Laserfiche WebLink
NEUDORFER <br />ENGINEERS <br />AN Ctegro COMPANY <br />Grille, Register, & Diffuser Test Data <br />Project No. <br />2024-1113 <br />Project I.D. <br />Edward Jones Branch # 98316 <br />Test Date <br />9/16/2024 <br />Tested By <br />Vinh Nguyen <br />Area Served <br />Return Air <br />Equipment I.D. <br />FCU-4 <br />Grille, Register, Duct, Test Data <br />Flow Spec + 10% - 10% <br />GRID <br />No. <br />Area Served <br />Instrument <br />Used <br />GRID <br />Type <br />Size <br />Inches <br />AK <br />Design <br />CFM <br />Initial <br />CFM <br />Final Airflow <br />FPM <br />CFM <br />% <br />Notes <br />1 <br />Large Confer. 106B <br />Flowhood <br />RG-1 <br />10" <br />1.00 <br />430 <br />495 <br />400 <br />93% <br />(1) <br />(This Page) Total Airflow <br />430 <br />495 <br />400 <br />93% <br />Test Notes <br />Note <br />(1) 1 The volume damper is full open. <br />Page 22 of 49 <br />