NW 1/4, SEC. 11 T.28 N, R.4 E, W.M.
<br />CITY OFEVERETT, WASHINGTON
<br />NOTES
<br />1. CONNECTION TO SEWER MAIN PER SEC. 7 OF
<br />STANDARD SPECIFICATIONS AND SPECIAL
<br />PROVISIONS AND STANDARD DRAWING 602.
<br />2. INSTALL 6" MINIMUM PIPE SIZE IN RIGHT OF
<br />5' MAXIMUM IF
<br />WAY'
<br />GREATER THAN 5'
<br />3. INSTALL 6" CLEAN OUT PER STANDARD.
<br />INSTALL ADDITIONAL
<br />DRAWING 604.
<br />CLEAN OUT REQUIRED
<br />CLEAN OUT AT
<br />AT ALL ANGLE POINTS
<br />BUILDING CONNECTION.
<br />OVER 45°
<br />4. PRIVATE SIDE SEWER PIPE DIAMETER:
<br />4" MINIMUM FOR SINGLE FAMILY
<br />6" MINIMUM FOR ALL OTHER USES.
<br />GENERAL NOTES
<br />1. SEE SECTION 7 OF STANDARD
<br />SPECIFICATIONS FOR ROADS; BRIDGE AND
<br />MUNICIPAL CONSTRUCTION WSDOT/APWA
<br />AND CITY SPECIAL PROVISIONS SECTION
<br />BUILDING
<br />7-18 FOR DETAILS AND REQUIREMENTS ON
<br />Q
<br />LATERALS.
<br />0
<br />2. ALL CLEAN OUT'S ON PRIVATE PROPERTY
<br />�I
<br />ARE TO BE ADJUSTED TO GRADE IF IN PAVED
<br />AREAS PER STANDARD DRAWING 604.
<br />3. CLEAN OUT'S ARE TO BE CONSTRUCTED
<br />WITH WYES OR SANITARY "T"S (SWEEPS).
<br />TYPICAL
<br />INSTALL
<br />STRAIGHT "T"S ARE NOT PERMITTED.
<br />CLEAN OUT
<br />AT BLDG.
<br />4. ALLOWABLE GRADES ARE 2% (1/4"/FT)
<br />ALTERNATES
<br />CONNECTION
<br />MINIMUM TO 100% (FT/FT) MAXIMUM.
<br />4
<br />5. SEWER MUST BE STRAIGHT BETWEEN
<br />ANGLE POINTS, CHANGES IN LINE OR
<br />3
<br />GRADE SHALL BE MADE WITH APPROVED
<br />FITTINGS.
<br />0
<br />PROPERTY
<br />o
<br />_
<br />LINE
<br />6. NORMALLY ONLY ONE(1) CONNECTION TO
<br />2
<br />THE SEWER MAIN PER BLDG. IS ALLOWED.
<br />3
<br />TWO (2) DIFFERENT LAYOUTS ARE SHOWN
<br />F
<br />1
<br />FOR ILLUSTRATIVE PURPOSES ONLY!
<br />z
<br />0
<br />w
<br />SEWER MAIN
<br />0
<br />u
<br />CITY OF EVERETT
<br />PUBLIC WORKS DEPARTMENT
<br />a
<br />N\
<br />Ciry Engineer 'DRi°n Manager CAD Manager Drawn By urre ev
<br />SASS DAVID VOIGT PAULWILHELM WRR 12/30/2016
<br />TITLE 12/30/2016
<br />STANDARD DRAWING Nn.
<br />Aao
<br />-�a
<br />TYPICAL SIDE SEWER LAYOUTS 601
<br />ri- TYPICAL SIDS' SEWER LAYOUTS
<br />SW2 N.T.S. (CITY OF EVERETT STD. 601)
<br />NOTES
<br />1. W = MAXIMUM WIDTH OF TRENCH. FOR PIPES 15"
<br />OR LESS IN DIA W=40". FOR PIPES 18" OR GREATER
<br />W=1.5 X I.D. + 18". PIPE MUST BE CENTERED IN
<br />TRENCH.
