Laserfiche WebLink
We invented the concept of flexible fire protection"' <br />Installation of FlexHead® Commercial Ceiling Flexible Sprinkler Drop System <br />For use with FlexHead® hoses; 2024T, 2036T, 2048T, 2060T, 2072T 2024ET, 2036ET, 2048ET, 2060ET, 2072ET <br />T Bar Ceiling Grid Installation <br />The bracket is designed for use on ceiling grids conforming <br />to ASTM C635. <br />1) Locate the center of the ceiling tile marking, then align <br />the screw hole for true center of tile installation. <br />2) Clip the bracket on the T-Bar Ceiling Grid. <br />3) Center of the leg section must be on the outside of <br />the T-Bar (Figure 1). <br />4) Secure each bracket leg to the T-Bar with #2 Head self <br />tapping screw. <br />FlexHead° Flexible Hose Installation <br />1. Apply Teflon® tape and pipe sealant to the 1 " NPT <br />thread. Install into branch outlet. Any direction is <br />acceptable, ensure the hose is allowed at least one <br />bend per installation to allow for seismic movement. <br />2. Tighten hose using the pipe drop section, never apply <br />a wrench to the braided hose for installation. <br />Do not wrench on braided hose <br />Q FLEXHEAD <br />I N D U S TRI E S L iO www.flexhead.com <br />..� �. Llaikore <br />