SYSTEM DESIGNATIONS EQUIPMENT/DEVICES RECEPTACLES ABBREVIATIONS GENERAL NOTES
<br /> HASH MARKS INDICATE THE QUANTITY OF CONDUCTORS $ SINGLE POLE TOGGLE SWITCH DUPLEX,15A,120V,10,2P,3W, PARALLEL BLADE, GROUNDED. A. AMPERES A. ELECTRICAL LAYOUT DRAWINGS ARE PARTIALLY DIAGRAMMATIC. REFER
<br /> (#12 WIRE UNLESS OTHERWISE NOTED). IF UNMARKED AC ALTERNATING CURRENT TO ARCH ITECTURAL,STRUCTURAL, MECHANICAL AND HVAC DRAWINGS FOR
<br /> IN STALL
<br /> 2#12 IN 1/2"CONDUIT $3 THREE-WAY TOGGLE SWITCH FOUR PLEX-2 DUPLEX 15A,10,2P,3W, PARALLEL BLADE GROUNDED. GUIDANCE ON DIMENSIONS, CEILING HEIGHTS, DOOR SWINGS, ROOM FINISHES,
<br /> PHASE CONDUCTORS $K KEY SWITCH *30 SINGLE, 30A, 48OV, 30, 4 POLE, WITH A.F.F. ABOVE FINISHED FLOOR STRUCTURAL AND ARCHITECTURAL DETAILS, LOCATIONS OF DUCTS, PIPES AND
<br /> NEUTRAL C0NEUCTOR(IF REQUIRED) BACK BOX, GROUND THRU EXTRA POLE AND SHELL. ATS AUTOMATIC TRANSFER SWITCH STRUCTURAL STEEL. INSTALL THE ELECTRICAL SYSTEMS WITHOUT INTERFERING
<br /> GROUND CoNDUCTOR(II REQUIRED) $Lv SWITCH FOR LOW-VOLTAGE SWITCHING SYSTEM 20 AWG AMERICAN WIRE GAUGE WITH DUCTS, PIPES, STRUCTURAL STEEL OR OTHER SYSTEMS. LOCATE LIGHTING
<br /> 3V34-1V-6A/7,9j1 DUPLEX,20A,120V,10,2P,3W, PARALLEL BLADE, GROUNDED SYMMETRICALLY IN PROPER RELATION TO FINISHED AREAS EXCEPT WHERE
<br /> 3/4'C,3#8 PANEL HOME-RUN $Lv(z) AS INDICATES NOTED ON DRAWING. (EG. (2)VINDICATES
<br /> LTAGE DICATESWTWO ES B.O.D. BOTTOM OF DUCT IG DUPLEX 15A 120V 10 2P 3W PARALLEL BLADE B.O.T. BOTTOM OF TRAY
<br /> DIMENSIONED ON THE DRAWINGS OR LOCATED ON REFLECTED CEILING PLANS.
<br /> PANEL/CIRCUIT
<br /> CONDUIT/CONDUCTORS SWITCHES AT THIS LOCATION) WITH ISOLATED GROUND, ORANGE CAT. NO. CATALOGUE NUMBER B. PROVIDE ADDITIONAL SUPPORTS FOR SWITCHES, STARTERS, RACEWAYS AND
<br /> OTHER ELECTRICAL EQUIPMENT WHERE THE BUILDING STRUCTURE IS NOT
<br /> CONDUIT RUN EXPOSED, ALL CONDUITS 1/2" UNLESS $GC LIGHTING SWITCH WITH OCCUPANCY SENSOR #20 FOUR PLEX-2 DUPLEX, 20A,10,2P,3W, PARALLEL BLADE GROUNDED. CKT. CIRCUIT SUITABLE FOR DIRECT MOUNTING.
