<br /> Sheet Number Sheet Title
<br /> E0.00 LEGENDS, SCHEDULES&NOTES
<br /> E3.01 POWER
<br /> E3.02 LOW VOLTAGE
<br /> E5.00 PANEL SCHEDULES
<br /> E6.00 ONE LINE p�
<br /> =ono
<br /> SCOPE OF WORK
<br /> REFITTING OF EXISTING INDUSTRIAL/FACTORY SPACE WITH ADDITIONAL PANEL BOARDS AND
<br /> TRANSFORMERS CONNECTED TO EXISTING 800A HOUSE PANEL. INSTALL PROVISIONS FOR
<br /> ELECTRICAL & DATA DROPS AT EQUIPMENT LOCATIONS.
<br /> RECEPTACLE SCHEDULE
<br /> SYMBOL DESCRIPTION CITY. co
<br /> ® RECEPTACLE-DUPLEX- 21 W o
<br /> DROP FROM 24'CEILINGJ
<br /> RECEPTACLE-QUAD 28 U
<br /> WALL MOUNT
<br /> ® RECEPTACLE-QUAD- 37
<br /> DROP FROM 24'CEILING
<br /> ® L15-3P 1 I.J_I
<br /> RECEPTACLE-DROP 3 U 11
<br /> FROM 24'CEILING-208V I.J_I
<br /> 3P Cr
<br /> ❑ RECEPTACLE-DROP 7
<br /> ® FROM 24'CEILING-
<br /> 480V 3P
<br /> TELE DATA DEVICE SCHEDULE
<br /> SYM DESCRIPTION WIRING CITY.
<br /> ❑ DATA-DROP FROM 24'CEILING CAT5K,W/RJ45 22 c
<br /> L
<br /> O
<br /> J
<br /> w
<br /> H
<br /> 120&208V EQUIP EQUIPMENT SCHEDULE 120&208V EQUIP EQUIPMENT SCHEDULE(CONY.) 277/480V EQUIP EQUIPMENT SCHEDULE
<br /> CALLOUT SYMBOL VOLTS AMPS KVA HP CIRCUIT CALLOUT SYMBOL VOLTS AMPS NVA HE CIRCUIT CALLOUT SYMBOL VOLTS AMPS KVA CIRCUIT
<br /> 1-CUSTOM 209V 2P 2W 41.54 8.64 LE.2D-3,5 17-DAYTON 208V 3P 3W 11.04 3.98 LE.2A-22,24,26 10-YAMAZAKI �.� 480V 3P 3W 95.84 79.68 LE.4C-7,9,1E
<br /> GRINDER GRINDER ❑ MAZAK 5800
<br /> 2-FSCURTIS 240V 3P 3W 80 33.26 30 HP LE.2C-2,4,6 18-CAUSING 208V 3P 3W 18.43 6.64 LE.2D-32,34,36 12-YAMAZAKI 480V 3P 3W 79.87 66.4 HP2
<br /> 3-ZEKS IS) 120V 1P 2W 8.72 1.05 LE.2D-1 MANUAL MILL ❑® MAZAK NEXUS 2 (E)-19,21,23
<br /> 4-DOALL 208V 3P 3W 13.02 4.69 LE.2D-20,22,24 TANK ENSOLV �.� 208V 3P 3W 67.16 24.2 LE.2A-9,11,13 MCKEEADDISON �.� 480V 3P 3W 23.96 19,92 LEAA-7,9,11
<br /> 5-DRILL 208V 3P 3W 18.43 6.64 LE.2D-13,15,17 23- 208V 3P 3W 26.51 9.55 LE.2A-4,6,8 21 -LEONARD 480V 3P 3W 34.94 29.05 LE.4A-14,16,18
<br /> MANUBEND (ENGLISH)
<br /> 6- 208V 2P 2W 18.08 3.76 LE.2D-4,6
<br /> CONCENTRIC ® 25- 208V 3P 3W 26.5E 9.55 LE2A-10,12,14 22-HERBER �.� 380V 3P 4W 37.98 25 T22- z
<br /> MANUBEND 22-HERBER-1 I11
<br /> 7-CLAUSING 208V 3P 3W 9.39 3.38 LE.2D-14,16"8 26- 120V 1P 2W 8 0.96 LE.2A-2 W
<br /> DRILL PRESSURE ® 24-LEONARD �� 480V 3P 3W 30.07 25 LE.4A-8110,12 C
<br /> 8-LATHE 208V 3P 3W 10.44 3.76 LE.2D-26,28,30 TESTER WASHER 32-BLM 480V 3P 3W 34.94 29.05 LE.4C-13,15,17
<br /> 27- 120V iP 2W 8 0.96 LE.2A-1 SMART BENDER
