KAISER <br /> PERMANENTE <br /> Project <br /> Kaiser Permanente Everett <br /> Specialty Center <br /> 2930 MAPLE STREET <br /> EVERETT,WA 98201 <br /> DIVISION 26 ELECTRICAL SPECIFICATIONS 1.BRANCH CIRCUITS AND HOMERUNS: TYPE THHN OR THWN, 600-VOLT 2.FLEXIBLE METALLIC CONDUIT: STEEL, ONE- OR TWO-SCREW CLAMP TYPE. REINFORCED CONCRETE DUCT BANK SPANNING BETWEEN THE BUILDING <br /> 260500 COMMON WORK RESULTS FOR ELECTRICAL INSULATION, STRANDED OR SOLID COPPER CONDUCTOR. MINIMUM CONDUCTOR WALL AND A BEARING SURFACE ON UNDISTURBED EARTH. Prepared for <br /> SIZE: 3.LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT: GALVANIZED STEEL, COMPRESSION KAISER FOUNDATION <br /> A.SCOPE OF WORK TYPE. m.EMPTY RACEWAYS: PROVIDE A NYLON PULL STRING IN ALL EMPTY <br /> 1.COMPLY WITH THE GENERAL CONDITIONS OF THIS CONTRACT. THE c. NEUTRAL: #12 AWG 4.CONDUIT STRAPS: HEAVY DUTY, TWO-HOLE PRESSED STEEL. RACEWAYS. HEALTH PLAN, INC. <br /> REQUIREMENTS OF THIS SPECIFICATION ARE IN ADDITION TO THE REQUIREMENTS b. GROUND: #12 AWG 4.BOXES AND FITTINGS: NATIONAL FACILITIES SERVICES <br /> OF THE GENERAL CONDITIONS. C.OUTLET AND DEVICES BOXES POST OFFICE BOX 12916 <br /> c. PHASE CONDUCTORS (MORE THAN SIX IN A RACEWAY): #10 AWG 1.INTERIOR SURFACE-MOUNTED IN UNFINISHED AREAS: ONE-PIECE PRESSED a• GENERAL: BOXES SHALL BE SUPPORTED SECURELY AND INDEPENDENTLY. OAKLAND,CA 94604 <br /> 2.PROVIDE ALL LABOR AND MATERIAL NECESSARY TO ACCOMPLISH THE WORK MOUNT BOXES ON BUILDING SURFACES OR SUPPORT WITH TRAPEZE <br /> SPECIFIED HEREIN AND AS SHOWN ON THE DRAWINGS. d. PHASE CONDUCTORS (SIX OR LESS IN A RACEWAY): #12 AWG STEEL, ELECTRO-GALVANIZED, SIZE AND DEPTH REQUIRED BY CODE, EXCEPT HANGER AS DESCRIBED IN RACEWAY INSTALLATION. JUNCTION BOXES <br /> 4-INCH SQUARE OR 4-INCH OCTAGONAL MINIMUM. SHALL NOT BE USED UNLESS THE NUMBER OF BENDS, PULLING LENGTH, <br /> 3.COORDINATE WORK WITH ALL OTHER TRADES. 2.FEEDERS: FEEDERS SHALL BE SIZED AS SHOWN ON THE DRAWINGS AND 2.INTERIOR FLUSH-MOUNTED: SAME AS ABOVE EXCEPT PROVIDE PLASTER RING OR CIRCUIT REQUIREMENTS NECESSITATES THEIR INSTALLATION. JUNCTION <br /> 4.VISITING THE SITE AND VERIFYING EXISTING CONDITIONS PRIOR TO SUBMITTING COLOR-CODED IN ACCORDANCE WITH LIST BELOW. MAKE NO SPLICES UNLESS EXTENSION TO FINISHED SURFACE. OR PULL BOX OPENINGS MUST BE ACCESSIBLE. <br /> BID IS ENCOURAGED. REFER TO THE REQUEST FOR BID ADVERTISEMENTS FOR SHOWN ON THE PLANS. <br /> THE PRE-BID WALKTHROUGH