<br /> OTHERWISE REQUIRED OR NOTED SO ONE. CONDUIT
<br /> $M MOTOR RATED SWITCH, 120V, 15A, 10 SINGLE, 20A, 120V, 10, 2P, 3W, STRAIGHT BLADE, GROUNDED C. A NUMERAL BESIDE A BRANCH CIRCUIT OUTLET ON WIRING PLANS INDICATES
<br /> ------- CONDUIT RUN CONCEALED IN WALLS, ABOVE CEILING, IN 30 CONT. CONTINUATION PANELBOARD BRANCH CIRCUIT CONNECTION. A LOWER CASE LETTER BESIDE AN
<br /> FLOOR SLAB OR UNDERGROUND O PUSHBUTTON STATION SINGLE, 30A, 120V, 10, 2P, 3W, STRAIGHT BLADE, GROUNDED OUTLET INDICATES THE SWITCH LEG CONNECTION WHERE OUTLETS ARE LOCALLY
<br /> -T- TELEPHONE, 3/4" MINIMUM CONDUIT ONLY, UNLESS 53 MANUAL MOTOR STARTER WITH OVERLOADS AND �30 DC DIRECT CURRENT
<br /> SINGLE, 30A, 208V, 10, 2P, 3W, STRAIGHT BLADE, GROUNDED DISC DISCONNECT SWITCHED,
<br /> SIZED OTHERWISE PILOT LIGHT g20 SINGLE, 20A, 120/208V, 10, 3P, 4W, POLARIZED, DPST DOUBLE POLE SINGLE THROW D. SYMBOLS IN THE LEGENDS ARE APPLICABLE GENERALLY. FOR EXACT
<br /> STRAIGHT BLADE, GROUNDED REQUIREMENTS REFER TO THE SCHEDULES, LAYOUTS, DETAILS AND
<br /> 60 SINGLE, 60A, 120/208V, 10, 3P, 4W, POLARIZED, EL. ELEVATION
<br /> -E- EMERGENCY CIRCUIT ® MAGNETIC MOTOR STARTER DWG. DRAWING SPECIFICATIONS.
<br /> -PA- PAGING CONDUIT WITH WIRE AS NOTED COMBINATION STARTER, CIRCUIT BREAKER TYPE, STRAIGHT BLADE, GROUNDED ELEC. ELECTRICAL ELECTRIC E. PROVIDE SEAL FITTINGS IN CONDUITS THAT ENTER HAZARDOUS AREA FROM
<br /> -G- COPPER GROUND WIRE, SIZE AS NOTED 30A UNLESS NOTED OTHERWISE 20 DUPLEX, 20A, 120V, 10, 2P, 3W, STRAIGHT BLADE, NON-HAZARDOUS AREAS.
<br /> �cva /
<br /> ENCLOSED CIRCUIT BREAKER SIZE AS NOTED GROUND FAULT CIRCUIT INTERUPTING. EWC ELECTRIC WATER COOLER
<br /> -LV- LOW VOLTAGE CONDUIT/WIRE ON DRAWING FLOOR MOUNTED EXP EXPLOSION PROOF F. INSTALL 120 VOLT CONVENIENCE OUTLETS 48" A.F.F. FOR COLUMN MOUNTED
<br /> EXST. EXISTING AND 18" A.F.F. FOR WALL MOUNTED.
<br /> -FG- FIBER OPTIC, 3/4" MIN., WITH CABLE AS INDICATED, DISCONNECT SWITCH, FUSED, 30=SWITCH RATING, FOUR PLEX-2 DUPLEX 15A, 10, 2P, 3W,PARALLEL BLADE GROUNDED.
<br /> UNLESS SIZED OTHERWISE. NO CONDULET FITTINGS IN o FA FORCED AIR FIRE ALARM
<br /> so/zo 20=FUSE RATING �' FLOOR MOUNTED /FACP FIRE ALARM CONTROL PANEL G. UNLESS OTHERWISE NOTED, RECEPTACLES SHOWN MOUNTED ON STEEL COLUMNS
<br /> FIBER OPTIC RUNS ALLOWED. SINGLE, 30A, 208V, 10, 2P, 3W, TWISTLOCK, GROUNDED SHALL BE MOUNTED IN COLUMN WEB.
