Laserfiche WebLink
M <br /> GENERAL NOTES: o <br /> FIRE ALARM SYMBOL LEGEND 1. SCOPE OF WORK: THIS PROJECT SHALL INCLUDE THE INSTALLATION OF AN DMP <br /> NOTE a SYMBOLS ar NOT BE USED OB THIS BBaECT r. DUALCOM COMMUNICATOR TO AN EXISTING SILENT KNIGHT 6700 PANEL. <br /> SYMBOL DESCRIPTION MANUF. & PART # MOUNTING MOUNT IN OTY ! i 2. THESE DRAWINGS ARE DIAGRAMMATIC. REFER TO THE ARCHITECTURAL DRAWINGS <br /> FACP FIRE ALARM CONTROL PANEL SILENT KNIGHT-6700 EXISTING EXISTING - _ - FOR EXACT DIMENSIONS. o <br /> a z i <br /> COM FIRE ALARM COMMUNICATOR DMP-DUALCOMNF-FN WALL-TOP®66" ICABINET INCLUDEDt ,,. ,, , 3. INSTALLATION SHALL COMPLY WITH NEC, NFPA 72 AND ALL OTHER APPLICABLELD <br /> ry CODES AS REQUIRED BY THE LOCAL AUTHORITY HAVING JURISDICTION. a al <br /> ABBREVIATION DESCRIPTION ABBREVIATION DESCRIPTION j rnouss�© w 16 25 <br /> E EXISTING AWG AMERICAN WIRE GAUGE us001 OR MD1 _ 4. WIRING DEPICTED ON THESE PLANS IS SCHEMATIC - ACTUAL WIRE LOCATIONS MAY <br /> G WITH GUARD TWP TWISTED PAIR (L-DENOTES LOOP A - - - `1" '• DIFFER FROM THESE PLANS. WIRING SHALL BE PERFORMED AS ACTUAL BUILDING c <br /> P PENDENT MOUNT TWSP TWISTED SHIELDED PAIR (s a u-DENDEEs SENSOR OFUM000LE 1) `' _ :_• CONSTRUCTION CONDITIONS ALLOW AND TO MINIMIZE PENETRATIONS THROUGH AREA o <br /> R RESIDENTIAL 110V FPLP I FIRE POWER LIMITED PLENUM 1- 16 2 TWP ' `�- '� SEPARATION WALLS AND FIRE WALLS. THE USE OF A RACEWAY IS PERMITTED AS W <br /> S SOUNDER BASE FPLR FIRE POWER LIMITED RISER rnRE1YPE..RLvuIED - �. LONG AS NO 11OV OR HIGHER VOLTAGE CABLES ARE IN THE SAME RACEWAY. N <br /> WP WEATHERPROOF CONOUCWR COUNT �• - � 'N— N <br /> EOL END OF LINE RESISTOR BTR� N1RE SIZe -'= <br /> r CNAE A� or CMUS 0r OMMED 5. FIRE RATINGS SHALL BE MAINTAINED FOR ALL PENETRATIONS THROUGH FIRE-RATED z <br /> EOLR END OF LINE RELAY 15 30 �NLY 1 CABLE NEEDED) CONSTRUCTION. y o <br /> 6. POWER FOR ALL FIRE ALARM PANELS AND FIRE ALARM POWER SUPPLIES MUST BE rc <br /> PROVIDED BY A DEDICATED AC BRANCH CIRCUIT. THE LOCATION OF THE BRANCH <br /> CIRCUIT BREAKER SHALL BE PERMANENTLY IDENTIFIED AT THE CONTROL UNIT, <br /> 0 }1 �_- • MECHANICALLY PROTECTED, ACCESSIBLE ONLY TO AUTHORIZED PERSONNEL AND Z co <br /> co <br /> SHALL BE RED AND LABELED FIRE ALARM CIRCUIT CONTROL" IN ACCORDANCE <br /> WITH NFPA 72. ELECTRICAL CONTRACTOR SHALL PERFORM LOAD CALCULATIONS TO <br /> o < x = 3 r MM2�AhL� - ' :y DETERMINE SIZE OF WIRING AND BREAKERS FOR ALL FIRE ALARM AC BRANCH O co <br /> a z N x S K'4 CIRCUITS BASED ON THE INFORMATION PROVIDED IN THE BATTERY CALCULATIONS <br /> FOR THE FIRE ALARM EQUIPMENT. <br /> OPERATIONS a <br /> MATRIXftir 7. POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST REMAIN SEPARATED