<br />2. ALTERNATE SLOPING TRENCH WALLTO MEET
<br />EXISTING 7
<br />6
<br />8 9 10
<br />O.S.H.A. REQUIREMENTS (NO SLOPES STEEPER THAN
<br />PAVEMENT
<br />1:1 EXCEPT FOR ROCK).
<br />6"
<br />18"MIN
<br />3. SUITABLE NATIVE MATERIAL OR IMPORTED GRAVEL
<br />BORROW AS DIRECTED. COMPACT TO 90%
<br />MAXIMUM DENSITY.
<br />r - I
<br />I
<br />4. FOUNDATION GRAVEL IF REQUIRED BY THE
<br />I LEI
<br />I- -I I -I I --I-
<br />ENGINEER TO REPLACE UNSUITABLE MATERIAL.
<br />I
<br />I -I I _III
<br />SHALL BE FOUNDATION MATERIAL CLASS A, B OR AS
<br />-
<br />-I
<br />APPROVED BY THE ENGINEER.
<br />� 1
<br />I
<br />I
<br />5. FOR ADDITIONAL COMPACTION INFORMATION SEE
<br />-I
<br />III
<br />I I/
<br />1
<br />STANDARD DWG 615.
<br />1
<br />I/
<br />ICI Y I
<br />2
<br />6. IF DIRECTED BY THE ENGINEER THE TOP THREE TO
<br />FIVE FEET OF BACKFILL SHALL BE IMPORTED GRAVEL
<br />2
<br />� I-
<br />BORROW OR SUITABLE NATIVE MATERIAL
<br />1
<br />COMPACTED TO 95% MAXIMUM DENSITY.
<br />-I
<br />7. SEE CITY OF EVERETT STANDARD DWG 326 FOR
<br />PAVEMENT PATCH DETAILS.
<br />8. VERTICAL TRENCH WALLS WITH SHORING TO
<br />III
<br />CONFORM TO O.S.H.A. REGULATIONS.
<br />8
<br />III-
<br />9. SUBGRADE OR GROUND SURFACE IN NON -PAVED
<br />AREAS.
<br />10. EXCAVATED NATIVE MATERIAL OR STOCKPILED
<br />BACKFILL MATERIAL.
<br />3
<br />3
<br />11. FOR ALL TRENCHING TRANSVERSE TO THE ROADWAY
<br />a
<br />w �
<br />BACKFILL ABOVE THE PIPE ZONE SHALL BE
<br />°
<br />Z 1O
<br />0
<br />CONTROLLED DENSITY FILL. SEE SECTION 3-9.6 &
<br />w
<br />3-20.1 OF THESE STANDARDS.
<br />3
<br />Z
<br />II
<br />a w
<br />a Ln
<br />if
<br />12. FOR UTILITY CUTS SUCH AS GAS, TELEPHONE,
<br />w
<br />POWER, AND CABLE TV LONGITUDINAL TO THE
<br />I I
<br />ROADWAY, BACKFILL SHALL BE CONTROLLED
<br />W
<br />-
<br />I
<br />DENSITY FILL. SEE SECTION 3-9.5 OF THESE
<br />=
<br />O
<br />-I
<br />I
<br />STANDARDS.
<br />a
<br />-
<br />Z
<br />CITY OF EVERETT
<br />_I-
<br />4
<br />PUBLIC WORKS DEPARTMENT
<br />W (SEE NOTE1)
<br />06CIT
<br />WO
<br />SASS DAVIDaVOIGT �APAUL WILHELM ESH
<br />tea.
<br />TITLERYAN
<br />06/23/2017
<br />STANDARD DRAWING No.
<br />E61
<br />TYPICAL TRENCH SECTION 614
<br />4 TYPICAL TRENCHSECTION
<br />�W2 N.T.S. (CITY OF EVERETT STD. 614)
<br />Know what's below.
<br />Call before you dig.
