Laserfiche WebLink
Air Handling Unit Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />77 <br />Test Date <br />9/17/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />FCUs <br />Equipment I.D. <br />(E) ERV-2 <br />Unit Information <br />Manufacturer <br />Daikin Industries, LTD. <br />Model Number <br />VAM1200GVJU <br />Serial Number <br />F002165 <br />Unit Location <br />Hallway <br />Supply Fan Quantity <br />SF Drive Type <br />Direct Drive <br />Return/Relief Fan Quantity <br />RF Drive Type <br />Direct Drive <br />Unit Filter Information <br />Filter I.D. <br />Type <br />I Rating <br />Filter Size / Qty <br />I Filter Size / Qty <br />Filter Size / Qty <br />Pre <br />Pleated <br />I MERV 8 <br />20 x 30 x 2 / 1 (Supply) <br />1 20 x 30 x 2 / 1 (Return) <br />/ - <br />Unit Test Data <br />Total Design Airflow <br />440 CFM <br />Total Actual Airflow <br />470 CFM <br />Design Return Airflow <br />440 CFM <br />Actual Return Airflow <br />435 CFM <br />Min OSA CFM Des / Act <br />440 CFM / 470 CFM <br />Min OSA Position OSA / RA <br />N/A / N/A <br />Design ESP <br />0.56 in.wc <br />Actual ESP <br />0.63 in.wc <br />Act. Volts T1-2/ T2-3/ T1-3 <br />207.0 / / <br />Actual Amps T1 / T2 / T3 <br />4.70 <br />SF Motor Information <br />Manufacturer <br />Daikin VAM1200GVJU <br />Motor Frame / Serv. Factor <br />/ <br />HP / RPM <br />4x3/8 / - <br />Motor Phase / Hz <br />1 / 60 <br />Motor Rated Volts / FLA <br />208-230 / 7.6 <br />Motor Eff. / PF <br />/ <br />IL Return Fan Test Data <br />Total Design Airflow <br />440 CFM <br />Total Actual Airflow <br />435 CFM <br />Design ESP <br />0.56 in.wc <br />Actual ESP <br />0.84 in.wc <br />Act. Volts T1-2/ T2-3/ T1-3 <br />208.0 / / <br />Actual Amps T1 / T2 / T3 <br />4.81 <br />Fan Speed Setting <br />(1) <br />Additional Settings <br />N/A <br />JL RF Motor Information <br />HP / RPM <br />4X3/8 / - <br />Motor Phase / Hz <br />1 / 60 <br />Motor Rated Volts / FLA <br />208-230 / 7.6 <br />Motor Eff. / PF <br />/ <br />111111 General Notes <br />ERV-2, supply and return fan has the same speed mode. Speed mode was set at low speed. The motorized damper at OSA ductwork <br />Note (1) is not working (it was closed). The damper is manually open to balance the ERV airflow. This motorized damper issue needs to be <br />fixed. <br />Page 7 of 49 <br />