Laserfiche WebLink
Fan Unit <br /> PROJECT: Soni's Kitchen DATE: 6/14/2024 <br /> LOCATION: EVERETT,WA 'INTACT; Jim Givens <br /> PROJECT#: 2024-SK AUTHOR: <br /> SYSTEM/UNIT: EF-01 Tested By: Jim Givens <br /> Date: 6/14/2024 <br /> Unit Data Motor Data <br /> Fan Manufacturer ACCUREX Motor Manufacturer Baldor <br /> Fan Model Number XRUD-140-VG Motor Frame 182T <br /> Fan Serial Number 20830146 Motor HP 1 HP <br /> Fan Rotation Clockwise Motor RPM 1688 RPM <br /> Fan Discharge OTA Motor Rated Volts 115/60/1 Volts <br /> Drive Type Direct Drive Motor Phase 1 <br /> Fan Speed High Motor Hertz 60 Hz <br /> Motor Full Load Amps 16 Amps <br /> Test Data Motor Service Factor 1.15 <br /> Total Actual Flow 1830 CFM Nominal Efficiency 89.50% <br /> Motor VFD Hertz 60.0 Hz Power Factor 74.00 <br /> Motor Volts T1-T2 208 Volts <br /> Motor Volts T2-T3 208 Volts Test Pressures <br /> Motor Volts T1-T3 208 Volts Fan Suction SP (-)in.we <br /> Motor Amps T1 7.30 Amps Fan Discharge SP OTA in.we <br /> Motor Amps T2 7.40 Amps <br /> Motor Amps T3 7.40 Amps <br /> Log: EF-01 6/14/2024 Jim Givens OTA=Open To Atmosphere <br /> EF-01 6/14/2024 Jim Givens (-)There is no feasible location to obtain this reading. <br /> Preliminary- <br /> 06/14/2024 8:17:03 AM <br />