K ENGINEERS INC.
<br /> 208 Third Street
<br /> SPECIFICATIONS: Lynden,WA. 98264
<br /> Bus. (360) 354-4757
<br /> FAX (360) 354-6794
<br /> 1. THE GENERAL,SUPPLEMENTARY AND OTHER CONDITIONS OF THE CONTRACT, 20. DEFINITIONS 25. WIRING
<br /> MODIFICATIONS TO THE GENERAL CONDITIONS,THE DRAWINGS,AND THE APPLICABLE _(n
<br /> PROVISIONS OF THE OTHER DIVISIONS AR HEREBY MADE A PART OF THIS DIVISION AND A. THE TERM"CONTRACTOR"USED THROUGHOUTTHESE SPECIFICATIONS AND ON A. ALL WIRING SHALL BE ENCLOSED WITHIN THE RACEWAY SYSTEM. N
<br /> ALL ITS SECTIONS. THE ELECTRICAL DRAWINGS SHALL BE UNDERSTOOD TO MEAN THE ELECTRICAL Z
<br /> TH
<br /> CONTRACTOR.ALL OTHER WORK SHALL BE CALLED OUT BY NAME. B. PROTECT"OPEN"CABLE WIRING FROM ROUGH AND/OR SHARP EDGES ONLEC7RIC>4L LEGEND �'
<br /> 2. E REQUIREMENTS OF THIS SECTION APPLY TO ALL ELECTRICAL WORK. SUPPORTS,STRUCTURAL MEMBERS,ETC.AS REQUIRED DURING INSTALLATION. Z U)
<br /> B. "FURNISH"MEANS TO SUPPLY AND DELIVER TO THE PROJECT,READY FOR
<br /> 3. COORDINATE ELECTRICAL WORK WITH RELATED WORK SHOWN AND SPECIFIED INSTALLATION AND IN OPERABLE CONDITION. C. WIRE AND CABLE SIZES INDICATED AND/OR SPECIFIED ARE MINIMUMS ONLY AND O L
<br /> ELSEWHERE. SHALL BE INCREASED AS REQUIRED DUE TO NEC,SYSTEM,LOAD, I.�
<br /> C. "INSTALL"MEANS TO INCORPORATE IN THE WORK FINAL POSITION,COMPLETE, VOLTAGE DROP,ETC.REQUIREMENTS. \ BRANCH CIRCUIT CONDUIT,CONCEALED(OR SIMILAR m Q
<br /> 4. WORK INCLUDED:THE CONTRACTOR SHALL PERFORM ALL THE WORK REQUIRED ANCHORED,CONNECTED,AND IN OPERABLE CONDITION. 5LA6HE6=NO,OF CIRCUIT CONDUCTORS WHERE APPLICABLE)
<br /> (INCLUDING THE FURNISHING OF ALL SUPERVISION,LABOR,SERVICES,TOOLS, D. BRANCH CIRCUIT&EQUIPMENT GROUND CABLES WITHIN A CONDUIT SYSTEM
<br /> MATERIALS AND EQUIPMENT AND THE PERFORMANCE OF ALL OPERATIONS AND D. "PROVIDE"MEANS FURNISH AND INSTALL. SHALL BE 1/C COPPER STRANDED,#12 AWG(UNLESS NOTED OTHERWISE),WITH HOMERN TO LOCATION NDICATED,CONCEALED(TYPICAL)
<br /> INCIDENTALS NECESSARY)FOR A COMPLETE,SAFE AND RELIABLE ELECTRICAL 600V TYPE X-iHW OR THHN/THWN INSULATION. ----- EXISTING CONDUIT WITH NEW CABLE
<br /> INSTALLATION,ADJUSTED,TESTED AND READY FOR OPERATION.THE ELECTRICAL WORK E. F.O.I.C.-FURNISHED BY OTHERS,INSTALLED BY CONTRACTOR.
