Laserfiche WebLink
New Castle Mechanical <br /> Air Handling Unit <br /> PROJECT: Soni's Kitchen DATE: 6/14/2024 <br /> LOCATION: EVERETT, WA CONTACT: Jim Givens <br /> PROJECT#: 2024-SK AUTHOR: <br /> SYSTEMIUNIT: MAU-01 Tested By: Jim Givens <br /> Date: 6/14/2024 <br /> Unit Data Motor Data ! <br /> Unit Manufacturer ACCUREX MAU-01/Suooly Fan <br /> Unit Model Number XD GX-P115-H05-VFD Drive Type Direct Drive <br /> Unit Serial Number Vertical Motor Manufacturer Baldor <br /> Unit Discharge Motor Frame 182T <br /> MAU-01/SF Filter Bank Washable Aluminum 4 Motor HP 1 112HP <br /> Filter Type 16x20x2 Motor RPM 1725 RPM <br /> Filter Quantity-Size 1 Motor Rated Volts 208-230/460 Volts <br /> Filter Dimensions-Size 1 Motor Phase 3 <br /> Motor Hertz 60150 Hz <br /> Test Data Motor FL Amps 9-8.8/4.4/10.2/5.1 Amps <br /> Unit SA Actual Flow 1800 CFM Motor Service Factor 1.15 <br /> MAU-01/Suooly Fan Motor Efficiency 90.2/87.6% <br /> Fan Speed High Speed Motor Power Factor 74 PF <br /> VFD Setting 65.2 Hz <br /> Motor Volts T1-T2 207 Volts Test Pressures <br /> Motor Volts T2-T3 207 Volts SF Suction SP -0.74 in.we <br /> Motor Volts T1-T3 207 Volts SF Discharge SP 1 94 in.we <br /> Motor Amps T1 7.7 Amps SF Actual Total SP 2.68 in.we <br /> Motor Amps T2 7.6 Amps <br /> Motor Amps T3 7.7 Amps <br /> Log: MAU-01/Supply Fan Jim Givens Maximum setting at the wall module. <br /> Preliminary <br /> 024 8:16:49 AM <br />