULATION.SIZED IN ACCORDANCE WITH THE NEC.SHALL BE FURNISHED AND INSTALLED <br /> NATIONALIONALELECTRICAL CODE. WITH THE POWER CIRCUITS TO BTS EQUIPMENT. <br /> 4.2. ALL OVER T DEVICES SHALL HAVE AN INTERRUPTING CURRENT RATING THAT SHALL BE GREATER THAN THE SHORT CIRCUIT 6. EACH CABINET FRAME SHALL BE DIRECTLY CONNECTED TO THE MASTER GROUND BAR WITH GREEN INSULATED SUPPLEMENTAL EQUIPMENT GROUND WIRES,#6 STRANDED COPPER OR LARGER FOR INDOOR BTS;#2 BARE SOLID TINNED 1 <br /> CURRENT <br /> TO WHICH THEY ARE SUBJECTED,22,000 AIC MINIMUM.VERYIFY AVAILABLE SHORT CIRCUIT CURRENT DOES NOT EXCEED THE COPPER FOR OUTDOOR BTS.RATI a+�ct <br /> GOVERNINGEG OF ELECTRICALDICTI EQUIPMENT IN ACCORDANCE WITH ARTICLE 110.24 NEC OR THE MOST CURRENT ADOPTED CODE PRE THE 7. CONNECTIONS TO THE GROUND BUS SHALL NOT BE DOUBLED UP OR STACKED BACK TO BACK CONNECTIONS ON OPPOSITE SIDE OF THE GROUND BUS ARE PERMITTED. ■\ <br /> JURISDICTION. 8. ALL EXTERIOR GROUND CONDUCTORS BETWEEN EQUIPMENT/GROUND BARS AND THE GROUND RING SHALL BE#2 SOLID TINNED COPPER UNLESS OTHERWISE INDICATED. <br /> 5. EACH END OF EVERY POWER PHASE CONDUCTOR,GROUNDING CONDUCTOR,AND TELCO CONDUCTOR OR CABLE SHALL BE LABELED WITH 9, ALUMINUM CONDUCTOR OR COPPER CLAD STEEL CONDUCTOR SHALL NOT BE USED FOR GROUNDING CONNECTIONS. <br /> COLOR-CODED INSULATION OR ELECTRICAL TAPE(3M BRAND.12"PLASTIC ELECTRICAL TAPE WITH UV PROTECTION,OR EQUAL).THE 10. USE OF 90°BENDS IN THE PROTECTION GROUNDING CONDUCTORS SHALL BE AVOIDED WHEN 45°BENDS CAN BE ADEQUATELY SUPPORTED. Mobility <br /> IDENTIFICATION METHOD SHALL CONFORM WITH NEC AND OSHA. 11. EXOTHERMIC WELDS SHALL BE USED FOR ALL GROUNDING CONNECTIONS BELOW GRADE. <br /> C 6. ALL ELECTRICAL COMPONENTS SHALL BE CLEARLY LABELED WITH LAMICOID TAGS SHOWING THEIR RATED VOLTAGE,PHASE CONFIGURATION, 12 ALL GROUND CONNECTIONS ABOVE GRADE(INTERIOR AND EXTERIOR)SHALL BE FORMED USING HIGH PRESS CRIMPS. 19801 SW 72ND AVENUE,STE.200 <br /> WIRE CONFIGURATION,POWER OR AMPACITY RATING AND BRANCH CIRCUIT ID NUMBERS(i.e.PANEL BOARD AND CIRCUIT ID'S). 13. COMPRESSION GROUND CONNECTIONS MAY BE REPLACED BY EXOTHERMIC WELD CONNECTIONS. TUALATIN,OR 97062 <br /> 7. PANEL BOARDS(ID NUMBERS)SHALL BE CLEARLY LABELED WITH PLASTIC LABELS. 14. ICE BRIDGE BONDING CONDUCTORS SHALL BE EXOTHERMICALLY BONDED OR BOLTED TO THE BRIDGE AND THE TOWER GROUND BAR. <br /> 8. ALL TIE WRAPS SHALL BE CUT FLUSH WITH APPROVED CUTTING TOOL TO REMOVE SHARP EDGES. 