<br /> (NEW AND MODIFICATION OF EXISTING)IS GENERALLY DESCRIBED AS FOLLOWS: E. CABLE SHALL BE UNROLLED FROM REELS,OR REMOVED FROM CARTONS,AND m JUNCTION BOX
<br /> INSTALLED IN A MANNER WHICH WILL PREVENT KINKING,CRUSHING OR EXCESSIVE
<br /> A. DEMOLITION. 21. DEMOLITION TENSION ON CONDUCTORS AND INSULATION.CABLE PULLING LUBRICANTS OF A ® PANELBOARD
<br /> B. GROUNDING. TYPE HAVING NO DAMAGING EFFECT ON THE INSULATION,SHALL BE USED TO
<br /> C. WIRING DEVICES AND SPECIAL PURPOSE RECEPTACLES. A. CONTRACTOR SHALL REMOVE EXISTING EQUIPMENT,FIXTURES,DEVICES,ETC.AS MINIMIZE PULLING STRESSES ON THE CABLE. EX EXISTING TO REMAIN
<br /> D. BRANCH CIRCUIT WIRING SYSTEM FOR LIGHTING,OUTLETS,EQUIPMENT,ETC. INDICATED IN THE WORK AREA AND ALL ASSOCIATED CONDUIT,BOXES, rzEx REPLACE EXISTING i727 Uakes Ave.
<br /> E. DISCONNECTING MEANS,SWITCHES,RECEPTACLES,MOTOR STARTERS,CONTROL CABLES,ETC.SHALL BE REMOVED TO THEIR POINT OF ORIGIN&/OR DESTINATION. F. CABLE SHALL BE INSTALLED OR DRAWN INTO THE CONDUIT SYSTEM ONLY AFTER Sdde 100
<br /> DEVICES,ETC.(INSTALLATION ONLY IF FURNISHED WITH EQUIPMENT),AND FINAL ALL WORK OF ANY NATURE THAT COULD CAUSE INJURY TO THE CABLE IS FML RELOCATE EXISTING Everett,WA 95201
<br /> POWER AND LINE VOLTAGE(120 VOLT OR GREATER)CONTROL CONNECTIONS TO B. UNLESS NOTED OTHERWISE,CONCEALED RACEWAYS ARE ALLOWED TO REMAIN, COMPLETED. THE CONDUIT SYSTEM SHALL BE COMPLETE,SNAKED AND CLEANED
<br /> EQUIPMENT AND DEVICES PROVIDED BY THE OWNER,GENERAL CONTRACTOR OR EXCEPT,WIRING SHALL BE REMOVED. EXISTING CONCEALED RACEWAYS ARE BEFORE PULLING ANY CABLE. GFI GROUND FAULT INTERRUPTING REVISIONS
<br /> OTHER SUB-CONTRACTORS. ALLOWED TO BE RE-USED IF IN GOOD CONDITION&SUITABLE FOR THE NEW
<br /> F. LINE VOLTAGE(120 VOLT OR HIGHER)CONTROL STATIONS,DEVICES,CONDUIT, INSTALLATION. 26. GROUNDING:
<br /> BOXES,WIRING,ETC.(INSTALLATION ONLY IF FURNISHED WITH IMAGING EQUIPMENT)
<br /> G. SUPPORTS. C. EXISTING FEEDERS,CIRCUITS,CONDUITS,CABLES,ETC.INTERRUPTED DUE TO THE A. ALL ELECTRICAL EQUIPMENT,BOXES,DEVICES,SHALL BE PROVIDED WITH A
<br /> H. TEMPORARY CONSTRUCTION POWER AND LIGHTING. SYSTEM UPGRADE SHALL BE RE-CONNECTED AS REQUIRED TO MAINTAIN THE GROUND FAULT RETURN PATH BY MEANS OF THE INTEGRITY OF THE METALLIC
<br /> 1. TESTING AND COMPLETING. ORIGINAL FUNCTION. CONDUIT SYSTEM(WHERE APPLICABLE)&AN INSULATED GROUNDING
<br /> J. OBTAINING AND PAYING FOR ALL REQUIRED LICENSES,PERMITS,INSPECTIONS AND FEES. CONDUCTOR INSTALLED WITH THE CIRCUIT CONDUCTORS.CONDUIT SHALL BE
<br /> D. ALL SURPLUS MATERIAL REMOVED DURING THE DEMOLITION SHALL BE INSPECTED CLOSELY&TIGHTLY FITTED IN COUPLINGS,CONNECTORS,ETC.AND BE PROPERLY
<br /> 5. BEFORE SUBMITTING BID,EXAMINE EXISTING BUILDING AND EQUIPMENT CONDITIONS TO BY THE OWNER,AND THOSE ITEMS SELECTED SHALL REMAIN THE PROPERTY OF BONDED TO PROVIDE AN ELECTRICALLY CONTINUOUS LOW RESISTANT GROUND
<br /> DETERMINE EFFECT ON EXECUTION OF THE ELECTRICAL WORK AND INCLUDE COSTS IN THE OWNER. ALL REMAINING SURPLUS MATERIALS SHALL BE REMOVED FROM THE PATH.CONTINUITY TESTS SHALL BE MADE TO VERIFY THE CONTINUITY OF THE
<br /> BID. SITE&DISPOSED OF BY THE CONTRACTOR ACCORDING TO ALL APPLICABLE GROUNDING SYSTEM&ALL GROUND FAULT RETURN PATHS.