DATE. D.JUNCTION AND PULL BOXES: INTERIOR AREAS, STEEL, SCREW COVER, CODE GAUGE b. SOUND CONTROL: WHERE BOXES ARE MOUNTED IN A COMMON WALL, <br /> 3.COLOR CODING REQUIREMENTS: 120/208 VOLT, 3-PHASE, 4-WIRE SYSTEMS AND SIZE. LARGE JUNCTION AND PULL BOXES SHALL BE FABRICATED SHEET THEY SHALL WHEREVER POSSIBLE, BE OFFSET HORIZONTALLY SO THAT THEY <br /> 5.REMOVE ALL WASTE AND RUBBISH FROM THE SITE ON A DAILY BASIS. c. PHASE A: BLACK STEEL WITH BAKED ENAMEL FINISH AND RETURN FLANGE WITH SCREW RETAINED ARE NOT MOUNTED BACK-TO-BACK. CONNECT OFFSET BOXES WITH , <br /> COVER. FLEXIBLE CONDUIT NOT TO EXCEED 18 INCHES IN LENGTH. <br /> B.WARRANTY: WORKMANSHIP AND MATERIALS SHALL BE GUARANTEED FOR A PERIOD b. PHASE B: RED <br /> OF ONE YEAR FROM THE DATE OF FINAL ACCEPTANCE BY THE OWNER. PROVIDE E.EXECUTION 260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS <br /> ADDITIONAL WARRANTY FOR VOICE/DATA SYSTEM AS NOTED ELSEWHERE. c. PHASE C: BLUE 1.GENERAL: A.GENERAL: LABEL ALL JUNCTION BOXES, TERMINAL CABINETS, ETC., WITH THE <br /> C.REGULATIONS d. NEUTRAL: WHITE CIRCUIT NUMBER OR LOW-VOLTAGE SYSTEM CONTAINED WITHIN. <br /> o. COORDINATION: THE CONTRACTOR SHALL REVIEW ALL DRAWINGS, DETAILS <br /> 1.ELECTRICAL WORK SHALL COMPLY WITH THE FOLLOWING CODES AS PRESENTLY e. GROUND: GREEN AND ELEVATIONS PRIOR TO ROUGH-IN. WHERE EQUIPMENT IS FURNISHED B.EQUIPMENT NAMEPLATES: SHALL BE ENGRAVED IN 1/16 INCH THICK PHENOLIC <br /> APPLICABLE: BY OTHERS, THE CONTRACTOR SHALL ASCERTAIN THE PROPER VOLTAGE, LETTERS A MINIMUM OF 3/16 INCH HIGH. COLORING SHALL BE WHITE LETTERS ON Hellmuth,Obata&Kassabaum,Inc. <br /> f. TRAVELERS: YELLOW (FOR 3- AND 4-WAY SWITCHING) 1218 Third Avenue,Suite 1315 <br /> o. NATIONAL ELECTRICAL CODE (NEC) LOAD AND CONNECTION REQUIREMENTS PRIOR TO ROUGH-IN. BLACK BACKGROUND FOR NORMAL EQUIPMENT AND WHITE LETTERS ON RED Seattle,WA 98101 USA <br /> g. CONTROLS: BLACK WITH WIRE NUMBERS ON EACH CONDUCTOR b. MATERIALS: ALL MATERIALS OF A SPECIFIC TYPE SHALL BE PROVIDED BY BACKGROUND FOR EMERGENCY EQUIPMENT. t+1 206 493 1771 f+1 206 493 1778 <br /> b. WASHINGTON STATE NONRESIDENTIAL ENERGY CODE (NREC) WITH THE CITY 4.COLOR CODING REQUIREMENTS: 277/480 VOLT, 3-PHASE, 4-WIRE SYSTEMS: THE SAME MANUFACTURER THROUGHOUT THE PROJECT. 