V <br /> o a i v"- IN CABINET. ALL POWER-LIMITED CIRCUIT WIRING MUST REMAIN AT LEAST 0.25" <br /> EXISTING SYSTEM OPERATIONS SHALL y = < x r k _ r 1 AWAY FROM ANY NONPOWER-LIMITED CIRCUIT WIRING. FURTHERMORE, ALL <br /> REMAIN,FIELD VERIFY ACTUAL SYSTEM z o y o o - urt` POWER-LIMITED AND NONPOWER-LIMITED CIRCUIT WIRING MUST ENTER AND EXIT <br /> OPERATIONS =o Eso y W W " - `. THE CABINET THROUGH DIFFERENT KNOCK OUTS AND/OR SEPARATE CONDUITS. <br /> c a c o c a F < s w • 1 3. L.L E- <br /> z a � � ` ' - _ 8. WHEN UTILIZING CLASS "A" CIRCUITS, SEPARATE OUTGOING AND RETURN � d <br /> r � � 3o W W N CONDUCTORS OF CLASS "A" CIRCUITS BY A MINIMUM OF 12" WHERE RUN w <br /> _ Q <br /> Q Q 6 Q Q Q N Z N N Q W r OT , + U1 <br /> VERTICALLY AND 48" WHERE RUN HORIZONTALLY. (n <br /> FIRE ALARM INPUT c a a a a a a a N s z J v� <br /> SHIELDED <br /> SMOKE DETECTORS • • • • • • • • • � v 9 d NCTIONHENILIZING BOX. INSULATE A DBLE TAPEEBACKLDS AT ENDOUGH AND INSULATE AT EACH Q <br /> HEAT DETECTORS • • • • • • • • VICINITY MAP <br /> N 10. ALL FIRE ALARM CABLING SHALL BE ACCEPTABLE TO THE FIRE ALARM EQUIPMENT F <br /> KITCHEN HOOD • • • • • • • • SCHEMATIC:NOT TO SCALE MANUFACTURER FOR THE INTENDED PURPOSE. CABLES USED IN VERTICAL RUNS x <br /> SHALL BE TYPE FPLP OR FPLR. CABLE SPLICES OR TERMINATIONS SHALL BE MADE <br /> PULL STATIONS • • • • • • • • IN LISTED FITTINGS, BOXES, ENCLOSURES, FIRE ALARM DEVICES, OR UTILIZATION <br /> WATERFLOW SWITCHES • • • • • • • • EQUIPMENT. WHERE INSTALLED EXPOSED, CABLES SHALL BE ADEQUATELY <br /> VALVE SUPERVISORY SWITCHES • • • • SUPPORTED AND INSTALLED IN SUCH A WAY THAT MAXIMUM PROTECTION AGAINST c <br /> PHYSICAL DAMAGE IS AFFORDED BY BUILDING CONSTRUCTION. WHERE LOCATED <br /> DUCT DETECTORS • • • • • • WITHIN 7 FT OF THE FLOOR, CABLES SHALL BE SECURELY FASTENED IN AN <br /> FIRE ALARM AC POWER FAIL • • • • APPROVED MANNER AT INTERVALS OF NOT MORE THAN 18 IN. CQ <br /> FIRE ALARM LOW BATTERY • • • • 11. SMOKE DETECTORS SHALL NOT BE INSTALLED UNTIL AFTER CONSTRUCTION <br /> OPEN CIRCUIT • • • • A/C SUPPLY OR CLEAN-UP IS COMPLETED AND FINAL. <br /> GROUND FAULT • • • • RETURN DIFFUSER PENDANT MOUNTED NOTE:MEASUREMENTS 12. LOCATE SMOKE DETECTORS A MINIMUM OF THREE (3) FEET FROM MECHANICAL <br /> NAC SHORT CIRCUIT • • • • CEILING-MOUNTED II AUDIBLE/VISUAL SHOWN ARE TO THE DIFFUSERS. WALL-MOUNTED SMOKE DETECTORS SHALL BE LOCATED A MAXIMUM OF <br /> 4"MIN HEAT DETECTOR V II, APPLIANCES CLOSEST POINT OF 12" FROM CEILING. <br /> CEILLOSS OF AC TO BUILDING • • • • • /�/������ DETECTOR <br /> 4"MIN 6'MIN. 36"MIN* <br /> 13. PROVIDE SYNCHRONIZATION OF ALL VISUAL NOTIFICATION APPLIANCE CIRCUITS. <br /> 12"MAX AUDIBLE SUAL 12"MAX <br /> M