<br /> DISCONNECT SWITCH, NON-FUSED, 30A FATC FIRE ALARM TERMINAL CABINET
<br /> -C- COMMUNICATIONS CIRCUIT l' UNLESS NOTED OTHERWISE ® IN CARPET MOUNTED COMBINATION COMM/POWER FLA FULL LOAD AMPERES H. CONDUITS AND CABLE TRAYS SHALL MAINTAIN A MINIMUM CLEARANCE
<br /> IC WITH ONE DUPLEX 20A, 10, 2P, 3W, RECEPTACLES AND TEL/DATA JACKS OF 1'-O" FROM HOT WATER AND STEAM PIPES, ALL OTHER PIPING
<br /> CONDUIT TURNED UP ® MOTOR CONTROLLER CEILING MOUNTED 20A, 10, 2P, 3W RECEPTACLE,HUBBELL CAT NO 5362 FUT FUTURE GFI GROUND FAULT INTERRUPTER CLEARANCES SHALL BE A MINIMUM OF SIX (6) INCHES.
<br /> CONDUIT TURNED DOWN ® CAPACITOR GND GROUND I. B.O.D. & B.O.T. DO NOT INDICATE BOTTOM OF REQUIRED HANGERS &
<br /> 1A CONDUIT IDENTIFICATION
<br /> m TRANSFORMER, SIZE AND TYPE AS NOTED LABELING AND SIGN REQUIREMENTS: HID HIGH INTENSITY DISCHARGE SUPPORT MATERIALS FOR DUCT AND TRAY.
<br /> CABLE TRAY, SIZE AS NOTED ON THE DRAWINGS 4 MOTOR, 120V,10, SIZE AS NOTED A. PROVIDE SIGNS AS REQUIRED FOR EMERGENCY AND OPTIONAL STANDBY HPS HIGH PRESSURE SODIUM J. ALLALL WIRNG,UND FITTINGS, JUNC IONRGROUND AEASNBOXES,FRO CONDUIT, CONTROL PANELS, LTC.ELEVATION 100'-0" TONSHALL 0
<br /> MOTOR, 208V, 30, SIZE AS NOTED SYSTEMS IN ACCORDANCE WITH WAC 296-46B-700 AND WAC HORZ. HORIZONTAL CONFORM TO CLASS 1 DIVISION 1 GROUP C & D REQUIREMENTS PER THE NATIONAL
<br /> rV-Lf FLEXIBLE CONDUIT, 1/2" UNLESS NOTED OTHERWISE 296-46B-702. HE HORSEPOWER ELECTRICAL CODE SECTIONS 500 AND 501. FROM ELEVATION 125'-0" TO ELEVATION
<br /> 40 MOTOR, 460V, 30, SIZE AS NOTED HVAC HEATING, VENTILATING AND 137'-0" ALL WIRING, FITTINGS, JUNCTION BOXES, CONDUIT, CONTROL PANELS, ETC.
<br /> �Ff PREWIRED FLEXIBLE CONDUIT PROVIDED WITH LIGHT B. PROVIDE EMERGENCY SYSTEMS EQUIPMENT IDENTIFICATION IN ACCORDANCE AIR CONDITIONING SHALL CONFORM TO CLASS 1 DIVISION 2 GROUP C & D REQUIREMENTS PER THE
<br /> FIXTURE TYPE R, R-2, S AND S-2 AS LST (LABOR (DJUNCTION BOX, FIELD SIZED OR AS NOTED WITH WAC 296-46B-700. EXISTING PANELBOARDS THAT ARE DESIGNATED NATIONAL ELECTRICAL CODE SECTION 500 AND 502. ABOVE ELEVATION 137'-0" IS
<br /> SAVING TANDEM) J❑ JUNCTION BOX, SQUARE 4" TO BECOME PART OF THE "EMERGENCY" SYSTEM SHALL BE RENAMED AND INST. INSTRUMENT/INSTRUMENTATION RATED AS NON-HAZARDOUS, UNLESS NOTED OTHERWISE.