<br />UTILITY CONFLICT NOTE:•
<br />CAUTION -
<br />THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING THE LOCATION,
<br />DIMENSION, AND DEPTH OF ALL EXISTING UTILITIES WHETHER SHOWN ON THESE
<br />PLANS OR NOT, BY POTHOLING THE UTILITIES AND SURVEYING THE HORIZONTAL
<br />AND VERTICAL LOCATION PRIOR TO CONSTRUCTION. THIS AND THEN SHALL
<br />INCLUDE CALLING UTILITY LOCATE ® 1-800-424-5555 POTHOLING ALL OF THE
<br />EXISTING UTILITIES AT LOCATIONS OF NEW UTILITY CROSSINGS TO PHYSICALLY
<br />VERIFY WHETHER OR NOT CONFLICTS EXIST. LOCATIONS OF SAID UTILITIES AS
<br />SHOWN ON THESE PLANS ARE BASED UPON THE UNVERIFIED PUBLIC
<br />INFORMATION AND ARE SUBJECT TO VARIATION. IF CONFLICTS SHOULD OCCUR,
<br />THE CONTRACTOR SHALL CONSULT WITH INSIGHT ENGINEERING COMPANY TO
<br />RESOLVE ALL PROBLEMS PRIOR TO PROCEEDING WITH CONSTRUCTION.
<br />6" GASKETED NOTES
<br />6" GASKETED CAST IRON BOLTED RING & COVER SPIGOT CAP OR
<br />MECHANICAL 1. CLEAN -OUT PIPE AND FITTINGS SHALL BE PVC,
<br />TYPE 1 & 2 (SEE NOTE 5).
<br />SPIGOT CAP PLUG TYPE 1 & 2 ASTM D3034, SDR 35 OR AWWA C900.
<br />OR
<br />MECHANICAL 2. A SANITARY TEE MAY BE INSTALLED IN LIEU OF A
<br />PLUG WYE AS SHOWN. STRAIGHT TEES ARE NOT
<br />30" SQ
<br />TYPE 1 & 2 cr PROPERTY LINE LANDSCAPED OR ACCEPTABLE.
<br />UNPAVED SURFACE
<br />OR RIGHT-OF-WAY / 3. SEWER STUB WILL BE EXTENDED 10' BEYOND
<br />TYP
<br />PROPERTY LINE TO PREVENT DAMAGE TO
<br />PAVED SURFACE CLEAN OUTAND MINIMIZE CONFLICTS WITH OTHER
<br />UTILITIES WHEN SERVICE TO BUILDING IS
<br />°a INSTALLED.
<br />� A 4. TYPE 3 TEMPORARY INSTALLATIONS (NEW
<br />a DEVELOPMENT) SHALL HAVE A PRESSURE TREATED
<br />CONCRETE COLLAR SEE NOTES 2"X4" STUB MARKER THAT EXTENDS DOWN TO A
<br />(COMMERCIAL CONC) TYP. 6 AND 7 MIN OF 24" BELOW GROUND. A MIN OF 36" SHALL
<br />EXTEND ABOVE GROUND. STUB MARKER SHALL BE
<br />30" SQTYP. PAINTED WITH WHITE TRAFFIC PAINT. THE WORD
<br />SEE STANDARD 12" DIA PVC SLEEVE "SEWER" AND THE DEPTH IN FEET FROM GROUND
<br />DRAWING 602 TYP. TYPE 1 & 2 SEE STANDARD SURFACE TO SEWER STUB PIPE INVERT SHALL BE
<br />DRAWING 602 PAINTED ON THE MARKER WITH 3" HIGH BLACK
<br />SEAL ANNULAR SPACE PAINTED LETTERS.
<br />WITH FIBER JOINT
<br />TYPE 1 TYPE 2
<br />PACKING OR URETHANE 5. CAST IRON BOLTED RING AND COVER SHALL BE
<br />PAVED AREAS FOAM TYP. TYPE 1 & 2 UNPAVED AREAS EAST JORDAN IRON WORKS NO.3660CPT OR
<br />PERMANENT INSTALLATIONS EQUAL.
