Laserfiche WebLink
NEUDORFER <br />ENGINEERS <br />AN Ctegro COMPANY <br />Grille, Register, & Diffuser Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Supply Air <br />Equipment I.D. <br />FCU-3 <br />Grille, Register, Duct, Test Data <br />Flow Spec + 10% - 10% <br />GRID <br />No. <br />Area Served <br />Instrument <br />Used <br />GRID <br />Type <br />Size <br />Inches <br />AK <br />Design <br />CFM <br />Initial <br />CFM <br />Final Airflow <br />FPM <br />CFM <br />% <br />Notes <br />1 <br />Medium Conference 106A <br />Flowhood <br />SD-1 <br />12" <br />1.00 <br />350 <br />405 <br />340 <br />97% <br />2 <br />Welcome 100 <br />Flowhood <br />SD-1 <br />10" <br />1.00 <br />240 <br />275 <br />245 <br />102% <br />3 <br />Welcome 100 <br />Flowhood <br />SD-1 <br />10" <br />1.00 <br />240 <br />280 <br />240 <br />100% <br />4 <br />Welcome 100 <br />Flowhood <br />I SD-1 <br />10" <br />1.00 <br />240 <br />250 <br />1 <br />250 <br />104% <br />(This Page) Total Airflowl <br />1070 <br />1 1210 <br />1 <br />1075 <br />100% <br />(1) <br />Test Notes <br />Note (1) 1 The volume damper is full open. <br />Page 18 of 49 <br />