<br /> RE-LABELED TO REFLECT THEIR EMERGENCY DESIGNATION AS INDICATED IN JB JUNCTION BOX
<br /> )� CONDUIT T BE REMOVED Ca GROUNDING PIGTAIL THE 'PANEL NOMENCLATURE' IDENTIFICATION BREAKDOWN SHOWN BELOW. K THOUSANDS OF CIRCULAR MILS K. ALL METAL RACEWAYS, THE METAL ARMOR OR METALLIC SHEATH ON CABLES, AND ALL
<br /> EQUIPMENT TO BE REMOVED (EG. PANELBOARD) NON-CURRENT-CARRYING METAL PARTS OF FIXED OR PORTABLE ELECTRICAL EQUIPMENT,
<br /> O PULLBOX, FIELD SIZED OR AS NOTED C. EXISTING BACKUP SYSTEMS AND/OR EQUIPMENT SUCH AS FEEDERS, KV KILOVOLTS REGARDLESS OF VOLTAGE, SHALL BE GROUNDED.
<br /> (E) EXISTING dB JUNCTION BOX, SPECIAL. FIELD SIZED OR AS NOTED TRANSFER SWITCHES, DISTRIBUTION SWITCHBOARDS, PANELBOARDS, ETC., KVA KILOVOLT-AMPERES
<br /> THAT ARE TO REMAIN IN SERVICE BUT ARE NOT CLASSIFIED AS KW KILOWATTS L. TO PREVENT SPARKS FROM THE ACCUMULATION OF STATIC ELECTRICITY, ALL ELECTRICALLY
<br /> N TELEPHONE OUTLET, WALL MOUNTED "EMERGENCN' SYSTEMS SHALL BE RENAMED AND LABELED AS STANDBY CONDUCTIVE OBJECTS, INCLUDING METAL PARTS OF SPRAY BOOTHS, HVAC DUCTS, DUCT
<br /> DISTRIBUTION LTG LIGHTING SUPPORTS, METAL PIPING SYSTEMS, SYSTEMS CONVEYING FLAMMABLE OR COMBUSTIBLE LIQUIDS
<br /> b DATA OUTLET, WALL MOUNTED SYSTEMS IN ACCORDANCE WITH THE 'PANEL NOMENCLATURE' IDENTIFICATION MEZZ. MEZZANINE OR PAINT, SOLVENT LIQUIDS OR PAINT, SOLVENT TANKS, AND CANISTERS, SHALL BE GROUNDED.
<br /> ® PANELBOARD, 480V, 30, 3W, PANELBOARD BREAKDOWN SHOWN BELOW. MCC MOTOR CONTROL CENTER
<br /> O PUSHBUTTON STATION, TYPE AS NOTED M. NO PRODUCTS CONTAINING SILICONE SHALL BE USED IN THIS BUILDING.
<br /> PANELBOARD, 480Y/277V, 30, 4W, PANELBOARD, D. ALL EXISTING FEEDERS, BRANCH CIRCUITS, BOXES, ENCLOSURES, EQUIPMENT, MR MULTI-RATIO
<br /> a SURFACE MOUNTED, FLUSH MOUNTED T THERMOSTAT RECEPTACLES, OUTLETS, ETC., THAT ARE FED FROM A RENAMED PANELBOARD MTR. MOTOR N. SEAL EACH CONDUIT AT THE CLASS 1 BOUNDARY PER NEC.