<br />cr 6. RING AND COVER INSTALLATION IS SHOWN FOR
<br />PAVED AND UNPAVED AREAS, FIELD CONDITIONS
<br />STUB MARKER (NOTE 4) WILL DICTATE WHICH INSTALLATION IS
<br />SS BOLTS APPROPRIATE.
<br />S 12 7/8"MIN
<br />W 7. RING AND COVER WITH CONCRETE COLLAR MAY BE
<br />E PLACED AT GROUND SURFACE IN UNPAVED AREAS
<br />R ❑ ❑ -
<br />v DESIRED.
<br />1-1ElIF
<br />9� El �Tlm
<br />x ❑ ❑ ❑
<br />101/2"
<br />❑ ❑ ❑ MIN
<br />N
<br />18"MIN
<br />6" GASKETED CAP 10,
<br />(NOTE 4) PLAN SECTION
<br />12" CAST IRON BOLTED RING AND COVER
<br />(SEE NOTE 5)
<br />SEE STD CITY OF EVERETT
<br />DETAIL 6020:77-
<br />PUBLIC WORKS DEPARTMENT
<br />TYPE 3
<br />CiryEngineer section Mana er CAD Manager
<br />UNPAVED AREA EERYAN SASS DAVID VOIGT PAUL WILHELM wn ESH 03/30/2017
<br />SEWER CLEAN -OUT STANDARD DRAWING No.
<br />TEMPORARY INSTALLATION FOR NEW DEVELOPMENT
<br />A
<br />TYPE 1, 2, 3 & 12" CAST IRON 604
<br />=
<br />RING & COVER
<br />1 I
<br />SEWER CLEA1V OUT TYPE 1,2,3 & 12" CAST IRON RING & COVER
<br />N.T.S. (CITY OF EVERETT STD. 604)
<br />I
<br />NOTES
<br />FINAL JOINT MUST
<br />1. ALL TRENCHES IN ROADWAY AREAS SHALL BE
<br />BE SAWCUT
<br />BACKFILLED AND PATCHED WITH TEMPORARY
<br />EXISTING ASPHALT ASPHALT AT THE END OF EACH WORK DAY, UNLESS
<br />CONCRETE ASPHALT CONCRETE (2" MIN) PERMISSION IS GRANTED TO DO OTHERWISE BY THE
<br />TO MATCH EXISTING THICKNESS CITY ENGINEER.
<br />EXISTING CEMENT
<br />CONCRETE 2. ALL TEMPORARY PATCHES ON TRENCHES SHALL BE
<br />6" MIN °,. + .°:. SAWCUT OR LINE DRILL UNDERLYING CONCRETE PERMANENTLY PATCHED WITHIN 2 WEEKS OF
<br />COMPLETION OF WORK WITHIN ROADWAY AREA.
<br />° 6" MIN CEMENT CONCRETE TO
<br />MATCH EXISTING THICKNESS
<br />3. CEMENT CONCRETE FOR PATCHING SHALL BE
<br />6" MIN CRUSHED SURFACING TOP COURSE COMMERCIAL MIX AS CALLED OUT IN WSDOT
<br />STANDARD SPECIFICATIONS.