262416 PANELBOARDS &"lB1ec1ua1prope�"gM13e3eNeO <br /> o. PHASE A: BROWN 2.RACEWAY TYPES: INSTALL RACEWAY TYPES AND SIZES AS LISTED BELOW: ® <br /> OF EVERETT AMENDMENTS A.EXISTING PANELBOARDS: PROVIDE NEW BRANCH CIRCUIT BREAKERS, INCLUDING In°Association with <br /> c. WASHINGTON ADMINISTRATIVE CODE (WAC) WITH THE CITY OF EVERETT ASSOCIATED MOUNTING HARDWARE TO SERVE NEW LOADS. <br /> o. RIGID METALLIC CONDUIT: IN CONCRETE AND MASONRY AND EXPOSED <br /> AMENDMENTS b. PHASE B: ORANGE Mortenson <br /> EXTERIORS. 262816 ENCLOSED SWITCHES AND CIRCUIT BREAKERS General Co anlnr <br /> d. LOCAL CITY OF THE CITY OF EVERETT AND STATE CODES AND c. PHASE C: YELLOW A.APPROVED MANUFACTURER'S: GENERAL ELECTRIC, SIEMENS, CUTLER-HAMMER OR 10230 NE Kirkland, Points n0Drrive,Suite 300 <br /> 33 <br /> REGULATIONS d. NEUTRAL: GRAY b. ELECTRICAL METALLIC TUBING (EMT): ALL AREAS OTHER THAN ABOVE. SQUARE D. <br /> MAY BE USED FOR FEEDERS WITH INTEGRAL GREEN GROUND CONDUCTOR. <br /> 2.PERMITS: OBTAIN AND PAY FOR ALL REQUIRED PERMITS. e. GROUND: GREEN ConXtech,Inc <br /> c. FLEXIBLE METALLIC CONDUIT: RECESSED FIXTURE CONNECTIONS, INTERIOR B.SINGLE-PHASE MOTOR: MOTORS 1/3 HP OR LESS PROVIDE WITH TOGGLE-TYPE, StNaural Fabricator <br /> 3.SAFETY MEASURES: PROVIDE A SAFE ENVIRONMENT TO PROTECT EMPLOYEES f. TRAVELERS: LAVENDER (FOR 3- AND 4-WAY SWITCHING) CONCEALED EQUIPMENT CONNECTIONS, EXPANSION JOINTS AND SOUND 20-AMP, 120-VOLT RATING, SPECIFICATION-GRADE DISCONNECT SWITCHES. 6701 icon Center Parkway,Suite 150 <br /> AND ALL OTHERS FROM INJURY. COMPLY WITH "SAFETY AND HEALTH CONTROL. NOT TO BE USED EXPOSED INSTALLATIONS WITHIN THE Pleasanton,CA 94566 <br /> REGULATIONS FOR CONSTRUCTION," VOLUME 36, NO. 75, PART II, OF THE g. CONTROLS: BLACK WITH NUMBERS ON EACH CONDUCTOR BUILDING. C.THREE-PHASE MOTOR: MOTORS 1/2 HP AND LARGER PROVIDE WITH <br /> FEDERAL REGISTER BY THE U.S. DEPARTMENT OF LABOR. HORSEPOWER-RATED, HEAVY-DUTY, 30 AMPERE MINIMUM, 3-POLE DISCONNECT KPFS Consulting nEngineers <br /> 5.SPLICES AND TERMINATIONS: LIGHTING AND RECEPTACLE BRANCH CIRCUIT d. LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT: EXTERIOR EQUIPMENT SWITCHES. <br /> 1601 Fifth Avenue,Suite 1600 <br /> D.SUBMITTAL AND SHOP DRAWINGS: PRIOR TO INSTALLATION, SUBMIT CATALOG DATA CONDUCTORS UP TO NO. 10 AWG SHALL BE SPLICED WITH WING NUT TYPE CONNECTIONS. Seattle,WA9S101 <br /> FOR FILL STATION, CONTROL PANEL AND ANY OTHER WIRING DEVICES IN CONNECTORS. D.EQUIPMENT DISCONNECTS: SHALL BE FUSED OR NON-FUSED AS REQUIRED BY <br /> ELECTRONIC PDF FORMAT. e. MINIMUM RACEWAY SIZE SHALL BE 3/4 INCH, EXCEPT FOR