<br /> 9-BALDOR ❑ 120V 1P 2W 9.8 1.18 1/2 HP LE2D-2 PRESSURE TEST (I W 0
<br /> GRINDER ® OIL IrJn
<br /> 11 -EAST 208V 3P 3W 23.05 8.3 LE.2C-20,22,24 28-TORIT ® 208V 3P 3W 27.06 9.75 LE.2D-7,9,11 w
<br /> CRANE DRY FLOW 1
<br /> 13- 208V 3P 3W 122.46 44.12 LE.2C-8,10,12 29-WEST 208V 3P 3W 18.43 6.64 LE.2A-3,5,7 J
<br /> MATSUURA CRANE ❑® (< w z
<br /> 208V 20AC3P ® 208V 3P 3W 15.99 5.76 LE.2B-1,3,5 31- 208V 3P 3W 26.51 9.55 LE.2A-16,18,20 v N
<br /> MANUBEND
<br /> z in co
<br /> 14H-MISC 208V 3P 3W 15.99 5.76 LE.2B-7,9,11 33-ACCUREX ® 120V 1P 2W 16 1.92 LE.2A-28 LL,� Q)
<br /> 208V 20A 3P ® TUBEINSPECT
<br /> 141-MISC 208V 3P 3W 15.99 5.76 LE.2B-13,15,17 34-3CP 208V 3P 3W 7.85 2.83 2 HP LE.2B-14,16,18 Q
<br /> 208V 20A 3P ® PARKER DEBURR �/
<br /> P018V MISC
<br /> 3P ® 208V 3P 3W 23.98 8.64 LE.2B-2,4,6 35-HEAT 208V 2P 2W 24 4.99 LE.2C-7,9 /y Q
<br /> SHRINK LL
<br /> 2 �
<br /> 14,1-MISC ® 208V 3P 3W 23.98 8.64 LE.2B-8,10,12 36- 120V 1P 2W 16 1.92 LE.2B-20 W
<br /> 208V 30A 3P HORIZONTAL ® ❑ w
<br /> 15-BALDOR 208V 3P 3W 8.33 3 LE.2A-15,17,19 BANDSAW ``� ❑
<br /> 16-HEXAGON 208V 3P 3W 13.81 4.97 LE.2C-14,16,18
<br /> _j w
<br /> POWER AND LIOHTING M OUNTNG HEIGHTS SERVICE AND POWER DISTRIBUTION EOUPMEHT REFERENCE TAC38 RACEWAYS/WFWO GENERAL NOTES
<br /> VERIFY ALL MOUNTING HEIGHTS PRIOR TO INSTALLATION. O SERVICE SAITCHBJARD ❑T TRANSFORMER Imo,3DAF5 FUSIBLE DISCONNECT-30A,3-POLE W ❑1 KEY NOTE HP_I CONDOR OR CABLE CONCEALED IN CEIUNG OR WALL
<br /> R M: HEIGHT ABOVE ER15H FLOOR: yJ•254E / 1.ELECTRICAL INSTALLATION SHALL COMPLY WITH THE 2018 WAC 296-460,THE 2018 PROTECRON PER THE INTERNATIONAL BUILDING CODE.
<br /> DISTRIBUTION PANEL MOTOR OR EQUIPMENT POINT 3P 264-ERN VISE AND NEM4 TYPE 1HP,208/120V2P3W
<br /> THERMOSTATS 47 12"TO HIGHEST OPERABLE PPM,W. - -CONDOR OR CABLE ON EMERGENCY BRANCH IBC W/LOCAL AMENDMENTS,THE 2020 NFPA 72&THE 2020 NEC. Q
<br /> ® DU CONNECTION N1 DETAIL NUMBER/SHEET 5.ONE HOUR ARE RATED PROTECTION FOR LIGHTING FEATURES SHALL BE PROVIDED PER
<br /> WALL MOUNTED STAIR DGHTS 78°TO CENTER LINE U.O.N. E1.W MECHANICAL EQUIPMENT THE INTERNATIONAL BUILDING CODE. Z
<br /> MOTOR CONTROL CENTER-
<br /> WALL LIGHTS IN CORRIDOR VERIFY WITH OWNER � I--F,30/3 NON-FUSED DISCONNECT-30A-3 POLE DRAWING NUMBER - CONDOR OR CABLE CONCEALED UNDERFLOOR OR BELOW GRADE 2.USE 1HE NATIONAL ELECIRICA CONTRACi0R5 ASSOCMTION(NEGA)"STANDARD OF
<br /> "MCC" 6 6"x 6"DISTRIBUTION OENCE u' INSTALLATION"AS A GUIDE i0 THE WORKMANSHIP REQUIRED.
