Laserfiche WebLink
Fan -Coil Unit Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Break, Small Conference Rms. <br />Equipment I.D. <br />FCU-1 <br />Unit Information <br />Manufacturer <br />Carrier <br />Model Number <br />40VMV054A--3 <br />Serial Number <br />1724VO2578 <br />Unit Location <br />Break 107 <br />Supply Fan Quantity / Rotation <br />/ Correct <br />Supply Fan Drive Type <br />Direct Drive <br />Unit Filter Information <br />Filter I.D. <br />Type <br />Rating <br />Filter Size / Quantity <br />Filter Size / Quantity <br />Unit Filter <br />Pleated <br />N/A <br />24x22x2 / 1 <br />N/A / <br />Unit and Fan Test Data <br />Total Design Airflow <br />1,800 CFM <br />Total Actual Airflow <br />1,895 CFM <br />Design Return Airflow <br />1,800 CFM <br />Actual Return Airflow <br />1,695 CFM <br />Min OSA CFM Des / Act <br />110 CFM / 120 CFM <br />Min OSA Position OSA / RA <br />N/A / #VALUE! <br />Design ESP <br />0.50 in.wc <br />Actual ESP <br />0.43 in.wc <br />Actual Volts <br />208 <br />Actual Amps <br />1.87 <br />Fan Speed Setting <br />High <br />Additional Settings <br />- <br />Unit Motor Information <br />HP / RPM <br />3/4 / <br />Motor Phase / Hz <br />1 / 60 <br />Motor Rated Volts / FLA <br />208-230 / 5.7 <br />1 Motor Eff. / PF <br />/ - <br />Unit Pressure Data <br />Filter In / Out <br />-0.360 in.wc / -0.730 in.wc <br />Filter AID <br />0.370 in.wc <br />Supply Fan In / Out <br />N/A in.wc / 0.070 in.wc <br />Supply Fan A P <br />#VALUE! in.wc <br />External Static In / Out <br />-0.360 in.wc / 0.070 in.wc <br />External Static A P <br />0.430 in.wc <br />Unit Test Notes <br />Page 10 of 49 <br />