RACEWAYS THE EQUIPMENT MANUFACTURER, RATED AT 125 PERCENT OF FULL LOAD Mazzetti <br /> 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS WITH NO MORE THAN THREE #12 AWG CONDUCTORS WHICH MAY BE 1/2 NAMEPLATE AMPERAGE OR RATED HORSEPOWER, HEAVY-DUTY TYPE.A MEP+FP Engineering <br /> E.OPERATIONS AND MAINTENANCE MANUALS: PROVIDE MAINTENANCE AND OPERATIONS 2013 4th Avenue,Suite 200 <br /> DATA FOR ALL ELECTRICAL EQUIPMENT AND SIGNAL AND COMMUNICATIONS SYSTEMS A.GENERAL: PROVIDE THROUGH THE ENTIRE ELECTRICAL SYSTEM. A SEPARATE 3.RACEWAY INSTALLATION: E.DISCONNECTS: PROVIDE DISCONNECTS AT ALL MOTORS AND OTHER EQUIPMENT Seattle,WA 98121 <br /> IN ELECTRONIC PDF FORMAT. GREEN EQUIPMENT GROUNDING CONDUCTOR SHALL BE PROVIDED IN ALL LIGHTING ITEMS UNLESS THE EQUIPMENT HAS A SELF-CONTAINED, CODE APPROVED <br /> AND POWER RACEWAYS. c. CONCEALMENT: ALL RACEWAYS SHALL BE CONCEALED IN FINISHED DISCONNECTING METHOD. EQUIPMENT DISCONNECTS SHALL BE FUSED OR <br /> F.RECORD DRAWINGS: CORRECTIONS AND CHANGES MADE DURING THE PROGRESS AREAS. WHERE EXISTING WALL SURFACES ARE INACCESSIBLE, SURFACE NON-FUSED AS REQUIRED BY THE EQUIPMENT MANUFACTURER. Key Plan <br /> OF THE WORK SHALL BE NEATLY RECORDED AS ACTUALLY INSTALLED FOR B.BONDING: INSULATED GROUNDING BUSHINGS SHALL BE INSTALLED TO BOND ALL METAL RACEWAYS FOR THESE EXCEPTIONS MAY BE PROVIDED WHEN <br /> AS-BUILT RECORDS. SUBMIT TO THE ARCHITECT UPON PROJECT COMPLETION. FEEDER CONDUITS TO THE SWITCHBOARD GROUND BUS OR PANEL GROUND BUS AT APPROVED. END OF ELECTRICAL SPECIFICATIONS <br /> BOTH ENDS OF FEEDER RACEWAYS. INSULATED GROUNDING BUSHINGS SHALL BE <br /> G.CERTIFICATES OF INSPECTION: SUBMIT SIGNED-OFF PERMITS FROM THE CODE INSTALLED TO BOND ALL FEEDER CONDUITS TO THE GROUND BUS OR PANEL b. EXPOSED RACEWAYS: INSTALL EXPOSED RACEWAYS AS HIGH AS <br /> ENFORCING AGENCIES TO THE OWNER UPON PROJECT COMPLETION. ENCLOSURES AT BOTH ENDS OF THE RUNS. POSSIBLE, ABOVE DUCTWORK, PARALLEL OR AT RIGHT ANGLES TO BUILDING N <br /> LINES. S <br /> H.PRODUCT LISTING OR LABELING: ALL ELECTRICAL EQUIPMENT SHALL BE LISTED C.NEUTRAL GROUNDING: THE NEUTRAL POINT OF ALL TRANSFORMERS SHALL BE <br /> AND LABELED BY UNDERWRITERS' LABORATORIES, INC. SOLIDLY GROUNDED TO THE GROUNDING SYSTEM AND TRANSFORMER ENCLOSURE c. EXPANSION AND EARTHQUAKE JOINTS: RACEWAYS SHALL NOT BE <br /> WITH CODE SIZE GROUND CONDUCTORS. THE NEUTRAL BUS IN EACH PANELBOARD INSTALLED IN CONCRETE SLAB OR WALL