<br /> REGULATIONS.
<br /> 6. EXISTING CIRCUITS INDICATED ON THE PLANS ARE BASED ON WHAT WAS SHOWN ON B. EQUIPMENT GROUND CABLES SHALL BE 1/C COPPER,WITH 600V TYPE XHHW OR TF R. DI
<br /> THE ORIGINAL CONSTRUCTION DRAWINGS AND MAN NOT BE EXACTLY HOW THE ACTUAL 22. RACEWAYS THHN/THWN INSULATION. 1P aF WA
<br /> CONSTRUCTION WAS DONE. THE CONTRACTOR SHOULD EXPECT THAT SOME AMOUNT OF G
<br /> CIRCUIT TRACING TO DETERMINE WHO THE ACTUAL CIRCUITS ARE INSTALLED WILL BE A. RACEWAYS SHALL BE OF THE TYPES LISTED BELOW,UNLESS NOTED OTHERWISE: 27. WIRING DEVICES 3 y
<br /> REQUIRED.
<br /> 1. ELECTRICAL METALLIC TUBING(EMT)-CONCEALED ABOVE GRADE AND EXPOSED IN A. WIRING DEVICES SHALL BE HOSPITAL GRADE,RED COLOR ON CRITICAL BRANCH AND L City of Everett Permit Review 44194 .�49
<br /> 7. THE CONTRACTOR SHALL COORDINATE THE WORK AND COOPERATE WITH THE OWNER, UTILITY ROOMS AND OTHER NON-PUBLIC AREAS NOT READILY VISIBLE TO BUILDING IVORY COLOR ON NORMAL BRANCH. o F
<br /> EVERETT Status:Approved as Noted ,ETA
<br /> OTHER TRADES,AND SYSTEM CONTRACTORS TO HAVE THE WORK COMPLETED TO THE OCCUPANTS. ""'"'"°'°" S`StoNAL ti�G
<br /> BEST ADVANTAGE,INSURE THERE ARE NO INTERFERENCES,PROVIDE REASONABLE B. GENERAL PURPOSE OUTLETS SHALL BE STRAIGHT BLADE,15 AMP,125 VOLT. 08/30/2024 3:24:1 1 PM
<br /> OPPORTUNITY FOR THE OTHER TRADES AND CONTACTORS TO COMPLETE THEIR WORK 2. FLEX-SHALL BE USED FOR FINAL CONNECTIONS TO VIBRATING EQUIPMENT&
<br /> AND TO NOT DELAY THE WORK. MAY BE SUBSTITUTED FOR EMT WHEN RUN CONCEALED WITHIN WALLS& C. GROUND FAULT INTERRUPTER(GFI)TYPE RECEPTACLES SHALL BE DUPLEX CLASS SUBJECT TO FIELD
<br /> CEILINGS WITHIN THE LIMITS OF NEC 517. A,15 AMP,125 VOLT. INSPECTION
<br /> 8. THE ELECTRICAL PLAN DRAWINGS ARE GENERAL IN FORM AND DO NOTATTEMPTTO SHOW
<br /> COMPLETE DETAILS OR LIST EVERY ITEM OF THE ELECTRICAL SYSTEMS,THE BUILDING 3. MC CABLE-MAY NOT BE USED,EXCEPT FOR FIXTURE WHIPS IN ACCESSIBLE D. FLUSH MOUNTED DEVICES SHALL HAVE SMOOTH STAINLESS STEEL WALLPLATES.
