ter... <br /> Architects and Engineers Specifications <br /> The notification appliances shall be Wheelock®ExcederTM Series HS Audible Strobe appliances, Series ST Visual Strobe appliances <br /> and Series HN Audible appliances or approved equals.The Series HS and ST Strobes shall be listed for UL Standard 1971 (Emergency <br /> Devices for the Hearing-Impaired)for Indoor Fire Protection Service. The Series HS and HN Audibles shall be UL Listed under Standard <br /> 464 (Fire Protective Signaling). All Series shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with <br /> standard reverse polarity supervision of circuit wiring by a Fire Alarm Control Panel(FACP)with the ability to operate from 8 to 33 VDC. <br /> Indoor wall models shall incorporate voltage test points for easy voltage inspection. <br /> The Series HS Audible Strobe and ST Strobe appliances shall produce a flash rate of one (1)flash per second over the Regulated <br /> Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan®lens.The Series shall be of low current design. <br /> Where Multi-Candela appliances are specified, the strobe intensity shall have 8 field selectable settings at 15, 15/75, 30, 75, 95, 110, <br /> 135, 185 candela for wall mount and 15, 30, 60, 75, 95, 115, 150, 177 candela for ceiling mount. The selector switch for selecting <br /> the candela shall be tamper resistant. The 15/75 candela strobe shall be specified when 15 candela UL Standard 1971 Listing with <br /> 75 candela on-axis is required (e.g.ADA compliance). Appliances with candela settings shall show the candela selection in a visible <br /> location at all times when installed. <br /> The audible shall have a minimum of three(3)field selectable settings for dBA levels and shall have a choice of continuous or temporal <br /> (Code 3)audible outputs. <br /> The Series HS Audible Strobe,ST Strobe and Series HN Audible shall incorporate a patented Universal Mounting Base that shall allow <br /> mounting to a single-gang, double-gang, 4-inch square, 3.5-inch octal, 4-inch octal or 100mm European type back boxes. Two wire <br /> appliance wiring shall be capable of directly connecting to the mounting base. Continuity checking of the entire NAC circuit prior to <br /> attaching any notification appliances shall be allowed. Product shall come with Contact Cover to protect contact springs. Removal of <br /> an appliance shall result in a supervision fault condition by the Fire Alarm Control Panel(FACP). The mounting base shall be the same <br /> base among all horn, strobe, horn strobe,wall and ceiling models. All notification appliances shall be backwards compatible. <br /> The Series HS and ST wall models shall have a low profile measuring 5.24"H x 4.58"W x 2.19"D. Series HN wall shall measure 5.24" <br /> H x 4.58"W x 1.6" D. The Series HSC and STC shall been round and have a low profile with a diameter of 6.68"x 2.63" D. Series <br /> HNC ceiling shall have a diameter of 6.68"x 1.50" D. <br /> When synchronization is required,the appliance shall be compatible with Wheelock®'s DSM Sync Modules,Wheelock®Power Supplies <br /> or other manufacturer's panels with built-in Wheelock®Patented Sync Protocol.The strobes shall not drift out of synchronization at any <br /> time during operation. If the sync protocol fails to operate,the strobe shall revert to a non-synchronized flash-rate and still maintain(1) <br /> flash per second over its Regulated Voltage Range.The appliance shall also be designed so that the audible signal may be silenced <br /> while maintaining strobe activation when used with Wheelock®synchronization protocol. <br /> Wall Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal(CSFM), ULC, FM, RoHS <br /> Ceiling Appliances—UL Standard 1971, UL Standard 464, California State Fire Marshal (CSFM), ULC, FM, RoHS <br /> NEM <br /> Member <br /> . WE ENCOURAGE AND SUPPORT NICET CERTIFICATION <br /> 3 YEAR WARRANTY <br /> . Exceder- Spec Sheet 5/13 <br /> NJ Location <br /> 273 Branchport Ave. <br /> Long Branch, NJ 07740 <br /> P:800-631-2148 <br /> F:732-222-8707 <br /> www.coopernotification.com <br /> 101.1 <br /> Cooper Notification is Wheelock°(MEDC) SAFEPATHn WAVES, COOPER Notification <br />