<br />SEE STANDARD DRAWING 614
<br />EXISTING ASPHALT CONCRETE OVER CEMENT CONCRETE
<br />FINAL JOINT MUST
<br />BE SAWCUT
<br />ASPHALT CONCRETE (3" MIN)
<br />EXISTING ASPHALT REPLACEMENT PATCH TO BE
<br />CONCRETE 1" THICKER THAN PREVIOUSLY EXISTED
<br />6" MIN 6" MIN CRUSHED SURFACING
<br />TOP COURSE
<br />SEE STANDARD DRAWING 614
<br />EXISTING ASPHALT CONCRETE OVER PREPARED GRADE
<br />FINAL JOINT MUST
<br />3
<br />BE SAWCUT CEMENT CONCRETE (8" MIN)
<br />EXISTING CEMENT REPLACEMENT PATCH TO BE
<br />w
<br />CONCRETE 1" THICKER THAN PREVIOUSLY EXISTED
<br />g
<br />o
<br />PAVEMENT
<br />°
<br />w
<br />d
<br />° . <d b ° d °
<br />6" MIN CITY OF EVERETT
<br />0
<br />6" MIN CRUSHED SURFACING
<br />z
<br />TOP COURSE EVERETT PUBLIC WORKS DEPARTMENT
<br />aSEE
<br />WO
<br />o
<br />STANDARD DRAWING 614 <ityEngReer unManager AD Manager Drawn By Current Rev Date
<br />RYAN SASS TOM HOOD PAULWILHELM Wag 04/26/2017
<br />TITLE
<br />a
<br />0o
<br />STANDARD DRAWIrvG No,
<br />EXISTING CEMENT CONCRETE OVER PREPARED GRADE
<br />Ear
<br />PAVEMENT PATCHING DETAILS 326
<br />('T' PA VEMENT PATCHING DETAILS
<br />SW2 N.T.S. (CITY OF EVERETT STD. 326)
<br />SEE SHEET 104 PROPERTY LINE SEE SHEET 604
<br />NOTES
<br />OR RIGHT-OF-WAY
<br />R
<br />1. PVC SIDE SEWER CONNECTIONS TO PVC NEW
<br />GRADE ELEVATION
<br />TYP GRADE ELEVATION IMAINS
<br />SHALL BE FACTORY TEES.
<br />-
<br />6" PVC ASTM
<br />-III III
<br />2. TYPE A & B SHALL BE USED ONLY WHEN
<br />APPROVED D3034,
<br />INSTALL SDR35 OR
<br />Z
<br />g
<br />SEWER MAIN DEPTH EXCEEDS 15 FEET OR AS
<br />APPROVED BY THE ENGINEER. TYPE D SHALL
<br />CAP NOT COUPLING AWWA C900
<br />APPROVED COUPLING
<br />BE USED WHEN EXISTING SIDE SEWER IS
<br />PLUG
<br />SHALLOW (LESS THAN 6' DEPTH AT PROPERTY
<br />LINE)
<br />"DEEP
<br />2% MIN. SLOPE
<br />�N
<br />3. CONNECTIONS TO EXISTING CONCRETE
<br />SOCKET" FITTINGS
<br />EXISTING
<br />2�� E EXISTING SIDE SEWER
<br />SEWER MAINS SHALL BE MADE PER
<br />AT EACH END OF
<br />SIDE SEWER
<br />STANDARD DRAWINGS 612 & 613 OR BY
<br />VERTICAL PIPE SECTION
<br />6" PVC ASTM D3034.
<br />APPROVED MANUFACTURED CONCRETE TEE.
<br />"GPK PRODUCTS" OR EQUAL
<br />SDR35 OR AWWA C900 PVC SEWER MAIN
<br />(SEE CONNECTION
<br />4. SEE STANDARD DRAWING 604. WHERE RING
<br />NOTES 33)
<br />AND COVER INSTALLATIONS ARE SHOWN FOR
<br />35°MIN
<br />PAVED AND UNPAVED AREAS, FIELD
<br />45°MAX
<br />CONDITIONS WILL DICTATE WHICH
<br />O
<br />SANDBAG FILLED WITH 60LBS
<br />INSTALLATION IS APPROPRIATE.
<br />PVC SEWER MAIN
<br />MINIMUM DRY MIX CONCRETE
<br />(SEE CONNECTION
<br />12" X 12" CIP CONCRETE BLOCK. CONCRETE SHALL BE
<br />(OR CONCRETE BLOCK, SAME AS
<br />5. CONNECTIONS TO EXISTING HDPE SEWER
<br />NOTES 2 & 3)
<br />COMMERCIAL CONCRETE MIX AS CALLED OUT IN
<br />TYPE "A")
<br />MAINS SHALL BE MADE PER STANDARD
<br />WSDOT STD SPECS OR SANDBAG FILLED WITH 60LBS
<br />DRAWING 612 OR SIDE -WALL FUSION.