15. APPROVED ANTIOXIDANT COATINGS(i.e.CONDUCTIVE GEL OR PASTE SHALL BE USED ON ALL COMPRESSION AND BOLTED GROUND CONNECTIONS. <br /> 9. ALL POWER AND EQUIPMENT GROUND WIRING IN TUBING OR CONDUIT SHALL BE SINGLE COPPER CONDUCTOR( OR LARGER)WITH TYPE 16. ALL EXTERIOR GROUND CONNECTIONS SHALL BE COATED WITH A CORROSION RESISTANT MATERIAL <br /> W THHW,THN,THWN-2,XHHW,XHHW-2,THW,THW-2,RHW,OR RHW-2 INSULATION UNLESS OTHERWISE SPECIFIED. <br /> 17. MISCELLANEOUS ELECTRICAL AND NON-ELECTRICAL METAL BOXES,FRAMES AND SUPPORTS SHALL BE BONDED TO THE GROUND RING,IN ACCORDANCE WITH THE NEC. <br /> 10. SUPPLEMENTAL EQUIPMENT GROUND WIRING LOCATED INDOORS SHALL BE SINGLE COPPER CONDUCTOR(#6 OR LARGER)WITH TYPE THHW. 18. BOND ALL METALLIC OBJECTS WITHIN 6 R OF MAIN GROUND RING WITH(1)#2 BARE SOLID TINNED COPPER GROUND CONDUCTOR. <br /> TOWN,TOWN-2,XHHW,XHHW-2,THW.FLEXIBLE CORD RHW,OR RHW-2 IJ8 O R TYPES SOOW <br /> OTHERWISE CORD(414 OR 19. GROUND CONDUCTORS USED FOR THE FACILITY GROUNDING AND LIGHTNING PROTECTION SYSTEMS SHALL NOT BE ROUTED THROUGH METALLIC OBJECTS THAT FORM A RING AROUND THE CONDUCTOR,SUCH AS METALLIC CONDUITS, <br /> 11. POWER AND CONTROL WIRING IN SHALL BE MULTI-CONDUCTOR, SOO (#14 LARGER)UNLESS OTHERWISE <br /> SPECIFIED. METAL SUPPORT CLIPS OR SLEEVES THROUGH WALLS OR FLOORS.WHEN IT IS REQUIRED TO BE HOUSED IN CONDUIT TO MEET CODE REQUIREMENTS OR LOCAL CONDITIONS,NONMETALLIC MATERIAL SUCH AS PVC CONDUIT SHALL BE e•#1 a s T e c <br /> USED.WHERE USE OF METAL CONDUIT IS UNAVOIDABLE(i.e.,NONMETALLIC CONDUIT PROHIBITED BY LOCAL CODE)THE GROUND CONDUCTOR SHALL BE BONDED TO EACH END OF THE METAL CONDUIT. <br /> 12. POWER AND CONTROL WIRING FOR USE IN CABLE TRAY SHALL BE ULESS MULTI-CONDUCTOR.TTYPE IC CABLE(#14 OR LARGER),WITH TYPE THHW, 20, ALL GROUNDS THAT TRANSITION FROM BELOW GRADE TO ABOVE GRADE MUST BE#2 BARE SOLID TINNED COPPER IN 3/4"NON-METALLIC,FLEXIBLE CONDUIT FROM 24"BELOW GRADE TO WITHIN 3"TO 8"OF CAD-WELD TERMINATION POINT. Network Solutions <br /> TOWN,TOWN-2,XHHW,XHHW-2,THW,THW-2.RHW,OR INSULATIONRHW-2E, UNLESS OTHERWISE SPECIFIED. THE EXPOSED END OF THE CONDUIT MUST BE SEALED WITH SILICONE CAULK.(ADD TRANSITIONING GROUND STANDARD DETAIL AS WELL). <br /> 13. ALL POWER AND GROUNDING CONNECTIONS SHALL BE CRIMP-STYLE,NOT <br /> E,COMPRESSION WIRE LUGS AND WIRE NUTS BY THOMAS AND BETTS(OR <br /> EQUAL).LUGS AND WIRE NUTS SHALL BE RATED FOR OPERATION N LESS THAN 75°C(90•C IF AVAILABLE). 21. BUILDINGS WHERE THE MAIN GROUNDING CONDUCTORS ARE REQUIRED TO BE ROUTED TO GRADE,THE CONTRACTOR SHALL ROUTE TWO GROUNDING CONDUCTORS FROM THE ROOFTOP,TOWERS,AND WATER TOWERS GROUNDING RING, 22263 68TH AVENUE SOUTH <br /> 14. RACEWAY AND CABLE TRAY SHALL BE LISTED OR LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA,UL,ANSMEEE AND NEC. TO THE EXISTING GROUNDING SYSTEM.THE GROUNDING CONDUCTORS SHALL NOT BE SMALLER THAN 2/0 COPPER.ROOFTOP GROUNDING RING SHALL BE BONDED TO THE EXISTING GROUNDING SYSTEM,THE BUILDING STEEL COLUMNS, KENT.WA 98032 <br /> 15. ELECTRICAL METALLIC TUBING(EMT),INTERMEDIATE METAL CONDUIT(IMC),OR RIGID METAL CONDUIT(RMC)SHALL BE USED