AUDIBLE-ONLY REMOTE ALARM CEILING MOUNTED CEILING MOUNTED PROVIDE ALL REQUIRED SYNC MODULES. PROVIDE AMULTI-SYNC MODE SLAVE <br /> EVER AND/OR VISUAL ® APPLIANCES INDICATOR SMOKE/HEAT AUDIBLE/VISUAL CONNECTION BETWEEN ALL SYNC MODULES. <br /> HERE ONLY APPLIANCE C= o DETECTOR APPLIANCES <br /> WALL-MOUNTED 14. VERIFY ALL FIELD SELECTABLE AUDIBILITY SETTINGS OF NOTIFICATION APPLIANCES <br /> WALL-MOUNTED SMOKE DETECTOR WITH FIRE ALARM CONTRACTOR. <br /> HEAT DETECTOR DOOR WIDTH <br /> LEss 3� 15. UPON COMPLETION OF THE FIRE ALARM SYSTEM INSTALLATION AND PROGRAMMING, <br /> 6 THE INSTALLING CONTRACTOR SHALL PERFORM FINAL TESTING OF THE ENTIRE <br /> FSA GD OIRRd 30 MAX SYSTEM, PER ALL APPLICABLE CODES, AND SHALL COORDINATE AND PERFORM A <br /> Fa SYSTEM HOLDER FINAL FIRE ALARM SYSTEM INSPECTION. (+Iy <br /> SIDE WALL <br /> RECORDS. <br /> ® 80 MIN. 10' MAX 30'MAX CD <br /> DOCUMENTS LOWEST <br /> 71 TO LOWEST WHEREERE CEILING AFF AFF 16. PROVIDE OFF-SITE MONITORING AS REQUIRED BY THE INTERNATIONAL FIRE CODE, Q W N Q <br /> PART OF LENS HEIGHT ALLOWS 5 SECTION 907.6.E AND THE LOCAL AUTHORITY HAVING JURISDICTION. V J <br /> 'MAX. <br /> 00 <br /> 66'TO 66"TO 66"TO FROM EXIT FINISHED <br /> 1pppo yypp�� TOP OF TOP OF TOP OF ® WALL 17. INSTALLING CONTRACTOR SHALL, PHYSICALLY, L(ABEL ALL INITIATING DEVICES AND <br /> DEDICATED CIRCUIT /�, FSA FRCP CABINET NOTIFIC�ULL�46 LABELSATION SHALL BEIAINCE CIRCUIT PLACE PRIORD OF LINETO START-UP AND WHEN TESTING CLASSING "B"). THESE m Q <br /> V INISHED STATION 18. ROOMS CONTAINING CONTROLS FOR AIR-CONDITIONING SYSTEMS, SPRINKLER RISERS ~ J <br /> FLOOR AND VALVES OR OTHER FIRE DETECTION, SUPPRESSION OR CONTROL ELEMENTS Q Q <br /> V SHALL BE IDENTIFIED WITH PERMANENTLY MOUNTED SIGNS WITH LETTERING NOT W U J <br /> LESS THAN 2 INCHES TALL WITH A PRINCIPAL STROKE OF NOT LESS THAN 3/8 W Q <br /> FACP J INCH. LETTERS SHALL CONTRAST WITH BACKGROUND. W CD W <br /> rn EXISTING INITIATING:NO CHANGE FIRE ALARM DEVICE MOUNTING HEIGHTS W W Lu <br /> SCALE:NOT TO SCALE _ <br /> W <br /> ALARM FACP-1 EXISTING NOTIFICATION:NO CHANGE <br /> FACP-2 EXISTING NOTIFICATION:NO CHANGE <br /> DMP <br /> CELLULAR <br /> FIRE ALARM <br /> COMMUNICATOR E O anrhBr <br /> NO CONDUIT IN BOTTOM OF CAN <br /> SALARM RISER DIAGRAM <br /> CHBA TI NOT TO <br /> SCALE <br /> Drawings reviewed by: DRAWN <br /> CRL <br /> Brady B.Haws SET UNICAD JOB#23539 <br /> NICET Certification CHECKED BRADY B.HAWS <br /> Fire Protection Engineering Technology NICET IV138751 <br /> Fire Alarm Systems-Level IV DATE 9/18/2023 <br /> Cert.No.138751 <br /> EXp 5/1/2025 REVISION 0 <br /> SCALE 1/8•=1'-0" <br /> ­y NCADUTUFA-1 <br /> Office:891.985.9410 � <br /> u"katlne <br />