Laserfiche WebLink
Permit#: K2211-007 <br /> Site Address: 1422 112TH ST SW <br /> TYPE 1 - Kitchen Hoods Owner: SEATTLE VISION CHURCH <br /> Tenant: SEATTLE VISION CHURCH <br /> 1 Hoods - 10' in Length App. Date: 11/23/2022 <br /> Proposed Use: COMMERCIAL <br /> 6 TOTAL FLOWS 16 NOZZLES Description: CHEMICAL- INSTALL RANGE GUARD/KIDDE <br /> 21"W x 10"D —I FIRE SUPPRESSION SYSTEM <br /> KIDDE RangeGuard <br /> 2.5 Gallon System Reviewed By �� <br /> (8 Flow Capacity) ADP ADP `' Office Set Job Site Set Fire;Planning Set <br /> rC, U. , <br /> (360°) (360°) I e <br /> iI 2 3 U 0 <br /> L0110--ADP <br /> , I 10'H OD i <br /> � <br /> DEC 01 20 <br /> r, <br /> ,,, <br /> RenidGde '�-' '"CITY OF EVI TT <br /> *6"Min. *6"Min. Permit Servl'.. <br /> Overhang to Overhang to <br /> �'.EwP°" -n.) Cooking Cooking <br /> /uy Equipment. ® Equipment. <br /> R R ADP <br /> 13-48"from nozzle to <br /> 20-42"from nozzle to cooking surface(ADP) <br /> (.6 <br /> cooking surface(R) <br /> PULL � 1 <br /> STATION Amp =`� <br /> (10-20ft 4 — —_�— <br /> from hood) <br /> ` ��+ <br /> I <br /> [located in ` -_�• _ �' <br /> path of egress] <br /> • <br /> Kidde ®®e ®® <br /> Fire Systemk.„. 3 0 3D <br /> 2.5 Gal.Tank <br /> (6 flows) , G 1 c, <br /> wigII <br /> GAS VALVE / <br /> 1 • <br /> = <br /> �.... U U U U <br /> u <br /> Steam Kettle 4 Burner Range Griddle <br /> (24"W x 24"D) (24"W x 24"D) <br /> DRAWN BY: Holly Gualco SEATTLE \II S I O N CHURCH GENERAL NOTES: INITIALS REVISION DATE A L E XA N D E R G O W �, <br /> Y HG Issued For Construction 11/15/22 <br /> 1. 318"pipe used in all distribution piping. FIRE EQUIPMENT CO. <br /> CHECKED BY: Darin Wa i 2. Fire Suppression System to be tied into - n <br /> PLOT DATE: ii/15/22 1422 112TH STREET SW building fire alarm(if applicable). 1436 NW 53RD STREET //\ <br /> EVE RETT WA 98204 3.8 MAX flow points per 2.5 gallon cylinder. SEATTLE, WA 9 8 1 0 7 <br /> 4.Upon activation of fire suppression system, P H : (2 0 6) 6 3 2 2 81 0 <br /> F all gas or electrical power supply under the -t. <br /> SHEET hood will shut down. F X. (2 0 6) 6 3 3-0 4 3 4 SW <br /> SHEET NUMBER: Fire Suppression System Schematic - <br />