<br /> EXTERIOR WALL UGHTS VERIFY WITH OWNER A-1,3 6,ALL DIMENSIONS ARE TO CENTER OF BOX(U O.N.) Q
<br /> 30.4F5 ENCLOSED CIRCUIT BREAKER-3O AMP FRAME- SHEET NOTE/SHEET TYPICAL HOME RUN i0 PANEL-"A°CIRCUITS I k 3
<br /> OUTLETS SUITE PROS 47 I 2"TO HIGHEST OPERABLE PPM,W. BRANCH CIRf1Jli PANEL- °O' FAIR OR MOTOR DRAWING NUMBER 3.EXAMINE THE PEWS AND N THE PLAN WORK TO AVOID CONDUCTS,ERRORS AND
<br /> FLUSH MOUNTED 0 SCAT 30 AMP TRIP E1.W DEMYS.WIRING SHOWN ON THE PLANS IS DIAGRAMMATIC ONLY,AND IS MEANT i0 7.ALL CONDOR,ETC.PENETRATIONS THROUGH THE BUILDING SHALL BE ARE/SMOKE
<br /> COUNTER OUTLETS COORDIN4IE WITH CABINET DETAILS / y TICKS INDICATE NUMBER OF f l2 WIRES,LINE WITH DOT W
<br /> EIGHT SWITCH 47 12"TO HIGHEST OPERABLE PART,MAX. O MAGNETIC MOTOR STARTER.NUMBER INDICATES SIZE INDICATES GROUND WIRE,2�12 WIRES AND GROUND U.O.N. SHOW CIRCUITING AND SWITCHING DETAILS.LOCATIONS OF UGHTING NATURE.OXIMA STOPPED,PER THE RY,WITH
<br /> EDITION OF THE UNDERWRITER'S LABORATORIES ARE W
<br /> TERMINAL BOARD/GASNET- ®1 EQUIPMENT AND ELECTRICAL OUTLETS SHOWN ON THE PLANS ARE APPROXIMATELY STOPS.
<br /> DIRECTORY,WITH HOURLY RATINGS FOR THROUGH-PENETRATION ARE
<br /> ELECTRICAL PANELS AND ENCLOSURES 72°TOP OF PANEL(U.O.N.) SURFACE MOUNTED EQUIPMENT CONNECTION OR CONTROL DEVICE HEATERS CORRECT;HOWEVER,CHECK THE LOCATIONS BY TAKING MEASUREMENTS ON THE JOB. STOPS. O J
<br /> CONDUN OR CABLE STUB TO ACCESSIBLE SPACE
<br /> EXCEPT IN A0A ARIAS REFERENCE i0 AACHITECNRAL ELEVATIONS AND DETAILS.