<br /> CONSTRUCTION OR THE VARIOUS EQUIPMENT(NEW OR EXISTING);HOWEVER,THE ROUTING CEILING SPACE.
<br /> OF RACEWAYS AND CIRCUITS,AND THE LOCATIONS OF EQUIPMENT,DEVICES,FIXTURES, F. ALL OUTLETS SHALL BE LABELED WITH THE PANEL AND CIRCUIT NUMBER(S)FROM
<br /> ETC.REPRESENT THE DESIRED FINISHED ARRANGEMENT;EXCEPT,AS GOVERNED BY WHICH HE DEVICE IS FED.LABELS SHALL BE HEAVY DUTY ADHESIVE TYPE,CLEAR
<br /> STRUCTURAL OR MECHANICAL CONDITIONS OR OBSTRUCTIONS. B. RACEWAYS AND CABLES THROUGHOUT THE FACILITY SHALL BE RUN CONCEALED IN WITH BLACK LETTERS ON LIGHT COLORED DEVICES AND CLEAR WITH WHITE
<br /> THE WALLS,ABOVE THE CEILING OR BELOW THE FLOOR WHERE POSSIBLE,EXCEPT, LETTERS ON DARK COLORED DEVICES.LETTERING SHALL BE 1/4"MINIMUM.
<br /> 9. CONTRACTOR SHALL COORDINATE WORK TO AVOID DISTURBANCE TO BUILDING EXPOSED WITHIN UTILITY&OTHER NON-PUBLIC SPACES. WITHIN PUBLIC SPACES, SELF-ADHESIVE CIRCUIT NUMBERS,MASKING TAPE,PLASTIC PUNCH TYPE"DYMO"
<br /> OPERATIONS AND PERSONNEL,AND TO ALLOW ACCESS FOR BOTH PERSON TO AND WHERE DUE TO THE BUILDINGS CONSTRUCTION,IT IS NOT POSSIBLE TO ROUTE LABELS,ETC.ARE NOT ACCEPTABLE.
<br /> WITHIN ALL PORTIONS OF THE FACILITY AND VEHICLES TO THE FACILITY.ACCESS TO RACEWAYS&CABLES CONCEALED,RACEWAYS MAY BE RUN EXPOSED WHEN
<br /> OFFICE SPACES,CLASSROOMS,ETC.WILL NOT BE ALLOWED WHEN THEY ARE OCCUPIED. APPROVED BY ARCHITECT. EXPOSED RACEWAYS SHALL BE RUN AS NEATLY&
<br /> ANY AND ALL COSTS INCURRED FO NON-STANDARD HOURS,DOUBLE SHIFTS,OVERTIME, UNOBTRUSIVELY AS POSSIBLE,SUPPORTED AS REQUIRED,PARALLEL OR AT RIGHT
<br /> ETC.OR ANY OTHER COSTS ASSOCIATED WITH COMPLETING THE PROJECT WITHIN THE ANGLES TO CEILINGS,WALLS&STRUCTURAL MEMBERS.
<br /> COMPLETION TIMES REQUIRED SHALL BE INCLUDED WITHOUT INCREASE IN CONTRACT
<br /> SUM. C. RACEWAYS SHALL BE SIZED SO THAT THE CABLE FILL DOES NOT EXCEED 40%,
<br /> EXCEPT,MINIMUM CONDUIT(&EQUIVALENT SURFACE METAL RACEWAY)SIZES
<br /> 10. THE COMPLETED INSTALLATION SHALL BE DONE IN A NEAT&WORKMANLIKE MANNER, SHALL BE AS FOLLOWS,UNLESS NOTED OTHERWISE.