CONSTRUCTION WHEN PASSING <br /> I. MATERIAL AND EQUIPMENT: ALL MATERIALS AND EQUIPMENT SHALL BE NEW SHALL BE ISOLATED FROM GROUND. THE NEUTRAL SHALL BE GROUNDED ONLY AT THROUGH AN EXPANSION OR EARTHQUAKE JOINT. RACEWAYS SHALL BE ' <br /> UNLESS NOTED OTHERWISE. PROTECT ALL MATERIALS AND EQUIPMENT FROM A SINGLE POINT AT THE MAIN SWITCHBOARD OR AT SEPARATELY DERIVED SYSTEM INSTALLED IN FURRED OR SUSPENDED CEILING SPACES WITH A MINIMUM OF <br /> DAMAGE OR CORROSION. TRANSFORMERS. 24 INCHES OF FLEXIBLE CONDUIT CROSSING THE EXPANSION OR <br /> J.CUTTING AND PATCHING: PROVIDE ALL REQUIRED CUTTING AND PATCHING FOR THE D.RECEPTACLE GROUNDING: CONNECT THE GROUND TERMINAL OF ALL RECEPTACLES EARTHQUAKE JOINTS. <br /> ELECTRICAL WORK. BY UTILIZING A SEPARATE GROUNDING CONDUCTOR BETWEEN THE RECEPTACLE d. ROUTING: ALL RACEWAYS SHALL BE INSTALLED PARALLEL OR AT RIGHT Professional Seals <br /> GROUNDING SCREW AND THE GROUND CONDUCTOR PROVIDED IN THE BRANCH ANGLES TO THE BUILDING CONSTRUCTION UNLESS PROHIBITED BY A <br /> K.EXISTING CONDITIONS CIRCUIT. INTEGRAL MOUNTING STRAPS WITHIN THE RECEPTACLE CONNECTED TO PHYSICAL OBSTRUCTION. <br /> 1.GENERAL: SPECIFIC SCOPE OF DEMOLITION WORK AND OPERATING CONDITIONS THE DEVICE MOUNTING STRAPS ARE NOT APPROVED AS A GROUNDING METHOD. <br /> TO BE ENCOUNTERED SHALL BE VERIFIED BY ON-SITE REVIEW PRIOR TO e. RACEWAY SUPPORTS: RACEWAYS SHALL BE SUPPORTED WITH z <br /> SUBMITTING BID. DEMOLITION WORK IN GENERAL IS NOTED OR SHOWN ON E.FLEXIBLE CONDUIT GROUNDING: PROVIDE A SEPARATE GROUNDING CONDUCTOR IN HEAVY-DUTY, ONE-HOLE, PRESSED STEEL STRAPS ON INTERIOR SURFACES. <br /> ALL FLEXIBLE CONDUIT RUNS INCLUDING WATERTIGHT FLEXIBLE CONDUIT WITH SUPPORT PENDANT-MOUNTED RACEWAYS ON 3/8-INCH ROD WITH <br /> THE DOCUMENTS BASED UPON AVAILABLE 'DRAWINGS OF RECORD" AND MAY / �csre °g mzRe° <br /> NOT SHOW THE ACTUAL CONDITIONS AS THEY PRESENTLY EXIST. INTEGRAL GROUNDING STRAPS. INSTALL GROUND CONDUCTOR INSIDE CONDUIT WITH PEAR-SHAPED HANGER OR TRAPEZE-TYPE HANGER WITH 3/8-INCH ROD oNaL wee oxpt 'G3ltglya <br /> UNGROUNDED CONDUCTORS. (MINIMUM) AND 1-5/8-INCH SQUARE PREFORMED CHANNEL AND PIPE <br /> 2.OWNER-RETAINED EQUIPMENT: THE OWNER MAY WISH TO RETAIN CERTAIN F.GROUND CONNECTIONS: GROUND CONNECTIONS TO BUILDING STEEL, GROUND CLAMPS. PARALLEL, SURFACE-MOUNTED RACEWAYS SHALL BE SUPPORTED <br /> SPECIFIC ITEMS SCHEDULED FOR DEMOLITION. THE CONTRACTOR SHALL RODS AND CABLE TAPS SHALL