Calculation: RTU Analysis 7_16 {5-7} <br /> Unit Anchorage to Structure-Design and Analysis: <br /> Ty'Direction Loading(Overturning about the X-X Axis) <br /> Wind Loading: Seismic Loading: <br /> FY: 1725.6 lb @ 2.542 ft above top of curb FY: 665.8 lb @ 3.389 ft above top of curb <br /> At Unit to Curb Connection: At Unit to Curb Connection: <br /> OTM: 4386 lb-ft OTM: 2256 lb-ft <br /> Resist.OTM: 2650 lb-ft Resist.OTM: 2650 lb-ft <br /> Tension: 524.6 lb(ASD,LC 0.6D+0.6W) Tension: 90.79 lb(ASD,LC 0.6D+0.7E) <br /> Compression: 1196 lb(ASD,LC 1.OD+0.6W) Compression: 957.6 lb(ASD,LC 1.OD+0.7E) <br /> At Curb to Structure Connection: At Curb to Structure Connection: <br /> OTM: 6399 lb-ft OTM: 3033 lb-ft <br /> Resist.OTM: 2650 lb-ft Resist.OTM: 2650 lb-ft <br /> Tension: 798.1 lb(ASD,LC 0.6D+0.6W) Tension: 213.9 lb(ASD,LC 0.6D+0.7E) <br /> Compression: 1469 lb(ASD,LC 1.OD+0.6W) Compression: 1081 lb(ASD,LC 1.OD+0.7E) <br /> Unit Connection to Curb: (Worst Case) <br /> Try: #10 @ 8"o/c with 43mil material <br /> Tallow: 109 lb Eff.Tension Fasteners: (12) -> 43.72 lb/fastener 0.401 OK <br /> Vallow: 263 lb Eff.Shear Fasteners: (15) -> 67.89 lb/fastener 0.258 OK <br /> Unity Check: 0.659 OK <br /> Curb Connection to Structure: (Worst Case) <br /> Try: 1/2"dia bolts to angle below Eff.Tension Fasteners: (2) -> 399.1 lb/fastener 0.09 OK <br /> Tallow: 4,418 lb Eff.Shear Fasteners: (8) -> 129.4 lb/fastener 0.049 OK <br /> Vallow: 2,651 lb <br /> Unity Check: 0.139 OK <br /> 'Fx'Direction Loading(Overturning about the Y-Y Axis) <br /> Wind Loading: Seismic Loading: <br /> FX: 1039.3 lb @ 2.542 ft above top of curb Fx: 665.8 lb @ 3.389 ft above top of curb <br /> At Unit to Curb Connection: At Unit to Curb Connection: <br /> OTM: 2641 lb-ft OTM: 2256 lb-ft <br /> Resist.OTM: 4400 lb-ft Resist.OTM: 4400 lb-ft <br /> Tension: 144.9 lb(ASD,LC 0.6D+0.6W) Tension: N/A lb(ASD,LC 0.6D+0.7E) <br /> Compression: 816.1 lb(ASD,LC 1.OD+0.6W) Compression: 815.4 lb(ASD,LC 1.OD+0.7E) <br /> At Curb to Structure Connection: At Curb to Structure Connection: <br /> OTM: 3854 lb-ft OTM: 3033 lb-ft <br /> Resist.OTM: 4400 lb-ft Resist.OTM: 4400 lb-ft <br /> Tension: 244.1 lb(ASD,LC 0.6D+0.6W) Tension: 22.71 lb(ASD,LC 0.6D+0.7E) <br /> Compression: 915.3 lb(ASD,LC 1.OD+0.6W) Compression: 889.5 lb(ASD,LC 1.OD+0.7E) <br /> Unit Connection to Curb: (Worst Case) <br /> Try: #10 @ 8"o/c with 43mil material <br /> Tallow: 109 lb Eff.Tension Fasteners: (8) -> 19.01 lb/fastener 0.174 OK <br /> Vallow: 263 lb Eff.Shear Fasteners: (24) -> 25.98 lb/fastener 0.099 OK <br /> Unity Check: 0.273 OK <br /> Curb Connection to Structure: (Worst Case) <br /> Try: 1/2"dia bolts to angle below Eff.Tension Fasteners: (2) -> 122.1 lb/fastener 0.028 OK <br /> Tallow: 4,418 lb Eff.Shear Fasteners: (8) -> 77.95 lb/fastener 0.029 OK <br /> Vallow: 2,651 lb <br /> Unity Check: 0.057 OK <br /> 13228 NE 20th St.,Suite 100,Bellevue,WA 98005 425 614-0949 <br /> Project: Casino Road RTU Pg.No: A-6 <br /> AU E Address: 2525 Casino Rd,Everett,WA 98204 Date: 12/22/2023 <br /> Client: ACCO Engineered Systems Job No.: 23454 <br />