FOR EXPOSED LIGHTNING PROTECTION SYSTEM.AND BUILDING MAIN WATER LINE(FERROUS OR NONFERROUS METAL PIPING ONLY). <br /> INDOOR LOCATIONS. <br /> 16. ELECTRICAL METALLIC TUBING(EMT)OR METAL-CLAD CABLE(MC)SHALL BE USED FOR CONCEALED INDOOR LOCATIONS. <br /> 17. SCHEDULE 40 PVC UNDERGROUND ON STRAIGHTS AND SCHEDULE 80 PVC FOR ALL ELBOWS/90s AND ALL APPROVED ABOVE GRADE PVC <br /> CONDUIT. <br /> 18. LIQUID-TIGHT FLEXIBLE METALLIC CONDUIT(LIQUID-TITE FLEX)SHALL BE USED INDOORS AND OUTDOORS,WHERE VIBRATION OCCURS OR ,/5 <br /> FLEXIBILITY IS NEEDED. <br /> 19. CONDUIT AND TUBING FITTINGS SHALL BE THREADED OR COMPRESSION-TYPE AND APPROVED FOR THE LOCATION USED.SET SCREW FITTINGS Z F F <br /> ARE NOT ACCEPTABLE. <br /> 20. CABINETS,BOXES AND WIRE WAYS SHALL BE LABELED FOR ELECTRICAL USE IN ACCORDANCE WITH NEMA,UL,ANSUIEEE AND THE NEC. d > w z w <br /> 21. WIREWAYS SHALL BE METAL WITH AN ENAMEL FINISH AND INCLUDE A HINGED COVER,DESIGNED TO SWING OPEN DOWNWARDS(WIREMOLD E. ¢ E r I <br /> SPECMATE WIREWAY). g O ¢ O <br /> 22. SLOTTED WIRING DUCT SHALL BE PVC AND INCLUDE COVER(PANDUIT TYPE E OR EQUAL). 111 CO S+ ¢ H ¢ <br /> 23. CONDUITS SHALL BE FASTENED SECURELY IN PLACE WITH APPROVED NON-PERFORATED STRAPS AND HANGERS.EXPLOSIVE DEVICES(Le. O a z i <br /> POWDER-ACTUATED)FOR ATTACHING HANGERS TO STRUCTURE WILL NOT BE PERMITTED.CLOSELY FOLLOW THE LINES OF THE STRUCTURE, LL p O 0 <br /> MAINTAIN CLOSE PROXIMITY TO THE STRUCTURE AND KEEP CONDUITS IN TIGHT ENVELOPES.CHANGES IN DIRECTION TO ROUTE AROUND DI w 03 Uii <br /> OBSTACLES SHALL BE MADE WITH CONDUIT OUTLET BODIES.CONDUIT SHALL BE INSTALLED IN A NEAT AND WORKMANUKE MANNER.PARALLEL W ,71,. ..i, <br /> i w <br /> AND PERPENDICULAR TO STRUCTURE WALL AND CEILING LINES.ALL CONDUIT SHALL BE FISHED TO CLEAR OBSTRUCTIONS.ENDS OF CONDUITS m u rc <br /> SHALL BE TEMPORARILY CAPPED FLUSH TO FINISH GRADE TO PREVENT CONCRETE,PLASTER OR DIRT FROM ENTERING.CONDUITS SHALL BE - <br /> RIGIDLY CLAMPED TO BOXES BY GALVANIZED MALLEABLE IRON BUSHING ON INSIDE AND GALVANIZED MALLEABLE IRON LOCKNUT ON OUTSIDE W- <br /> AND INSIDE. <br /> 24. EQUIPMENT CABINETS.TERMINAL BOXES,JUNCTION BOXES AND PULL BOXES SHALL BE GALVANIZED OR EPDXY-COATED SHEET STEEL SHALL 0 o 8 0 /2 <br /> MEET OR EXCEED UL 50 AND BE RATED NEMA 1(OR BETTER)FOR INTERIOR LOCATIONS AND NEMA 3R(OR BETTER)FOR EXTERIOR LOCATIONS. .- <br /> 25. METAL RECEPTACLE.SWITCH AND DEVICE BOXES SHALL BE GALVANIZED,EPDXY-COATED OR NON-CORRODING;SHALL MEET OR EXCEED UL < m o <br /> 514A AND NEMA OS 1 AND BE RATED NEMA 1(OR BETTER)FOR INTERIOR LOCATIONS AND WEATHER PROTECTED(WP OR BETTER)FOR 66 <br /> EXTERIOR LOCATIONS. .t.1d P.SL iy <br /> 26. NONMETALLIC RECEPTACLE,SWITCH AND DEVICE BOXES SHALL MEET OR EXCEED NEMA OS 2(NEWEST REVISION)AND BE RATED NEMA 1(OR