UTILIZE AN EXOTHERMIC WELDING PROCESS. FROM 1-5/8-INCH SQUARE PREFORMED CHANNEL AND PIPE CLAMPS. ALL No. Description Data <br /> CAREFULLY REMOVE THESE ITEMS, PROVIDE PROTECTION AND PACKAGING AS CADWELD, ERICO PRODUCTS, INC., OR APPROVED EQUAL. FITTINGS AND SUPPORTS SHALL BE HOT-DIP GALVANIZED IN EXTERIOR PERMITSET 03rIarz0 <br /> MAY BE REQUIRED TO PROTECT THE EQUIPMENT AND TURNOVER SAID AREAS. <br /> EQUIPMENT TO THE OWNER AT A PLACE DESIGNATED ON THE JOBSITE. ANY 260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS <br /> EQUIPMENT THAT THE OWNER DOES NOT DESIRE TO RETAIN SHALL BECOME A RACEWAYS f. INDEPENDENT SUPPORT: CONDUITS SHALL NOT BE SUPPORTED FROM <br /> . <br /> THE PROPERTY OF THE CONTRACTOR AND BE REMOVED FROM THE SITE. THE CEILING SUSPENSION SYSTEM, DUCTS, PIPES OR OTHER SYSTEMS <br /> 3.UNUSED CONDUIT AND WIRING: ALL UNUSED CONDUCTORS RESULTING FROM 1.RIGID METALLIC CONDUIT: ZINC-COATED STEEL WITH FULL THREADED FOREIGN TO THE ELECTRICAL INSTALLATION. THE ENTIRE ELECTRICAL <br /> THIS PROJECT SHALL BE REMOVED. ALL UNUSED CONDUIT SHALL BE <br /> CONNECTIONS. INSTALLATION SHALL BE KEPT INDEPENDENT FROM ANY OTHER TRADE. <br /> REMOVED EXCEPT WHERE LOCATED IN OR ABOVE EXISTING CONSTRUCTION 2.ELECTRICAL METALLIC TUBING (EMT): ZINC-COATED STEEL. g. PULL BOXES WITH COVERS: SHALL BE PROVIDED AS SHOWN ON THE <br /> WHICH IS NOT BEING ALTERED AND WOULD REQUIRE REMOVAL AND DRAWINGS OR AS REQUIRED BY CODE. ALL PULL BOXES SHALL BE <br /> REPLACEMENT OF THE EXISTING CONSTRUCTION. 3.FLEXIBLE METALLIC CONDUIT: HELICALLY WOUND GALVANIZED STEEL, SECURELY LOCATED SO AS TO BE ACCESSIBLE. <br /> 4.EXISTING RACEWAYS: PROPERLY SUPPORT ALL EXISTING RACEWAYS ABOVE INTERLOCKED, RWS (REDUCED WALL STEEL) TYPE. h. FLEXIBLE CONDUIT: SHALL BE USED ONLY FOR LIGHTING FIXTURE <br /> SUSPENDED CEILINGS WHERE WORK IS TAKING PLACE. VERIFY EXTENT OF 4.LIQUIDTIGHT FLEXIBLE METALLIC CONDUIT: HELICALLY WOUND, GALVANIZED PIGTAILS IN ACCESSIBLE CEILINGS, FLUSH-MOUNTED SPEAKER PIGTAILS IN <br /> WORK PRIOR TO SUBMITTING BID. STEEL, INTERLOCKED, WITH INTEGRAL GROUND CONDUCTOR AND OVERALL PVC ACCESSIBLE CEILINGS, SOUND CONTROL, MOTOR CONNECTIONS AND AT <br /> L.CONTINUITY OF SERVICE: PERMANENTLY REROUTE OR RELOCATE EXISTING WIRING JACKET. BUILDING EXPANSION JOINTS AS SPECIFIED. ANY OTHER PROPOSED USE <br /> OF FLEXIBLE CONDUIT MUST BE APPROVED PRIOR TO INSTALLATION. <br /> AND/OR EQUIPMENT WHICH IS IN CONFLICT WITH EXISTING