<br /> LIGHTING FD(TURES GENERAL SYMBOL DETAILS WH-1 WALL HEATER ®BASEBOARD HEATER 8.PC CTONAL TESTS OF ALL AIROMAIIC LIGHTING CONTROLS SHALL BE PREFORMED BY
<br /> VERTICAL RUN-UP 4.PROVIDE APPROVED ARE STOPPING AT ALL PENETRATIONS REQUIRING FIRE THE LIGHTING CONTROLS MANUFACTURES REPRESENTATIVE. z
<br /> 1.OKVA208/12W2P3W 0 THERMOSTAT
<br /> (F-)INDICATES ES LIRE TYPE.SEE TEXTURE SCHEDULE(TYP). 0 SHADING INDICATES EMERGENCY SYSTEM CONNECTION VERTICAL RUN-GOWN
<br /> ()F- NUMBER INDICATES CIRCW NUMBER(TYPO. (TYPICAL ALL FIXTURES) EUH-1 UTIUD'HEATER DEFEfiRED APPROVAL W
<br /> 1^ 10KV0.208/120V2P3W RESIDENTIAL UNIT �F VAPOR SEAL I LOWER CASE LETTER INDICATES SCORCH CONTROL(1YP). WALL MOUNTED FAN _
<br /> �I DIAGONALLY SHADING INDICATES BATTERY BACKUP FORCED HEATER
<br /> (TYPICAL ALL FEATURES) DEVICES APPEARING IN THIS LEGEND MAY NOT ALL BE USED IN THIS DESIGN. Ln
<br /> C]
<br /> GENERAL ABBREVIATIONS
<br /> N
<br /> ZAMP AMPERE ATS AUTOMATIC TRANSFER SMTGI ODM COMMUNICATIONS DWG DRAWING FOP FlRE AWM CONTROL PANEL SAO GALVANIC D RIGID CONYJB IN INCH/INCTES(, L-N UNE TO NEUTRAL WE MAIN SWITCHBOARD N0. NUMBER() PF POWER FACTOR 18 RECEPTACLE PANELB]WI BASE SMTCTB]WD LAGS MARC NO SECONDARY z
<br /> f5 ACORNS
<br /> WINDING DISPLAY SYSTEM AUTO AIROMAPC CP COPDTtOL PANEL (E) IXISDNG F.BO Fl.RNSHFD BY OTHERS GND GROUND U JB J W00% LTG UGMINC L/EC EMPTY OCNDW N6 IN TO RII/P PHASE SCE SIGNAL CIRCUIT DRAWER EASY SWITCHAEAR UGT UNCFRGRWND 1FIEPHCNE O Z N
<br /> AC AIERNATING CURFSM AUX AUMI CT CURRENT TRANSFORMER EC ELECTRICAL CONTRACTOR F.1.B.0.FURNISIEID AND INSTALLED BY OTHER HH HAD TOTE K KEY LOCK LV LOW VOLTAGE WED MCA N/A NOT APPIJ US PALL PANEL SOH SCHEDULE SrM SYMLEERKAL UL UNDERWRITER'S LAB RATORY _
<br /> ACT ACOUSTICAL CEILING RE AWG AMERICAN WERE SAM CU COPPER EG EQUIPMENT GROUND PC FOOT CAN HDA HAND-OFF AUTOMATC KCMIL 1000 CIRCULAR ME MAX MAXIMUM MG MOUNTING W ON CENTER P.O.C. UTIUIY POINT OF CONNECTOR SOL SEWND4RY DAY EIGHT ZONE SON SCUD 409WLL VON UNLESS OIFERMSE NDTm L W W
<br /> A/C AIR CONEITIQYFR BD BOWD (Dl DEMO ELEC ELECTRIC,ELECTRICA FOR FOE HP HONE R,WER KV KILQvULT MCA MINMJM CIRCUIT AMPAC TY ME MMYNL TMNSER SWITCH
<br /> OCPD ONERCURRENT PROTECTION ONCE PM PMMA�A' DEC SE�^INiFY TO T119 IORE TERANAL BOAR UPS UNIMERRUPTIBIE A WAR SUABLY r - I�
<br /> PF AMPERE FAME(BRAERPATING) BKR RRFAKER OC DIRECT CURFEM EIR END OF UNE RESISTOR FIR EIM1R HFS HICK PRES7IFE SCDIUM KVA KILMOU AMPERE MCB MNN CIRCUIT BRFN(FR (N) NEW OFCI OWNER TURRETED CONTRACTOR INSTALLED PT PoTWORY TRANSFORMER Sf SOIUiRE FOOT iC PI£0.0q( UIP UNSHIDIIED 1MSlF➢PAR Q - U
<br /> ABC