<br />MIN OF DRYMIX CONCRETE.
<br />TYPE "A"
<br />TYPE "C"
<br />SEE SHEET 604 R SEE SHEET 604
<br />R
<br />GRADE ELEVATION GRADE ELEVATION
<br />-III I pi IT,
<br />I I I I I I- TTT
<br />z
<br />-I I
<br />SHALLOW SIDE SEWER
<br />o
<br />INSTALL CAP g g
<br />EXISTING SIDE SEWER
<br />N
<br />NOT PLUG
<br />6 PVC ASTM D3034,
<br />4" OR 6"
<br />o
<br />APPROVED SDR35 OR AWWA
<br />APPROVED COUPLING
<br />Z
<br />COUPLING C900
<br />Z
<br />EXISTING
<br />- 6"x6" OR 6"X4" SAN
<br />g
<br />PVC SEWER MAIN
<br />SIDE SEWER
<br />j / TEE/WYE
<br />>
<br />(SEE CONNECTION
<br />:drl�
<br />35°MIN
<br />o
<br />NOTES 2 & 3)
<br />2% MIN. SLOPE
<br />FUTURE DEEPER
<br />45°MAX
<br />h
<br />6" PVC ASTM D3034, SDR35 u
<br />SIDE SEWER
<br />N
<br />35°MIN OR AWWA C900 `=
<br />CITY OF EVERETT
<br />O''
<br />45°MAX
<br />SANDBAG FILLED WITH 60LBS MINIMUM
<br />DRY MIX CONCRETE
<br />PUBLIC WORKS DEPARTMENT
<br />o(OR
<br />CONCRETE BLOCK, SAME AS TYPE "A")
<br />ciry Engineer awn Cur Si°n Manager AD Manager Or By rent Rev Date
<br />eaDAVIDVOIGT
<br />$
<br />SANDBAG FILLED WITH 60LBS MINIMUM
<br />RVANSASS PAULWILHELM was
<br />R 12/30/2016
<br />TYPICAL SIDE SEWER nANDARDDRAWING N°.
<br />TYPE 111311 DRY MIX CONCRETE
<br />TYPE "D"
<br />A a
<br />(OR CONCRETE BLOCK, SAME AS TYPE "A")
<br />CONNECTIONS 602
<br />TYPE A,B,C,&D
<br />3 TYPICAL SIDE SEWER CONNECTIONS
<br />SW2 N.T.S. (CITY OF EVERETT STD. 602)
<br />SEWER MAIN SYSTEM CONSTR UCTION PLAN NOTES:
<br />THE INSTALLATION OF ALL EXTENSIONS TO THE SANITARY SEWER SYSTEM SHALL BE DONE
<br />PER PLANS WHICH HAVE BEEN APPROVED BY THE CITY ENGINEER.
<br />SANITARY SEWER PLANS ARE TO BE SEPARATE FROM OTHER UTILITY PLANS, BUT ALL
<br />OTHER UTILITIES ARE TO BE SHOWN, WITH SANITARY SEWER PORTIONS HIGHLIGHTED.
<br />UNLESS APPROVED OTHERWISE, PLANS SHOULD BE PREPARED ON 22 INCH BY 34 INCH
<br />PLAN/PROFILE TYPE SHEETS AND SHALL SHOW BOTH PLAN AND PROFILE VIEWS. OTHER
<br />UTILITIES ARE TO BE SHOWN IN PROFILE VIEW AND IN PLAN VIEW.
<br />THE MINIMUM ALLOWABLE SCALE SHALL BE 1 INCH = 40 FEET, ON SMALL PROJECTS, IT
<br />SHALL BE EXPECTED THAT THE SCALE WILL BE ENLARGED TO ADEQUATELY UTILIZE THE
<br />FULL PLAN SHEET.
