Laserfiche WebLink
NEUDORFER <br /> ENGINEERS N E rB B <br /> Cabinet Unit Heater - Electric <br /> PROJECT: St. Mary Magdalen Elementary HVAC Project DATE: 8/15/2024 <br /> LOCATION: Everett, WA CONTACT: Kami Valentine <br /> PROJECT#: 2024-0871 AUTHOR: <br /> 1 Electrical connections complete, unit Pass KV 8/8/24 8:38 <br /> energized <br /> 1.0 PreFunctional Performance - ECH-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 PFPT Completed Pass KV 8/8/24 8:38 <br /> 2 IStartup Completed Pass KV 8/8/24 8:38 <br /> 1.0 Setpoints - ECH-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 ISpace Temperature Setpoint 65 F KV 8/8/24 8:38 <br /> 1.1 As Found - ECH-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 lRecord Space Temperature 65 F KV 8/8/24 8:38 <br /> 2.0 Heat - ECH-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 TEST PROCEDURE,Set the space <br /> temperature setpoint above the <br /> currents ace temp <br /> 2 Fan is ON Pass KV 8/8/24 8:38 <br /> 3 Heater is ON Pass I KV 8/8/24 8:38 <br /> 4 JDAT increases. Record DAT 80 F I KV 8/8/24 8:38 <br /> 3.0 No Heat Demand - ECH-02 Functional Performance Test <br /> Verification Response Notes By Date/Time <br /> 1 TEST PROCEDURE,Set the space <br /> temperature setpoint below the <br /> currents ace temp <br /> 2 Fan is OFF Pass KV 8/8/24 8:38 <br /> 3 Heater is OFF Pass KV 1 8/8/24 8:38 <br />