<br /> SHALL BE SUITABLE FOR THE LOCATION,AND SHALL BE IN ACCORDANCE ALL LAWS,
<br /> RULES®ULATIONS IN EFFECTATTHE SITE(INCLUDING THE LATEST EDITIONS OF A. 3/4"-BRANCH CIRCUITS,EXCEPT AS NOTED OTHERWISE. O
<br /> THE NATIONAL ELECTRICAL CODE,THE WASHINGTON STATE RULES®ULATIONS
<br /> FOR INSTALLING ELECTRIC WIRES&EQUIPMENT,AND THE WASHINGTON STATE D. ELECTRICAL METALLIC TUBING SHALL BE ELECTRO-GALVANIZED STEEL.
<br /> ENERGY CODE). v
<br /> E. NO CONDUIT SHALL BEND MORE THAN 270 DEGREES BEFORE THE END OF ITS
<br /> 11. CONTRACTORS ARE RESPONSIBLE FOR DETERMINING THE FIRE RESISTIVE RATINGS RUN. BENDS IN CONDUITS SHALL BE MADE WITHOUT FLATTENING,KINKING OR
<br /> FOR WALLS,PARTITIONS AND OTHER BUILDING STRUCTURES. INSTALLATION OF REDUCING THE CROSS-SECTIONAL AREA OF THE CONDUIT. CONDUIT CUTS SHALL Al
<br /> NEW SYSTEM COMPONENTS MUST MAINTAIN THE EXISTING FIRE RESISTIVE BE MADE SQUARE WITH A PROPER CUTTING TOOL.THE INSIDE AND OUTSIDE OF YJ
<br /> RATING OF THE PENETRATED BUILDING ELEMENT. ALL CONDUIT ENDS SHALL BE REAMED TO ELIMINATE BURRS AND ROUGH EDGES, m T
<br /> THEN WIPED CLEAN. 7
<br /> 12. ALL SYSTEMS,EQUIPMENT,DEVICES,RACEWAYS,CABLES,ETC.INDICATED ARE L C N
<br /> NEW UNLESS NOTED OTHERWISE. F. SUITABLE BUSHINGS SHALL BE USED ON ALL CONDUIT TERMINATIONS. �\ mOD
<br /> > 0)
<br /> 13. ALL ELECTRICAL MATERIALS SHALL BE"UL"(UNDERWRITER'S LABORATORIES,INC.) G. CONDUIT SYSTEMS SHALL BE COMPLETE,SNAKED AND CLEANED BEFORE
<br /> LISTED,LABELED AND APPROVED FOR THE SERVICE INTENDED WHERE UL STANDARDS PULLING ANY CABLE.
<br /> HAVE BEEN ESTABLISHED. ALL ELECTRICAL MATERIAL SHALL BE NEW UNLESS 3
<br /> SPECIFICALLY NOTED OTHERWISE. 23. RACEWAY FITTINGS
<br /> .; �L O .r
<br /> 14. ALL OPERATIONS SHALL BE CONDUCTED IN A MANNER TO AVOID THE RISK OF HARM TO A. CONNECTORS,COUPLINGS,ETC.FOR EMT SHALL BE STEEL SET-SCREW TYPE, O A\ V
<br /> PERSONS OR DAMAGE TO PROPERTY.DAMAGE SHALL IMMEDIATELY BE REPAIRED. EXCEPT,STEEL RAINTIGHT COMPRESSION TYPE IN POTENTIALLY WET OR DAMP
<br /> CONSTRUCTION EQUIPMENT&TOOLS SHALL BE IN GOOD OPERATING CONDITION,AND LOCATIONS. L }s C4 m
<br /> BE DESIGNED FOR THE WORK REQUIRED.VERIFY WITH STRUCTURAL ENGINEER
<br /> ACCEPTABLE LOCATIONS FOR CORE DRILLING FLOORS,WALLS,ETC.FOR CONDUIT 24. BOXES V, T LLI
<br /> ROUTING.