<br />PROVIDE NOTES ON PLANS THAT REFER TO SPECIFIC CITY STANDARDS FOR SUCH THINGS
<br />AS MANHOLES, DROP CONNECTIONS, SIDE SEWERS, ETC.
<br />PLANS SHALL SHOW INVERT ELEVATIONS OF THE MAIN AT THE OUTLET AND ALL INLETS
<br />OF EACH MANHOLE, SLOPE OF THE MAIN AND SURFACE ELEVATIONS OF THE MANHOLE
<br />LID. IN THE PROFILE VIEW, THE FINISH GROUND ELEVATION OVER THE PIPE SHALL BE
<br />SHOWN AS WELL AS CROSSINGS OF OTHER EXISTING OR PROPOSED UTILITIES. STATIONING
<br />OF SIDE SEWERS FROM THE DOWNHILL MANHOLE IS REQUIRED.
<br />IN ALL CASES WHERE A NEW SEWER LINE IS TO BE LOCATED IN AN EASEMENT, THE
<br />EASEMENT IS TO BE SHOWN WITH MEASUREMENT INFORMATION TO ACCURATELY FIELD
<br />SURVEY AND STAKE LOCATION PRIOR TO CONSTRUCTING THE PIPE LINE.
<br />UPON COMPLETION OF CONSTRUCTION, THE ORIGINAL OF THE PLAN SHALL BE AS -BUILT
<br />BY THE DEVELOPER AND CERTIFIED AS AS -BUILT BY HIM AND TURNED INTO THE PUBLIC
<br />WORKS DEPARTMENT WITH PROPERLY EXECUTED EASEMENT DEEDS AS APPLICABLE FOR
<br />THE PROJECT.
<br />SEWER MAIN SYSTEMREQUIRED NOTES:
<br />THE FOLLOWING STANDARD NOTES ARE REQUIRED ON ALL SANITARY SEWER PLANS:
<br />A. ALL WORK AND MATERIALS SHALL CONFORM TO THE CITY OF EVERETT STANDARDS
<br />AND WSDOT/APWA STANDARD SPECIFICATIONS.
<br />B. NO PART OF THE SANITARY SEWER SYSTEM SHALL BE COVERED, CONCEALED OR
<br />PUT INTO USE UNTIL IT HAS BEEN TESTED, INSPECTED, AND APPROVED BY THE CITY
<br />INSPECTOR.
<br />C. APPROXIMATE LOCATIONS OF EXISTING UTILITIES HAVE BEEN OBTAINED FROM
<br />AVAILABLE RECORDS AND ARE SHOWN FOR CONVENIENCE. THE CONTRACTOR SHALL
<br />BE RESPONSIBLE FOR VERIFICATION OF LOCATIONS AND TO AVOID DAMAGE TO ANY
<br />ADDITIONAL UTILITIES NOT SHOWN. IF CONFLICTS WITH EXISTING UTILITIES ARISE
<br />DURING CONSTRUCTION, THE CONTRACTOR SHALL NOTIFY THE PUBLIC WORKS
<br />INSPECTOR AND ANY CHANGES REQUIRED SHALL BE APPROVED BY THE CITY
<br />ENGINEER PRIOR TO COMMENCEMENT OF RELATED CONSTRUCTION ON THE PROJECT.
<br />D. ALL SEWER MAIN EXTENSIONS WITHIN THE PUBLIC RIGHT-OF-WAY OR IN EASEMENTS
<br />MUST BE STAKED BY SURVEY FOR LINE AND GRADE PRIOR TO STARTING
<br />CONSTRUCTION.