BUILDING ALTERATIONS B.FITTINGS <br /> AND WHICH IS REQUIRED TO BE MAINTAINED IN USE. LPENETRATIONS: RACEWAYS WHICH PASS THROUGH BUILDING ROOF, <br /> 1.RIGID METALLIC CONDUIT: EXTERIOR WALLS OF BUILDING ABOVE OR BELOW GRADE AND FLOOR SLABS <br /> M.PHASE ROTATION: CHECK CONNECTIONS TO ALL NEW AND EXISTING THREE-PHASE a. COUPLINGS: THREADED-METALLIC TYPE OF THE SAME MATERIAL AS THE ON GRADE SHALL BE SEALED ON THE INTERIOR SIDE OF THE BUILDING <br /> EQUIPMENT FOR PROPER PHASE ROTATION. DISCONNECT ALL DEVICES THAT COULD CONDUIT. USING NON-HARDENING SEALING COMPOUND AFTER ALL CONDUCTORS HAVE <br /> BE DAMAGED BY THE APPLICATION OF VOLTAGE OR REVERSED PHASE SEQUENCE. BEEN INSTALLED IN THE RACEWAY. SEALING MATERIAL SHALL BE <br /> N.ANCHORAGE AND BRACING: PROVIDE COMPLETE SEISMIC ANCHORAGE AND BRACING b. LOCKNUTS: STEEL UP TO 2"INCHES, MALLEABLE IRON FOR 2-1/2 SPECIFICALLY DESIGNED FOR ELECTRICAL WIRING SYSTEMS. <br /> FOR THE LATERAL AND VERTICAL SUPPORT OF CONDUIT, LIGHT FIXTURES, AND INCHES AND LARGER. j. CONDUIT PASSING THROUGH BUILDING ROOF: PROVIDE A 4 LB. LEAD <br /> ELECTRICAL EQUIPMENT AS REQUIRED BY THE INTERNATIONAL BUILDING CODE. c. BUSHINGS: BAKELITE OR PLASTIC UP TO 2", MALLEABLE IRON WITH PLUMBING VENT FLASHING WITH A COUNTER FLASHING ATTACHED ABOVE <br /> O.FIRESTOPPING: PROVIDE FIRE STOPPING FOR ALL PENETRATIONS THROUGH RATED INSULATING COLLAR FOR 2-1/2 INCHES AND LARGER. USING A GALVANIZED STEEL CLAMP. <br /> WALLS, CEILINGS AND FLOORS. d. UNIONS: ZINC-PLATED MALLEABLE IRON, THREE PIECE CONDUIT k. CONDUIT PENETRATING MEMBRANES: ALL CONDUITS PENETRATING WALLS <br /> P.PAINTING: PAINT ALL EXPOSED RACEWAYS, EXCEPT SMR, IN FINISHED AREAS TO COUPLING. OR SLABS WITH MEMBRANES SHALL BE INSTALLED WITH APPROVED <br /> MATCH ADJACENT SURFACES. MEMBRANE CLAMPING DEVICES IN ORDER TO PROVIDE NECESSARY SEAL. <br /> e. ELECTRICAL METALLIC TUBING (EMT): STEEL SET-SCREW TYPE. FITTINGS (.EXTERIOR WALLS: CONDUITS PASSING THROUGH EXTERIOR WALLS BELOW <br /> 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 2" AND LARGER SHALL BE STEEL AND MAY BE SETSCREW TYPE CONTAINING KP Project N. CAP02O4G7 <br /> DUAL SETSCREWS ON EACH SIDE OF COUPLING. GRADE AND/OR BRIDGING AN AREA WHICH WAS PREVIOUSLY EXCAVATED HOK Project No: <br /> A.WIRE AND CABLE: AND BACKFILLED SHALL BE RIGIDLY SUPPORTED BY A STRUCTURALLY Sheet Title: <br /> ELECTRICAL <br /> SPECIFICATIONS <br /> 24 Sheet Number <br /> M E4 .0 <br />