<br /> ABOVE FlNISHED CWMFR BLllG BUIUMNG FELT PEDAL EMT ELECTRICAL METAWC TUBING M FULL LOAD AMK HR HOUR kW KILOWATT MCC MOTOR CONTROL CENTER N NEUIR4L OH "'N E D P! PHOIUDLTAC SFCB SUB FFfO CIRCUIT 9tFN(ER TELL 7ELFPHJFE V VOLT ` W
<br /> ALG ABOVE FlNISHED GRADE C CONDUIT DA DIAMETER ENCL ENCLOSURE EQUIP EQUIPMENT FLIX FLEXIBLE HI HEM BAN KILOWATT HOLR MM MAN OSIRIBJIIW FRAME WC NOIIFlCATION AaPIWNE gPOUIT OHEI WERHFAD ELECTRICAL TELEPHONE PVD PoLYv1Nd CHLORIDE SLC SIGNALING UNE CIRCUIT TE11YM TBE07M,MNIGTIONS VA VOLT-AMPERE
<br /> ARE PBGVE FlNIGUA BOOR GAB CABINET DISC DISCONNECT EPM ELEVATOR POWER MCWE FLUOR
<br /> ROOFESCEM HIR WATER
<br /> N UCRMIFD ARRESTOR MDP MAN gSIPoBZW PANEL NC NOMlA1LY 0.0SE0 O°P OPPGSITE POUR POKER SITE STRUCTURED AEON EN0.C6UTE 7P iAIPER%DOF STD VARNBLE FFEWENCf gEVE J Z
<br /> AFU AUMORBY HAWNG JURY CB CIRCUIT DREIER RISE DISTRIBI EV ELECTRIC VEHICLE F010 REMERTIED BY OWNER INSTALLED BY OWNER WAC H APING VENTILATION AND AR NNDMONING UW LOCAL AREA NE WYfK MECH MY
<br /> NEC NATIONAL BECTRICAL ALOE W OCCUPANCY SENSOR M QUANTITY SPKR SPEAKER N IEFASICN VP VAPOR PROOF W '^
<br /> ABU AIR BACONS UNIT CAN CASE TDD90N DN OMSION SAC ELECTRIC WATER COOLER A FODI/FEF I') HZ HERTZ LC LOAD CENTER MEN MAN NO NU A NATO ELECTRICAL MARS
<br /> ASSDOATON P HMf R RELOCATE AS SHOWN SPEC SPECIHCAPONI T1P MICA W OFF OR WIRE
<br /> NC AMPERE INTERIM NO CAPACITY CCTV CLOSED CIRCUIT TV ION DOWN SAN ELECTRIC WATER HEATER GO GENERAL CORE IOR IBC IMERKATICNAL BUILDING CODE LEP LIGHTING CONTROL PANEL MH MAN HOLE HE NON FUSIBLE PA PLBUC ADDRESS NEC RECEPTACLE SPDT SINCIE POE DOUBLE MAR4 T/XFM2 7RANSFOT4At W/ W71H M� SCARE 1 $ = 1 -O
<br /> 11
<br /> ALT AlERN41E CD CANDELA DP DISIRIBOON PANE IXP IXPLOSION PFUOF CEC CLDUHLNG EECTFOOE CONDUCTOR II INTERMEDIATE gSIRIBUTIW FRAME U UNAL FOOT MIN WIN NIC NOT IN CCNEW PB PUL BO% FF RADIO FREQUENCY SPOT SINGLE POE SINGE THROW OF LNOERFLODR W/O VNTRy,TE LLL
<br /> ARCH ARCHITECT (ARC CIRCUIT SPOT DOUBLE POLE DOUBLE THROW F FUSE GEN GENERATOR TES ILLUMINATING ENGINEERING SOCIETY UP UpRING PAWL MFC MISCELLANEOUS HT NIGHT UGHT ADD POWER DISTRIBUTION BOARD AEC RIGID STFFL WHEAT ST SHUNT TRIP DU WOERCROAJD YN RTATHIA I'POQ� m DATE 3/1/24
<br /> AT AMPERE TRIP CLG CEIUNG OAST DOUBLE POE SINGE THROW FA ARE ALARM
<br /> CA GROUND FAULT INTERRUPTER D IS(MAIED GROUND L-L ONE TO ENE MLO MAN LUGS ONLY ND NORMALLY OPEN PDL PRIMARY MY UNIT ZONE AA RUM'ING LOAD AMPS STU STANDARD ONE UNDERGROUND ELECTRIC
<br /> CO CONVENIENCE WIPER OR CAREEN MCNDXIDE TAN DIGITAL VIDEO RECORDER FAA ARE ALARM ANNUNCIATOR PANEL GFCI GROUND FAULT PROTECTION INC INTERMEDIATE METAL CONDUIT L-G UM TO GROUND MOCP MAXIMUM OVER COMM PROTECTION HE PHOTOELECTRIC SCOTCH RILL BOOM S4 9WTCH JOE UNDERGROUND PRIMARY Q DRAWN D. BORBA
<br /> CHECKED
<br /> JOB NO,
<br /> SHEET
<br /> E0 . 00