K(, F 1z,1`,H/ 'Y <br /> BETTER)FOR INTERIOR LOCATIONS AND WEATHER PROTECTED(WP OR BETTER)FOR EXTERIOR LOCATIONS. �� rGO1C!G� <br /> B 27. THE CONTRACTOR SHALL NOTIFY AND OBTAIN NECESSARY AUTHORIZATION FROM THE CARRIER AND/OR AT&T BEFORE COMMENCING WORK h _ <br /> ON THE AC POWER DISTRIBUTION PANELS. <br /> 28. THE CONTRACTOR SHALL PROVIDE NECESSARY TAGGING ON THE BREAKERS,CABLES AND DISTRIBUTION PANELS IN ACCORDANCE WITH THE .1 1 <br /> APPLICABLE CODES AND STANDARDS TO SAFEGUARD LIFE AND PROPERTY. <br /> 29. INSTALL LAMICOID LABEL ON THE METER CENTER TO SHOW"AT&T'. q 50ab1 <br /> 30. ALL EMPTY/SPARE CONDUITS THAT ARE INSTALLED ARE TO HAVE A METERED MULE TAPE PULL CORD INSTALLED. '' , kQ/ .�p �i <br /> t. 0IKIVS 44' <br /> CONDUCTOR COLOR CODE SSK>NALk"V <br /> EL --'^AL CGP' <br /> SYSTEM CONDUCTOR COLOR <br /> is Hte (17/1'R(LU24 <br /> A PHASE BLACK <br /> B PHASE RED APWA UNIFORM COLOR CODE: O7IO'I�OZZ <br /> 120240V.10 NEUTRAL WHITE <br /> 111 <br /> GROUND GREEN } <br /> A PHASE BLACK WHITE PROPOSED EXCAVATION J < <br /> B PHASE RED PINK I TEMPORARY SURVEY MARKINGS a -j N O <br /> 120208V.30 C PHASE BLUE ELECTRIC POWER LINES.CABLES, Q 00 <br /> NEUTRAL WHITE RED I CONDUIT,AND LIGHTING CABLES -Q ..IGROUND GREEN YED_GW GAS,OIL STEAM,PETROLEUM.OR1 <br /> Q <br /> A PHASE BROWN GASEOUS MATERIALS <br /> 0 <br /> B PHASE ORANGE OR PURPLE COMMU ORANGE I CABLES,OR CONDUITL AND TRAFFRM OR NC LOOPS AL LINES, WN W W N <br /> 277/480V.30 C PHASE YELLOW Ld� L Lu - <br /> NEUTRAL GREY . .. POTABLE WATER W <br /> 11J <br /> III <br /> GROUND POS`o) RED-GREEN PURPLE I RECLAIMEDSLURRYLINES WATER,IRRIGATION,AND lU 0 <br /> U.I o <br /> DC VOLTAGE W <br /> NEC(-) BLACK•• <br /> •SEE NEC 210.5(C)(1)AND(2) <br /> I GREEN SEWERS AND DRAIN LINES <br /> •'°POLARITY MARKED AT TERMINATION L <br /> ABBREVIATIONS: <br /> ISSUED FOR: <br /> ANT ANTENNA <br /> (E) EXISTING REVIEW 01/0422 <br /> FIF FACILITY INTERFACE FRAME -- <br /> GEN GENERATOR PERMIT - <br /> A GPS GLOBAL POSITIONING SYSTEM <br /> GSM GLOBAL SYSTEM FOR MOBILE CONSTRUCTION <br /> LTE LONG TERM EVOLUTION <br /> MGB MASTER GROUND BAR RECORD - <br /> MW MICROWAVE <br /> (N) NEW <br /> NEC NATIONAL ELECTRIC CODE "- - <br /> (F) PROPOSED PROJECTMINAGER - '�-S <br /> PP POWER PLANT CB I D 50 <br /> OTY QUANTITY _ _ I <br /> RECT RECTIFIER i'_"�' <br /> RBS RADIO BASE STATION •r.:.�"_-N: p fig.• I'�i T�}�. GPO JOB NO. <br /> RET REMOTE ELECTRIC TILT u't - 5 '.✓I p <br /> RFDS RADIO FREQUENCY DATA SHEET <br /> RRH REMOTE RADIO HEAD I 2021723.06.44617.01 <br /> RRU REMOTE RADIO UNIT iy. e sr'+ F oR PERMIT <br /> SIAD SMART INTEGRATED DEVICE 1-i "• �v <br /> TMA TOWER MOUNTED AMPLIFIER <br /> TYP TYPICAL <br /> UMTS UNIVERSAL MOBILE TELECOMMUNICATIONS SYSTEM N -2 <br /> W.P. WORK POINT <br />