<br />NOTE:
<br />THE CURRENT DESIGN AND CONSTRUCTION STANDARDS AND SPECIFICATIONS ARE
<br />AVAILABLE ONLINE AT HTTPS://EVERETTWA.GOV/1531/DESIGN-CONSTRUCTION-STANDARDS
<br />SEWER MAIN SYSTEM GENRAL NOTES:
<br />CONSTRUCTION OF ALL SANITARY SEWER MAINS, SIDE
<br />SEWERS (LATERALS) - WHETHER SIDE SEWERS ARE BY GRAVITY, BY FORCE
<br />MAIN, OR PRESSURE SEWER -AND RELATED FACILITIES, INCLUDING BUT
<br />NOT LIMITED TO SEWER LIFT STATIONS, TELEMETRY FACILITIES AND
<br />APPURTENANCES WILL BE UNDER THE SUPERVISION OF THE CITY AND
<br />SHALL BE IN COMPLIANCE WITH ALL ORDINANCES AND CURRENT
<br />STANDARDS OF THE CITY OF EVERETT, WASHINGTON STATE DEPARTMENT
<br />OF ECOLOGY CRITERIA FOR SEWAGE WORKS DESIGN (ORANGE BOOK), OR
<br />THE UNIFIED PLUMBING CODE AS APPLICABLE.
<br />SEWER MAIN EXTENSIONS WILL BE REQUIRED WHEN THE PROPERTY DOES
<br />NOT FRONT ON A SEWER MAIN OR WHEN THE EXISTING SEWER MAIN IS
<br />NOT ADEQUATE FOR THE INCREASED USE PROPOSED. THE MINIMUM
<br />EXTENSION SHALL BE TO A POINT AT LEAST 5 FEET INSIDE THE
<br />PROLONGATION OF THE PROPERTY LINE.
<br />EACH SIDE SEWER SHALL SERVE ONLY ONE BUILDING AND ONE PARCEL
<br />(ONE CONNECTION FROM LOT TO MAIN) PER SECTION 6-8.3 AND EMC
<br />14.08.170.
<br />ALL NEW SEWER CONNECTIONS SHALL COMPLY WITH BACKWATER VALVE
<br />REQUIREMENTS IN EMC 14.08.180 B. 1.
<br />ALL PIPE INSTALLED SHALL BE STRUCTURALLY SOUND FOR THE DESIGN
<br />DEPTH.
<br />REQUIREMENTS FOR NEW PROPOSED LIFT (PUMP) STATIONS TO BE
<br />DEDICATED TO THE CITY ARE PROVIDED IN SECTION 6-5.1 AND PER THE
<br />CITY'S CURRENT LIFT STATION STANDARDS AS ESTABLISHED BY THE CITY'S
<br />MAINTENANCE DIVISION/SEWER UTILITY. LIFT STATIONS ARE DEFINED AS
<br />SEWAGE PUMPING SYSTEMS THAT SERVE MULTIPLE RESIDENTIAL LOTS OR
<br />A NON-RESIDENTIAL DEVELOPMENT GENERATING SIGNIFICANT SEWAGE
<br />VOLUME. LIFT STATIONS MUST BE DEMONSTRATED TO BE NEEDED, COST
<br />EFFECTIVE FOR THE CITY TO OWN AND MAINTAIN BASED ON SEWER RATES
<br />AND LIFECYCLE 0&M COSTS, MEET THE MAINTENANCE DIVISION
<br />STANDARDS, AND BE PERMITTED AND APPROVED SOLELY AT THE INTEREST
<br />OF THE DEPARTMENT. GRINDER PUMP INSTALLATION FOR INDIVIDUAL
<br />PARCELS MAY BE ALLOWED UNDER SEPARATE REVIEW PER SECTION 6-5.2.
<br />ALL REQUESTS FOR INSPECTIONS AND FOR WITNESSING ACCEPTANCE
<br />TESTS SHALL BE SCHEDULED WITH THE PUBLIC WORKS INSPECTOR AT
<br />LEAST 24 HOURS IN ADVANCE. FAILURE TO GIVE ADEQUATE ADVANCE
<br />NOTICE MAY RESULT IN DELAYS TO THE CONTRACTOR FOR REQUIRED
<br />INSPECTIONS.