<br /> v PANELBOARD, 208Y/12OV, 30, 4W, OR 30, 5W © CONTACTOR, TYPE AS NOTED OR SWITCHBOARD SHALL BE RE-LABELED TO MATCH THE NAMING USED FOR MV MEDIUM VOLTAGE
<br /> a PANELBOARD SURFACE MOUNTED, FLUSH MOUNTED THE PANELBOARD OR SWITCHBOARD IN ACCORDANCE WITH THE ABOVE
<br /> pCC MOTOR CONTROL CENTER ® CONTROL PANEL PARAGRAPHS AS APPLICABLE TO "EMERGENCY" AND "STANDBY" SYSTEMS. NEC NATIONAL ELECTRIC CODE COLOR CODES
<br /> NEMA NATIONAL ELECTRICAL C 120/208 COMPUTER CIRCUITS
<br /> [� SPECIAL PANEL AS NOTED (D RELAY PANEL NOMENCLATURE MANUFACTURERS ASSOCIATION
<br /> INDICATES WALL MOUNTING N.C. NORMALLY CLOSED IRE ALARM SYSTEM PHASE COLOR
<br /> SINGLE LINE DIAGRAM xE 3 V03-1 U D12-1-D A BLACK
<br /> TELEPHONE AND DATA/POWER POLE N.I.C. NOT IN CONTRACT WALL MOUNT HORN/STROBE B
<br /> SUFFIX "-D" INDICATES DISTRIBUTION PANEL SUBSCRIPT ##CD = CANDELA RATING RED
<br /> CIRCUIT BREAKER, AIR, DRAW OUT PROVIDED BY SYSTEMS FURNITURE MFR. O.C. ON CENTERS
<br /> TELEPHONE AND DATA/POWER POLE SUFFIX "-1, -2, -3, ETC." IS USED TO PBRD. PANELBOARD SUBSCRIPT WP = WEATHER PROOF C WHITE PHASE TAPE BOTH
<br /> ® FUSE OINDICATE MULTIPLE PANELS AT SAME LOCATION ENDS BLUE OR YELLOW)
<br /> l PROVIDED BY ELECTRICAL CONTRACTOR WHICH ARE SAME VOLTAGE, FED FROM SAME PH. PHASE SUIBSCRIPTLING O##CD = CANDEUNT LA RATING NEUTRAL WHITE
<br /> BE
<br /> TRANSFORMER VAULT AND LOCATED ON SAME FLOOR RECP. RECEPTACLE ® WALL MOUNT STROBE EQPT. GROUND GREEN
<br /> S SINGLE POLE SINGLE THROW
<br /> LIGHTING NOTE: IF SUFFIX "-A, -B, -C, ETC." IS BEING SWW.. SUBSCRIPT ##CD = CANDELA RATING SWITCH 120/208VAC POWER
<br /> CURRENT TRANSFORMER A FIXTURE TYPE DESIGNATION. SEE FIXTURE SCHEDULE, USED INSTEAD OF "-1, -2, -3, ETC.", THEN SMOKE DETECTOR,
<br /> s SWITCHGEAR
<br /> -34 TYE. TYPICAL
<br /> SHT. EOb QUANTITY AND RATING OF LAMPS CONTINUE USING SUFFIX LETTERS FOR CLARITY SWGR. x:xx SUBSCRIPT X:XX DEVICE ADDRESS PHASE COLOR
<br /> GROUND
<br /> � (A=TYPE, 2=QUANTITY, 34=LAMP RATING) A BLACK
<br /> PANEL LOCATION AT NEAREST COLUMN V. VOLT O HEAT DETECTOR, B RED
<br /> -
<br /> ® x:xx LOCATION OF PANEL WHEN NOT ON FIRST FLOOR: VFD VARIABLE FREQUENCY DRIVE SUBSCRIPT X:XX = DEVICE ADDRESS C BLUE
<br /> AMMETER FLUORESCENT FIXTURE, 3 LAMP, TYPE AS NOTED M = MEZZANINE U = BIND FLOOR VERT. VERTICAL ❑F MANUAL STATION,
<br /> x:xx NEUTRAL WHITE
<br /> P = PENTHOUSE UT = UTILIDOR VPB VERTICAL PAINT BOOTH SUBSCRIPT X:XX = DEVICE ADDRESS Q GROUND GREEN V VOLTMETER FLUORESCENT FIXTURE, 2 LAMP, TYPE AS NOTED R = P1 PARKING FLOOR V = 3RD FLOOR W WATT SMOKE DUCT DETECTOR
<br /> S P2 PARKING FLOOR W 4TH FLOOR � PROVIDED BY OTHERS) 277/480 VAC POWER CABLES