<br /> A. BOXES SHALL ACCOMMODATE ANY DEVICES TO BE INSTALLED AND SHALL BE DRAWING INDEX
<br /> 15. POWER INTERRUPTIONS(WHETHER TO THE ENTIRE SYSTEM OR TO INDIVIDUAL SIZED AS REQUIRED BY THE APPLICABLE CODES FOR NUMBER AND SIZE OF
<br /> BUILDINGS,PANELS,EQUIPMENT,DEVICES,ETC.)SHALL BE KEPT TO AN ABSOLUTE CONDUITS AND CABLES ENTERING AND LEAVING;EXCEPT MINIMUM AS NOTED SHEET DRAWING TITLE 2297
<br /> MINIMUM,AND SHALL NOT BE DONE WITHOUT PRIOR APPROVAL,2 WEEKS BELOW.
<br /> ADVANCED SCHEDULING&COORDINATION MEETING WITH THE OWNER.SECONDARY EO.1 ELECTRICAL-SPECIFICATIONS,LEGEND&INDEX oenwH er KL
<br /> VERIFICATION THAT POWER INTERRUPTION WILL OCCUR IS ALSO REQUIRED 48 HOURS B. INDOOR BOXES ABOVE GRADE IN DRY LOCATIONS SHALL BE STANDARD STAMPED E2.1 ELECTRICAL-POWER PLAN&SCHEDULES
<br /> PRIOR TO THE DATE OF OCCURRENCE. GALVANIZED STEEL TYPE,SUITABLE FOR EMBEDMENT IN CONCRETE AND/OR E6.1 ELECTRICAL-POWER SYSTEM RISER DIAGRAM He«eo aY BD
<br /> MASONRY WHERE REQUIRED. E6.2 ELECTRICAL-POWER SYSTEM RISER DIAGRAM `
<br /> 16. CABLE,BOXES,ETC.SHALL BE STORED OFF THE GROUND,PROTECTED FROM THE E6.3 ELECTRICAL-POWER SYSTEM RISER DIAGRAM
<br /> WEATHER IN RACKS OR BINS,OR ON SHELVES.EQUIPMENT,WIRING DEVICES,CIRCUIT C. UNLESS NOTED OTHERWISE,LARGER SIZE PULL AND JUNCTION BOXES SHALL BE
<br /> BREAKERS,ETC.SHALL BE STORED INDOORS IN A DRY,WARM AREA;FREE OF DUST& FABRICATED FROM CODE GAUGE GALVANIZED STEEL. PERMIT SET
<br /> ONE IN WHICH CONDENSATION WILL NOT OCCUR.
<br /> D. SWITCH,OUTI_ET,DEVICE,ETC.BOXES SHALL BE SINGLE OR GANGED TO 5-29-24
<br /> 17. EQUIPMENT,BOXES,ETC.SHALL BE INSTALLED PLUMB&TRUE,AND BE FIRMLY ACCOMMODATE THE REQUIRED NUMBER OF DEVICES;EXCEPT,FLUSH MOUNTED
<br /> SUPPORTED EITHER DIRECTLY OR INDIRECTLY BY A SOUND&SAFE STRUCTURAL BOXES SHALL BE MINIMUM 4 INCHES SQUARE FOR CONDUITS 1 INCH OR LESS AND
<br /> MEMBER. 4-11/16 INCHES SQUARE FOR LARGER CONDUITS.BOXES CONTAINING A SINGLE ELECTRICAL -
<br /> DEVICE SHALL BE MINIMUM 1-1/2 INCHES DEEP.BOXES CONTAINING MULTIPLE SPECIFICATIONS
<br /> 18. ROUTING OF EXISTING CONDUITS INDICATED IS APPROXIMATE ONLY. DEVICES SHALL BE MINIMUM 2-1/8 INCHES DEEP.FLUSH MOUNTED BOXES SHALL
<br /> BE EQUIPPED WITH PLASTER RINGS AND SUITABLE WALLPLATES.SURFACE LEGEND &
<br /> 19. VERIFY ALL EQUIPMENT,DEVICE,ETC.LOCATIONS WITH THE OWNER PRIOR TO MOUNTED BOXES SHALL HAVE RAISED SURFACE TYPE COVERS.
<br /> ROUGH-IN. INDEX
<br /> E0.1