<br /> I ENCLOSED CIRCUIT BREAKER T = TRUSS LEVEL X 5TH FLOOR W/ WITH
<br /> L_L_J SIZE AS NOTED No TN = TUNNEL W/0 WITHOUT MMM MINI MONITOR MODULE, PHASE COLOR
<br /> 11111111111131111 FLUORESCENT FIXTURE ON EMERGENCY SYSTEM, SUBSCRIPT X:XX = DEVICE ADDRESS
<br /> TYPE AS NOTED WP WEATHERPROOF A BROWN
<br /> AUXILIARY SYSTEMS ® SOURCE OF POWER: VAULT NO. XFMR. TRANSFORMER FATC FIRE ALARM TERMINAL CABINET B ORANGE
<br /> FLIGHTLINE EXAMPLE: VS38 FOR SUBSTATION S38 FRCP FIRE ALARM CONTROL PANEL
<br /> FLUORESCENT FIXTURE WITH BRANCH CIRCUIT CH GROUSE HINDS C YELLOW
<br /> $V P.A. SYSTEM ATTENUATOR, WALL MOUNTED, ® CONNECTION POINT 1 LAMP, TYPE AS NOTED VOLTAGE AND ASSOCIATED PANEL SYMBOL: CLASS I DIV. 1 RATED [EA-Cl FIRE ALARM COMMUNICATOR (CELLULAR DIALER) NEUTRAL WHITE/GREY
<br /> 10 WATT RATING FLUORESCENT FIXTURE WITH BRANCH CIRCUIT GRC GALVANIZED RIGID GROUND GREEN
<br /> S ® ® 4 = 480V, 3PH, 3W RPS REMOTE POWER SUPPLY
<br /> SPEAKER, RECESSED MOUNTED IN CEILING CONNECTION POINT 2 LAMP, TYPE AS NOTED STEEL CONDUIT
<br /> ® 3 = 480Y/277V, 3PH, 4W 28 VOLT D.C. CIRCUITS
<br /> ® ANNUNCIATOR ( INCANDESCENT FIXTURE, TYPE AS NOTED 0 2 = 208Y/12OV, 3PH, 4W OR *NOTE: SEE SHEET E510 FOR ADDITIONAL
<br /> ® TELEPHONE CABINET © 120/24OV, 1 PH, 3W FIRE ALARM ABBREVIATIONS. POSITIVE (+) RED
<br /> Ho EXIT LIGHTING SIGN, WALL MOUNTED. NEGATIVE BLACK
<br /> © 575Y
<br /> 0 LIMIT SWITCH DIRECTION OF EGRESS AS NOTED 5 = 400 HZ, /331V, 3PH, 4W (-)
<br /> 0 2 = 400 HZ, 200Y/115V, 3PH, 4W
<br /> ® EXIT LIGHTING SIGN, SUSPENDED OR CEILING 1 28 VDC 15 KV POWER CABLES
<br /> MOUNTED. DIRECTION OF EGRESS AS NOTED PREFIX:
<br /> O FIXTURE OUTLET (SHOWN WITH FIXTURES) (BLANK)= NORMAL POWER PANEL PHASE COLOR
<br /> "I" = ISOLATED GND PANEL /
<br /> OS OCCUPANCY SENSOR "Z" = 400 HZ PANEL A BLACK/PURPLE BAND 1
<br /> B RED/PURPLE BAND
<br /> "XE" = EMERGENCY PANEL C BLUE/PURPLE BAND
<br /> "XL" = LEGALLY REQUIRED STANDBY PANEL GROUND GREEN
<br /> "XS" = OPTIONAL STANDBY PANEL
<br /> SYM REVISION BY APPROVED DATE SYM REVISION BY APPROVED DATE A SUBTITLE CURRENT REVISION SYMBOL DATE
<br /> ncC EPGN AND/OR CHECKED oN 05 09 24 ELECTRICAL LEGEND&ABBREVIATIONS A 05/10/24
<br /> A EVERETT W2 LOT FIRE PANEL INSTALLATION 34558629 AGOW/JS AGOW/KM 05/10/24 m rNls DESIGN ANDPRO K. MULo
<br /> Sp
<br /> IS APPROVED K. MULLEN 05 10 24 SHEET 0 SEQUENCE Na.
<br /> Q�BOE//VG APPROVED BY DEPT. DATE K. MULLEN 05 O9 24 TITLE EVERETT FIRE PANEL INSTALLATION
<br /> [>'� HEVPInNLLQ! CHECKED
<br /> � r �• APPROVED LOT W2 BUILDINGS 7-581, 7-582 & 7-584 34558629
<br /> APPROVED EVERETT, WA. DWG No. FA-W2-7-582